Wet Venting Video:3 - Sizing a Basic System

Поділитися
Вставка
  • Опубліковано 5 січ 2025

КОМЕНТАРІ • 20

  • @kotaplumbingandheating
    @kotaplumbingandheating 2 роки тому

    Thanks Kelly. I write my IP in 4 weeks so this is great review.

  • @marcuspearson9509
    @marcuspearson9509 3 роки тому +2

    Love the video’s, pls keep them coming. I appreciate your time and effort for making the videos . I don’t do a lot of abs, but being able to watch over and over again is very helpful! Thank you!

  • @flexiblefix-montreal1167
    @flexiblefix-montreal1167 3 роки тому

    right now I am holding my 2015 plumbing code and saying I am really appreciate your work!!!! 🙏 Thx

  • @mxm7688
    @mxm7688 2 роки тому

    wow, thank you for taking time, really clear explanation. Im in the middle of my reno so that is helping a lot.

  • @steveg665
    @steveg665 3 роки тому +1

    Thanks for creating these videos. Very well explained!

  • @jetdelacruz2840
    @jetdelacruz2840 2 роки тому +1

    Thank you

  • @mimkarimi9721
    @mimkarimi9721 2 роки тому

    Great videos, very helpful. thank you

  • @numbasixx
    @numbasixx 2 роки тому

    Excellent excellent Videos and of course they’re buried on UA-cam and very hard to stumble on. You must have terminated a vent stack in some UA-cam executives jewelry closet or something.

  • @dantully6087
    @dantully6087 2 роки тому +1

    The 1 1/2 bathtub drain in those pictures is draining into the wet vent and it is not individually vented. So the wet vent is also venting the bathtub?

  • @safa111
    @safa111 3 роки тому

    Good, we just had the same topic in our classroom (level 2 plumbing)

  • @dannyjin4273
    @dannyjin4273 Рік тому

    how come the wet vented system without water closet which serves 1.5 FU for the shower and 1.5 FU for the bathtub is Ok with 1 1/2" wet vent? 1.5FU+1.5FU=3FU so it should be 2" wet vent. that part is confusing. thank you!

    • @MathematicPlumber
      @MathematicPlumber  Рік тому +1

      When you total up FUs draining into a wet vent, you never count the last/lowest connected fixture, in this case the shower. The shower is being vented through the wet vent but it's not draining into the wet vent. (The wet vent ends at the shower wye connection, therefore the shower is being drained into a Branch)
      To think about this another way, the wet vent will never get filled up by water from the shower (Unless the drain gets blocked downstream in the system somewhere)

  • @yma7689
    @yma7689 11 місяців тому

    what about using the 6" wet vent without serving the toilets, what's the maximum load allowed?

    • @MathematicPlumber
      @MathematicPlumber  11 місяців тому

      Never come across a 6" wet vent. According to the table at 2:47 it is not permitted.
      Further to that, if I saw my employee running drainage like that, I would ask them to give their head a shake. Huge waste of money

  • @SupraDanrx8
    @SupraDanrx8 11 місяців тому

    Isn't shower suposed to be 2 inch ?

    • @MathematicPlumber
      @MathematicPlumber  11 місяців тому

      Not according to table 2.4.9.3 or any other code clause

  • @donny2446
    @donny2446 2 роки тому +1

    3:21---here in Ontario you can't put a double wye on the horizontal, Otherwise very informative video!

    • @Superboi100
      @Superboi100 2 роки тому +1

      there's literally nothing wrong with the set up shown in the video, the system will drain just fine with 0 risk of clogs/leaks

  • @nathanaelrodgerson7216
    @nathanaelrodgerson7216 2 місяці тому

    Lebron James