Continuity of protective bonding conductors & equipotential bonding explained

Поділитися
Вставка
  • Опубліковано 6 сер 2024
  • In this video i demonstrate the continuity of protective bonding conductors test and explain why we use equipotential bonding as best as i can.
    T I M E S T A M P S ⏰
    0:00 - Intro
    0:55 - What the regs say
    3:15 - What is earthing and bonding?
    4:29 - What is an extraneous conductive part?
    5:01 - Why do we need bonding?
    6:27 - What is electrical potential?
    8:28 - What is supplementary bonding?
    9:53 - To bond or not to bond
    12:06 - Safe isolation
    13:12 - Diverted neutral currents
    15:40 - THE TEST PROCEDURE
    18:30 - What if i cant find the bond?
    20:05 - Making a good connection
    21:05 - Massive earth cables
    22:13 - Designing bonding conductor cables
    22:57 - Different bonding clamp types
    24:09 - Parallel paths
    26:06 - Outro
    If you enjoy electrical content please subscribe to the channel and checkout my links below 👇
    M Y W E B S I T E ⚡
    residualcurrent.com/
    M Y L O A D O U T 🛠️
    residualcurrent.com/pages/loa...
    B I G B O O T S D I S C O U N T 🥾
    bigboots.co.uk/?ref=4s3760y77o - Use code RESIDUAL
    U N I L I T E D I S C O U N T 🔦
    unilite.co.uk/?ref=RESIDUAL - Use code RESIDUAL
    J O I N T H E C H A N N E L 🤝
    / @residualelectrical
    I N S T A G R A M 📷
    / residualcurrent
    T I K T O K ♪
    vm.tiktok.com/ZM86U2jjG/
    The works carried out in the video and the opinions shared are my own, and not representative of the associates and companies in the video.
    This content is purely for entertainment purposes and is in no way a "how to", tutorial or educational video.
    Please consult an electrician when dealing with any electrical installations.
    #electricianlife #electrical #electricalengineering

КОМЕНТАРІ • 45

  • @craigtonge455
    @craigtonge455 2 роки тому +4

    Sorry dude. Just watching it again. You've got a talent for training! I was in corporate training and development for years before seeing the light and becoming and sparky. You've got talent. Just saying.

  • @electrician247
    @electrician247 2 роки тому +6

    These videos are so good Mike. I am sure everyone in A121 is following anyways but I will be directing them at this! Keep it up mate.

  • @rondo122
    @rondo122 2 роки тому +4

    What a high quality video this is! Congratilations, this is real high standard educational content! Many thanks

  • @andyclark1426
    @andyclark1426 2 роки тому +4

    Excellent explanation and video mate! Stop putting yourself down, you explain it in the way we understand and that’s far better than some professor with a blackboard, I’m glad you spoke about DNC, it’s a big topic up here in Scotland as our network is on its arse (I’d imagine rest of uk is same), i had some right arguments with so-called electrical engineers when I was a generator engineer, some of the gurus never used earth rods at generator stating that the generator was TNC-s....... the outgoing side was but the alternator is the star point so needs a rod, once again Mikey thank you for doing these videos

  • @keithhand3380
    @keithhand3380 2 роки тому +2

    Really well presented.
    Like someone said in a previous comment, you have a great way of explaining in normal speak and not sounding like a professor.
    Well done 👏

  • @kingofthetrowel1725
    @kingofthetrowel1725 2 роки тому +1

    Seriously mate I’m loving your videos, very informative for myself as an adult learner🙌🏻🙌🏻 keep them coming mate and thank you 👍👍

  • @andystaineselectrical4847
    @andystaineselectrical4847 2 роки тому +3

    Cracking explanation of earthing and bonding!! Loved your detailed description and useful analogies.. I've shared with our apprentices as I think it will be super helpful for them to get their heads around what is a very tricky concept indeed!! Nice one 👍 👌

  • @richiethegod
    @richiethegod 2 роки тому +1

    Great video, clear explanation Thankyou for your content!
    Legend

  • @michaelcostello6991
    @michaelcostello6991 11 місяців тому

    Very good video. The photos add great clarity to your lectures for apprentices etc. Please keep adding those type of photos or wiring diagrams for that extra clarity. The don to earth "Normal Speak " as someone else mentions below is great and not aimed at engineers. Thanks again

  • @craigtonge455
    @craigtonge455 2 роки тому

    Cracking video. I wish you were around when I was learning this stuff. Keep it up.

  • @sergiofernandez3725
    @sergiofernandez3725 2 роки тому +1

    Good video Mike. I enjoyed and learnt from it. Keep it going

  • @ForTheBirbs
    @ForTheBirbs 2 роки тому

    Fantastic video Mike! So well explained. I'm in a unit block in Sydney and our water meter seal failed. The water authority changed the meter and I was interested to see what they'd do to protect themselves when removing the meter. They had a test / monitoring device which they clamped on to the incoming and outgoing water pipe. I wish I'd got the name of the bit of kit. I was happy to see no issues on exported or imported fault current. Cheers

  • @alexsanderson6648
    @alexsanderson6648 2 роки тому

    Awesome content mate, taking some of this knowledge into my new job as a Trainee spark ( big ginge from Kettering)

  • @simonmadahar5463
    @simonmadahar5463 2 роки тому

    Awesome UA-cam mate, very helpful

  • @user-tl1xm9vk8c
    @user-tl1xm9vk8c 9 місяців тому

    Excellent

  • @no_short_circuit
    @no_short_circuit 2 роки тому

    John Ward in the making? Great explanation.

  • @hassanhasse8928
    @hassanhasse8928 Рік тому

    Thanks

  • @Mike_5
    @Mike_5 2 роки тому +1

    Nice video but small anal fact here that if you coil the Earth cable you can induce noise into the CPC circuit as it acts like a sort of tuned radio aerial which can make your RCBO's trippy

  • @motivationhero7
    @motivationhero7 2 роки тому

    Diverted neutral current...hats off

  • @ja_adam_
    @ja_adam_ Рік тому

    Can you do a video on how you test if a part is actually extraneous using the 22k ohm reading

  • @geraldelwood9660
    @geraldelwood9660 Рік тому

    Grt Info. One question : is a surface tester the only way to check for a safe Neutral/MET ie no Imported voltage due to a diverted neutral on a neighbouring property?

  • @tonyclark9851
    @tonyclark9851 2 роки тому +1

    For a young lad you are very knowledgeable you should look into doing traing courses like the 18th edition and ev charging

  • @ja_adam_
    @ja_adam_ Рік тому

    Mike, what determines if you need supplementary bonding? Are you always supposed to actually test between a tap and metallic light for example ?

  • @Eicles
    @Eicles Рік тому

    Where do you get your signs for the MET (shown at 0:48)? I looked online but they’re really expensive. They look much better than the stickers though because they can’t fall off! :-)

  • @barghtubereza
    @barghtubereza 3 місяці тому

    Hi
    What is the reference of 0.05ohm for bonding wire?

  • @hippo-potamus
    @hippo-potamus Рік тому

    Would it be better to just test the voltage and ensure all bonded parts have the same resting voltage?

  • @mathman0101
    @mathman0101 2 роки тому

    Also resistance values depend on temperature and humidity and any significant metal part not connected to MET should be labeled describing decision why it could also be noted on an EICR. The issue of fortuitous connections to earth of metal parts is an important one and the issue of importing and exporting potential due to broken PEN is a very important one and should be assessed but normal electricians are limited here as it’s an issue somewhat out of their control, and dare I say perhaps DNOs but without maintenance and wider testing by DNOs the extent of the problem will remain a mystery.

  • @tumelokedirile5652
    @tumelokedirile5652 Рік тому

    So basically, whatever that is metallic in the house must be bonded to the earth?

  • @Satters
    @Satters 2 роки тому +3

    bonding leads should not be coiled, as it creates inductive impedance, shortest and most direct route for all earthing and bonding conductors is best practice

    • @finnl1525
      @finnl1525 2 роки тому +1

      looks nice though lol

    • @retrozmachine1189
      @retrozmachine1189 2 роки тому +3

      @@residualelectrical At 50hz, 2/3 of bugger all. At high frequencies, a lot. I used to work in / around telecommunications and have seen curled earth bonding between racks. Those very same racks also had lightning damaged equipment. Racks without curled up bonding all survived. I've seen it time and time again. Curled wiring, even wiring with sharp angled bends instead of smooth curved radii all put the impedance way up when it comes to impulse current and that is a significant contributor to things failing when Mr Lightning comes knocking.

    • @Satters
      @Satters 2 роки тому +2

      @@residualelectrical ​ it's not the resistance but the raised impedance during a transient or surge of high potential difference at harmonic frequencies which can result in damaged electronic equipment

  • @leestorey18
    @leestorey18 2 роки тому

    What's the purpose of spiraling the cable like that?

    • @1simo93521
      @1simo93521 3 місяці тому

      Maybe to give it some give if you need to move pipes a bit.

  • @aaronmdjones
    @aaronmdjones Рік тому

    Disconnecting the Earth for London xD

  • @trp2413
    @trp2413 8 місяців тому

    16 minutes to get to the test 😮

  • @mb-electricalservices
    @mb-electricalservices 2 роки тому +1

    Just thought I would mention that where a PVC water pipe is utilised at the point of entry to a domestic installation, you need to be certain that the water pipes do not re-enter the ground at any point within the installation. If that is the case, you will need to bond the water pipe regardless of it being PVC or not.
    Been a spark for 25 years and things like this still trip me up.

    • @kingofthetrowel1725
      @kingofthetrowel1725 2 роки тому

      I’ve glad you have put this mate, I’m not a sparks yet but my understanding was “oh if it’s plastic don’t bond it” but then I have a situation at my house where yes it comes in plastic,but bit further down the line a copper pipe goes into the integral garage through the ground as you say is re entering.when I get my mft I’ll be testing the bugger 😂😂🙌🏻🙌🏻

    • @mb-electricalservices
      @mb-electricalservices 2 роки тому +1

      @@kingofthetrowel1725 Yeah, it can trip you up mate. The way I see it, if it's easy enough to bond it, just bond it. It's great that you're aware of the situation at your property though. 👍

    • @kingofthetrowel1725
      @kingofthetrowel1725 2 роки тому

      @@mb-electricalservices nice one thanks mate 🙌🏻🙌🏻

  • @michaelsmith9308
    @michaelsmith9308 Рік тому

    So basically you need a license to become an attorney to read those legal requirements correctly, then you need a license to become an engineer to apply the training, then you need a license as a doctor so you can treat yourself if you make a mistake!

  • @Ibrahim-vt2tz
    @Ibrahim-vt2tz 2 дні тому

  • @richardbradley7988
    @richardbradley7988 2 роки тому +1

    Nice one mate! 🤌🏻 imported diverted neutrals much more dangerous too if your neighbours house is on a different supply phase!!

    • @richardbradley7988
      @richardbradley7988 2 роки тому +1

      @@residualelectrical cracking channel mate! Looking forward to more of the same! 👍

  • @Ibrahim-vt2tz
    @Ibrahim-vt2tz 2 дні тому

    English way of explaining things
    Does not work for every one
    It would be good if we could see real testing more around property practically I mean
    This way of explaining. Is colledge way for
    Students you could be good trainer and teacher. For sure
    If some one who just started college say like few months
    Still would not get what you saying
    Even if they have English as first language
    But it is good for some one who is electrician or work as electrician for company or self employed
    If you deal with Costomer directly and deal with work as well as main guy
    I mean if you are director
    Then you must know all this. All of it
    And I think it take 5 years for students here to understand electric in and out also uk work system and style
    In whole is good explanation
    Study make perfect and learning and learning
    Thank you. ❤