Inspecting an Electrical Panel

Поділитися
Вставка
  • Опубліковано 8 чер 2024
  • Electrical panels pose an important part of the home inspection process. Here you will see me perform an electrical panel inspection using the InterNACHI standards of practice. Note, not all deficiencies will be discussed. Do not try this at home.

КОМЕНТАРІ • 71

  • @ragingpyro1215
    @ragingpyro1215 3 роки тому +9

    Loving the longer videos on UA-cam! Currently looking at my breaker like I know something

  • @shawnrehal9483
    @shawnrehal9483 3 роки тому +3

    I don’t know why I watch these but here I am

  • @whitetiger8652
    @whitetiger8652 Рік тому +2

    Very informative, Thanks!

  • @KevinCoop1
    @KevinCoop1 Рік тому +8

    Just so you know, the No oxide paste is not required by the conductor manufacturers or most panel and equipment manufacturers. The aluminum has been changed to not require it. But, there are some pieces of equipment that the manufacturer does require it. So, if it’s there, no issue. If it’s not, may or may not be an issue.

    • @chopshop523
      @chopshop523 Рік тому +3

      Why would you ever not apply the cheap antioxidant to aluminum wiring???? Never have someone who cuts corners do your work

    • @robertbritton656
      @robertbritton656 10 місяців тому +3

      ​@@chopshop523When the manufacturer states you don't need it.

    • @tracynation2820
      @tracynation2820 4 місяці тому +2

      Apply anti-oxidation grease or mineral oil to ALL connections in a breaker box, including ALL lugs, stabs, wire clamps, splices, terminal and bonding screws, and neutral/ground bars, and any and all wire to wire or wire to terminal connections, even if you don't need to. If it was my house, I would also wire brush all copper and aluminum wires and terminals and apply ox-guard before connection.
      Also apply it to outlets, switches, and lights, basically any place that the wire makes contact. Do double wiggle the wire and retorque all terminals, and put anti ox on the receptacles, wire nuts and Ideal/Wago splices, ground screws, and terminals also, a well as the ground wire clamp, blades on a plug and the hot, neutral, and ground slots on all outlets and light bulb sockets. 💙 T.E.N.

  • @ericarthur8912
    @ericarthur8912 3 роки тому +3

    In school now for home inspection, headed to Nashville for vacation and potential house hunting

  • @PG-wi9oq
    @PG-wi9oq 3 роки тому +1

    Good stuff!

  • @Z-Ack
    @Z-Ack 2 роки тому +1

    Looks just like and has the same mannerisms as a guy i used to work with at the university of ky.. dude was in the communications/ it dept.. like they could be brothers.. really close resemblance, is crazy.. dude was a real good dude also..

  • @BillC-64
    @BillC-64 2 роки тому +4

    In Canada, we require a barrier over the service entrance and main breaker, where you cannot run the those wires from the breaker.

    • @jontopham2742
      @jontopham2742 2 роки тому +2

      Required in USA now too in the new code

  • @fudge417
    @fudge417 3 роки тому +2

    Woo 900th subscriber!!

  • @therealcbrady
    @therealcbrady 3 роки тому +8

    Any concern with that water line right next to it?

  • @--JohnDoe
    @--JohnDoe 2 роки тому +11

    Blunt end screws or not! If there are wires on the back side of the hole, it will get damaged, especially if its a feeder or a tight bundle that cant get pused back. All wires should be away from the holes.

  • @InspectorAJ
    @InspectorAJ  3 роки тому +4

    Good lord I look like I’ve never slept. Ever.

  • @electricalron
    @electricalron 4 дні тому

    Did the short-circuit current rating of the main breaker exceed that of the available fault current?

  • @whith5184
    @whith5184 3 роки тому +1

    is the insulation surrounding the service conductor wires and peaking into the panel okay? thanks

  • @leegarcia81
    @leegarcia81 3 роки тому +6

    FYI UA-cam has your settings set to "videos made for kids" meaning you can't enable auto play on your videos and it affects the amount of views and subscriptions $$$ you can get. Thanks for the videos and good luck with the channel.

  • @spicermedic
    @spicermedic 3 роки тому +1

    Are the "Recommendations" added to your report, or just verbally mentioned to the customer? Do you say anything to the home owner (assuming the customer is not the home owner). Also, how long does it take to inspect a home? This looks very detailed.
    Thanks for doing these! Love watching your videos!

    • @InspectorAJ
      @InspectorAJ  3 роки тому +3

      I tell the buyer and also report it.

  • @FireHazardMan103
    @FireHazardMan103 Місяць тому

    @InspectorAJ What is wrong with the dryer wires running behind the service lines? What problems can that cause?

  • @cpu64
    @cpu64 2 роки тому +3

    I used my ocd in my breaker box so it's perfect, lol

  • @bradleywills9241
    @bradleywills9241 3 роки тому +6

    “It would behoove you”...your military/veteran status is showing...hooah!

  • @Richet125
    @Richet125 3 роки тому +2

    What are your thoughts on tandem breakers?

  • @kykle90
    @kykle90 Рік тому +7

    👍🏻 nice video, It looks that panel was supposed to be wired as a sub panel based on the conductors entering the panel. If so, the grounds and neutrals should be separated.

    • @jesusbarriga2800
      @jesusbarriga2800 Рік тому +1

      The meter might be behind it on the other side of the wall?

    • @cyborgdale
      @cyborgdale Місяць тому

      And the bonding screw removed from the neutral bus bar. Often you will find a jumper from neutral to ground which also should not be there for a sub panel. And neutrals on one bus bar and grounds on separate bus bar regardless of main (best practice) or sub panel (essential). Both bus bars are jumpered together and bonded if the panel is main.

  • @havox112
    @havox112 2 роки тому +2

    Wire size doesnt have to match breaker for AC units. Article 440.

  • @dreamergth
    @dreamergth 3 роки тому +1

    How about the arc fault brakers?

  • @onpurpose2629
    @onpurpose2629 Місяць тому

    Electric panel isn’t allowed to be used as a junction box. Well except for when adding a generator panel next to it that has junctions required in the panel?

  • @heroknaderi
    @heroknaderi 3 роки тому +2

    Great information ℹ

  • @jeffhrycuna3349
    @jeffhrycuna3349 Рік тому +2

    Doing a service charge you land the wires on a breaker to avoid splices

    • @DevJB
      @DevJB Рік тому +2

      When splices are in the panel, it's usually because breakers were reorganized or balanced..
      When landing a new string, it's easy to drop to bottom of panel and have enough length.

  • @bklyn2va2dc
    @bklyn2va2dc 9 місяців тому +1

    If there was a sub panel right next to the main panel, and you wanted to move one or two circuits to the sub panel from the main panel, could you splice the original wires inside the main panel with new wires coming into the main panel from the sub panel? Or must the spliced wires all be contained in the main panel only?

    • @tracynation2820
      @tracynation2820 4 місяці тому +1

      If you add a sub panel beside the main panel, the only splices would be in the main panel. The sub panel would not require any splices, as only the circuit wires that you need extended from the main to the sub panel need to be spliced. P.S. Splice all the wires in a circuit, (Hot, neutral, and ground) and take them to the sub panel. 💙 T.E.N.

  • @tracynation2820
    @tracynation2820 4 місяці тому +1

    Super. 💙 T.E.N.

  • @scottresch9912
    @scottresch9912 2 роки тому +2

    No drp loop on new pull makes me sad 😞

  • @CaptJamieSmith
    @CaptJamieSmith Рік тому +2

    Is nobody going to point out the cut/slice in the insulation on the second wire down on the 30 amp breaker?

    • @stevebabiak6997
      @stevebabiak6997 Рік тому +1

      At 1:55 on the right hand side. Good eye, it’s not so obvious when the video is running because he is moving the camera quite a bit up and down while filming.

  • @williamrhodes4455
    @williamrhodes4455 Місяць тому

    Was the panel bonded?

  • @28ashcat
    @28ashcat 2 роки тому +1

    Not a mention of grounding the service panel. ( I did see it was grounded to a water pipe.)

    • @DevJB
      @DevJB Рік тому +1

      No mention of separate neutrals and grounds per bus lug.
      Gotta' keep 'em separated. Ground and Neutral under same screw is not ok and should be mentioned.
      Also didn't mention how much he saved on car insurance. ; )

  • @ripjohnson2121
    @ripjohnson2121 2 роки тому +1

    Are the wires long enough, looks like that's why they were run as they were.

    • @DevJB
      @DevJB Рік тому +1

      Panel probably had breakers balanced, moved around. That's why splices are typically in the panel.

  • @MrTHEBRITINWA
    @MrTHEBRITINWA 2 роки тому +1

    Excellence

  • @ronblack7870
    @ronblack7870 Місяць тому

    wow on the spliced wires. in canada that's a fail. you can't use the panel as a junction box due to extra heat from splices.

    • @nspro931
      @nspro931 Місяць тому

      Not a junction box, that is to extend wires because it is a retrofit. The splices will never get hotter than the wires, there is far more mass of metal in the splices esp. wirenut splices.

  • @giovanigomez6485
    @giovanigomez6485 Рік тому +3

    Can a sub panel be installed upside down?

    • @davidboldt1488
      @davidboldt1488 Рік тому +2

      Yes , just never have a breaker that when the handle is down the breaker would be in the on position .

    • @tracynation2820
      @tracynation2820 4 місяці тому +1

      They make panels with the main down low, not up top. 💙 T.E.N.

  • @s.e.v.2055
    @s.e.v.2055 Рік тому +2

    What about the bonding of the i
    Panel

    • @Roy-ij1wq
      @Roy-ij1wq Рік тому +1

      Question #1 is always is this a main or a sub?

  • @5zwoodworks
    @5zwoodworks 3 роки тому +1

    Ah. The 1 dislike was obviously someone that failed.

  • @ripjohnson2121
    @ripjohnson2121 2 роки тому +1

    Never seen blk cuttler hammer breakers before?

    • @larryoverhagen4967
      @larryoverhagen4967 Рік тому +1

      They are Eaton BR also in family of cutler hammer. Your thinking of the true Cutler hammer CH which have beige colored triggers. Not interchangeable but same family. I know confusing scenarios.

  • @harleydad1975
    @harleydad1975 3 роки тому +1

    So touch it to make sure it's not energized? Got it. I hope I never get it lol

    • @BillC-64
      @BillC-64 2 роки тому +1

      Proper procedure is to use the non touch voltage detector then the back of your hand.

  • @pukeschannel6882
    @pukeschannel6882 2 роки тому +2

    Are you kidding,? Best practices? Either it meets code or it doesn't.

  • @richardcranium5839
    @richardcranium5839 2 роки тому +2

    groung wire was insufficient even for 1980's standards

    • @anthonyhitchings1051
      @anthonyhitchings1051 2 роки тому +1

      The thin ground wire matches my 1964 house. As does the old style of Romex in on image (at the cable entry, top right corner).

    • @havox112
      @havox112 2 роки тому +1

      #4 is ok for 200 amp grounding 250.66

  • @michaelbaumgardner2530
    @michaelbaumgardner2530 2 роки тому +3

    That's a sloppy panel

  • @1ajs
    @1ajs 2 роки тому +1

    man what a hack job that is

  • @thomasmarable6818
    @thomasmarable6818 2 роки тому +1

    Electrician will tell the dryer wires are ok

  • @johnsmithth3318
    @johnsmithth3318 Рік тому +1

    Sloppy work