Wet Venting Video:4 - Sizing an Advanced System

Поділитися
Вставка
  • Опубліковано 4 лип 2024
  • This video talks about sizing an advanced wet vent system. It covers code clause 2.5.2.1.(1)-e,f
    All references are from the 2015 National Plumbing Code of Canada.

КОМЕНТАРІ • 13

  • @repairitdontwreckit4257
    @repairitdontwreckit4257 3 місяці тому +2

    I am a retired master plumber, plumbing inspector and plumbing instructor. Your series of videos are excellent. I have yet to see anything on utube that comes close to yours. I am Canadian plumber. I understand the National Plumbing Code of Canada. You are a natural teacher. Explanations are bang on.

  • @marcuspearson9509
    @marcuspearson9509 3 роки тому +1

    Great video! Thank you!

  • @VKP604
    @VKP604 2 роки тому

    thank you very much for the video!

  • @jetdelacruz2840
    @jetdelacruz2840 2 роки тому

    Thank you.

  • @steveprendergast356
    @steveprendergast356 Рік тому

    Hi Kelly. Can two separate wet vented sections from opposite ends of a house drain into the main drain and have their vents join in the attic before leaving the building through the roof. Thanks. Steve

  • @folsomatgranitebay5215
    @folsomatgranitebay5215 7 місяців тому

    Would anyone know when a vent over a sink isn’t required to be over flood level rim….?

  • @dantully6087
    @dantully6087 2 роки тому +1

    I have a 2 inch wet vent for a toilet feeding the LAV. Can I wye off the 2 inch wet vent and feed a bathtub drain that does not have an individual vent?

  • @3xbabe
    @3xbabe 2 роки тому +1

    Just a little confusion with the 2 Maximum FU draining into a Wet Vent. At 4:41 you have a shower with 3 heads with 3 FU. How come thats okay? Thank you so much.

    • @MathematicPlumber
      @MathematicPlumber  2 роки тому +5

      The 2 FU maximum is for Branches and Fixture Drains.
      The shower is being drained through a Trap Arm, the only rule that applies for it is maximum 2" in size

  • @staraijdid4216
    @staraijdid4216 Рік тому

    The regular vent needs to be rotated 45 deg above the middle of the pipe. And the wet vent does not. Would it be OK for the wet vent to be rotated more than 45 deg? Certainly would keep the wet vent with less than %50 capacity.

    • @MathematicPlumber
      @MathematicPlumber  Рік тому

      The wet vent can be more than 45°, it has no effect on its function

    • @staraijdid4216
      @staraijdid4216 Рік тому

      @@MathematicPlumber phew, I got something right.