What is the Difference Between a Short Circuit and a Ground Fault?

Поділитися
Вставка
  • Опубліковано 7 чер 2024
  • Join this channel to get access to perks:
    / @electricianu
    Troubleshooting can be one of the most daunting tasks an electrician can face. There are usually just so many variables to consider when trying to figure out what went wrong or when something isn’t working. In todays episode of Electrician U, Dustin answers a follower’s question regarding the difference between Short Circuits & Ground Faults and the values you should see on your multimeter when testing for them.
    🤘⚡️MEMBERSHIP⚡️🤘
    JOIN ELECTRICIAN U - become a member and get:
    FREE Continuing Education every year
    FREE Practice Exams
    FREE Monthly Video Courses
    FREE Weekly Live Instructor-Led Classes
    FREE Monthly Educational Newsletter
    Premium Members-Only Content
    Private Discord Channel
    Monthly Members-Only Discord Chats
    Sign up here --- www.electricianu.com/electric...
    🎧🎹MUSIC AND VIDEO:🎹🎧
    / descantmv
    🎬✍️ART AND ILLUSTRATION:✍️🎬
    www.daverussoart.com
    While the terms Short Circuit and Ground Fault seem to be used frequently and interchangeably, they are in fact quite different from one another. Think of a Short Circuit as a Short Cut, removing the load from the equation, and providing a path for the circuit to make its completed loop to the source of power. By doing this, it generates more amperage than the breaker is rated for, and the breaker trips. A ground fault is simply where a hot conductor has come into contact with something that is specifically grounded (maybe the grounding conductor itself or the case of a piece of equipment that is grounded, or a box/conduit that are grounded) and providing a return pathway to source. Either way, both of these scenarios happen BEFORE the load and in doing so, result in much higher amperage than the breaker is designed to withstand so it trips.
    A great way to diagnose your power issues is to use your multimeter. There are two functions of said multimeter that would be helpful in this situation. You could use the OHM setting to check for resistance in the circuit. However, if you did not know the EXACT wiring of the circuitry, this would not be the most helpful of the functions. If you were to check between a hot and a neutral, you would most likely get the same values as checking from hot to ground. This happens as the grounding conductor AND the neutral conductor are run in the same conduit and have roughly the same length. A better choice would be to use the continuity function of the multimeter. If you are measuring before the load, you should not have continuity between the hot and either ground, neutral, or another hot. Once you figure out which two wires are completing the circuit, then you have found your problem!
    Another great journeyman’s tip when troubleshooting is to gather as much information as you can about the situation and find out as many KNOWNS as you can. How much amperage is it supposed to draw? Has it done anything like this before? What exactly happened when it faulted (was there a shower of sparks, or a loud boom, etc.). A great one to ask is “did anyone perform any work on it recently? And if they did, are those folks available to speak? If something used to function, someone performed some type of work on the system, and now it doesn’t work, usually means the malfunction is either located within the work they did or is a direct result of the work they did. So, be a detective of sorts and gather as much information as possible. Use those KNOWNS to mark off the UNKNOWNS and it will narrow down the areas you will be looking in. It is also helpful to pull back and get a higher altitude look at the situation, then dive down into the details. Doing this in multiple areas of the whole system will help you eliminate possibilities, so you aren’t chasing demons throughout the entire system!
    Also, remember that breakers don’t just randomly trip, and fuses don’t just randomly pop! There is a reason that they do. So, it isn’t prudent to just attempt to continue cycling the breaker until the equipment stays on or replace the fuse with a higher rating (or bypass the circuits protection entirely!). Something has happened and the breaker/fuse is just doing what it was intended to do! The appropriate action would be to diagnose the problem and then correct it!
    We hope this has been helpful in understanding the difference between a Ground Fault and a Short Circuit and given you some useful information for troubleshooting an electrical problem. Please continue to follow Dustin and Electrician U as we are constantly updating our content to assist our followers in becoming the best electricians that they can be.
    #electrician #electrical #electricity

КОМЕНТАРІ • 336

  • @atmacm
    @atmacm Рік тому +28

    I’m glad you made this video. You’d be surprised how many electricians don’t realize the difference between ground faults and short circuits.

  • @JCWren
    @JCWren Рік тому +14

    This should be obvious, but never test continuity on a live circuit, e.g., using the meter in continuity mode across hot and neutral, hot and ground, or hot to hot (for 220V). A Harbor Freight quality meter will be destroyed, a good meter will blow the fuse. While electricians don't typically use this, but there's a device called a Time Domain Reflectometer. It fires pulses down the line, and measures the return times. It can find shorts, changes in resistance, and open circuits. You can also measure the length of the wire if you know it's velocity factor. They're not crazy expensive, but they're not cheap either.

  • @Sparky-ww5re
    @Sparky-ww5re Рік тому +28

    If your having trouble finding if you have a ground fault or short circuit, and tried removing appliances, turning wall switches off with no success, then you know the problem is within the building. Because grounds and neutrals ultimately end up at the same place in the main panel, what you might consider doing is removing the neutral of the problem circuit from it's bus bar, then check if you have continuity between the hot coming off the breaker and the neutral. If you don't, but you have continuity between the hot and ground bus, you narrowed it down to a ground fault. In either case, ask yourself, what circumstances changed? Ex. an electric heater was being used for an extended period, and you smell burned plastic near a receptacle, see wisps of smoke, and now the breaker won't hold. Perhaps you heard a pop or crackle, or seen a flash, before the breaker tripped. You narrowed it down to a ground fault in the building wiring. Upon pulling devices upstream of the space heater location, you find a wirenut had burned off the hot wire and is touching the metal box. Not all troubleshooting is going to be so simple and logical, but you get the idea.

    • @mexicanlucky
      @mexicanlucky Місяць тому +1

      These kinds of comments you find in youtube are solid gold. Thanks professor!

  • @dmeemd7787
    @dmeemd7787 Рік тому +104

    This is good stuff, you don't have to be in the electrical trade to need to learn the stuff I understand it, which is what I appreciate about this channel. People have trained in HVAC, I have sent them your way to do some homework. Videos like this being a perfect example, because I tell everyone, if you're not putting in time off the clock as well you're never going to succeed or learn what you need to learn or need to know

    • @josemartinez-jt6tw
      @josemartinez-jt6tw Рік тому +3

      Im in hvac and struggle electrical n using my meter

    • @that1electrician
      @that1electrician Рік тому +7

      @@josemartinez-jt6tw Buy some textbooks.
      See if your job will cover a few semesters of trade schools. I know a lot of employers do. That's how I got through trade school and got my certs. I wouldnt be where I am today if I didnt put my head to the ground and go for it.

    • @raymondgarafano8604
      @raymondgarafano8604 9 місяців тому

      YUP ppl who like this, their mind will absorb any info when they work on projects,
      sort of like seeing twine broken on motor windings, it is quite likely there will be
      a discoloration of the windings. even from years past seeing discolored coils in a
      motor or gen you'll remember the twine was most likely broken leading to the
      fact the coil overheated and a good chance there will be a shock hazard.

  • @igintell7295
    @igintell7295 3 місяці тому +5

    I'm a green maintenance tech and this video helped me out a lot.

  • @pdk79
    @pdk79 Рік тому +44

    Prior to continuity check, It seems a very important step is to disconnect the device from the supply neutral (and hots) otherwise the bonding at service panel will not allow you to differentiate between neutral and ground.

  • @Stones_Throw
    @Stones_Throw Рік тому +21

    An excellent explanation. I would have only added the step of unplugging/disconnecting the load from supply wiring to isolate and narrow down possible causes.

  • @MakeNoise280
    @MakeNoise280 Рік тому +7

    Remember when testing resistance or continuity remove power or turn off power. Thanks for the info, helpful.

  • @keltonfoster
    @keltonfoster Рік тому +1

    Man the way you explain it makes me understand it much better, thank you. That mentor you had is the man. Knowns is what will help you pin point the issue.

  • @joeyc5564
    @joeyc5564 Рік тому +2

    My trade school just uses you videos to teach us ⚡️⚡️

  • @colinstu
    @colinstu Рік тому +11

    "Finding the knowns" … yeah, that's an amazing troubleshooting step - and applies to all kinds of stuff including outside electrical. I can't tell you how many times someone asks for help only to find out they skipped all the easy stuff to check, didn't "look for the knowns" and is struggling off in some completely unrelated area because of it. I always step ALL the way. back, start from the beginning/scratch, and yeah, go thru all the knowns and go from there.

    • @desertodavid
      @desertodavid Рік тому

      @Colinstu by "knowns" are you talking about "probable faults" in a circuit?

    • @colinstu
      @colinstu Рік тому +1

      @@desertodavid it's talked about in the vid. But no, basically starting with the basics, starting with the baseline. You need to start an investigation by starting with the basics, and finding out the most basic parts of the situation.
      It can be easy to be carried away jumping into a situation going off of what other people have said, only to find out they missed something SUPER easy / simple because they skipped the basics and went right into more complex situations. (or you yourself doing the same thing. "I am so smart, it MUST be this instead of like… checking breakers, checking how the wires are connected, tracing them out, etc. A bad assumption can send you down a totally wrong path.
      You may end up with the final solution anyways - but all that could be skipped if the basics/knowns of the setup are determined first.

    • @desertodavid
      @desertodavid Рік тому

      @@colinstu nevermind. Obviously you don't know what I mean by probable faults. I'm an experienced Electronics technician, so save your time.

    • @colinstu
      @colinstu Рік тому

      @@desertodavid oh, PROBABLE, I read that as "ground" (as in ground faults). Yeah that's definitely all part of it.

  • @FR3ERUNN3R
    @FR3ERUNN3R 11 місяців тому +2

    Needed this today. Came across someone’s shoddy work and just immediately stressed out when I opened the j-boxes. Hopefully when I go back on Monday I can solve my problems.

  • @JohnThomas-lq5qp
    @JohnThomas-lq5qp Рік тому +2

    I'm a retired sparky with over 50 years in this great trade. Several times I have came out and found that a circuit breaker trips as soon as you turn it on. Unplugged everything & turned every switch on that circuit off and problem did not go away. Could not pick up and grounds on either of my VOM'S. Used my expensive Fluke combination VOM/ Megger. Did not pick up a ground at 50 volts but got a low resistance reading using 100 volts. One of these was caused by water that halve filled an outdoor receptacle box. Another time old rubber insulated wire had broken pieces of insulation allowing two wires maybe seperste by a hair. If I had 10 devices on a circuit would try to guess middle point and disconnect wired then flip the breaker.

  • @treyrmason
    @treyrmason 17 днів тому

    Hey man, thank you so much for all of the valuable info on your channel. I’m a coffee tech (espresso machines, commercial brewers, etc) so we basically need to be baby plumbers, baby mechanics, and baby electricians. The electrical side of things is always where I felt the least comfortable, but your videos really helped me step up and feel like I have a handle on what previously felt like black magic.

  • @Sparkeycarp
    @Sparkeycarp Рік тому +1

    We had a job subbing for a company that had a contract to move all the service meters from the panels on the sides of mobile homes to pedestals in the front corner of the houses. They ran all the new supply lines under the houses to the main panels. Our job was to solve all the ground to neutral faults in the whole park. As well as replace some very old or under rated panels and any other problems. I did all the troubleshooting with my apprentice helping. We had to open and disconnect a lot of wire nuts. First thing we always did was pull the electric dryer cord. A lot of those are neutral bonded to ground. Keep up the great videos. Still learning and finding better ways to explain things to apprentices and customers. Even though I have my own company now.

  • @Sembazuru
    @Sembazuru Рік тому +9

    There may not be "continuity" as defined by your DMM when a device is turned on. This is because the continuity feature of DMMs beeps below 1-2 ohms. But the actual load may be hundreds to hundreds of thousands of ohms. That said... __NEVER__ use the ohms/continuity reading of a DMM on a live circuit. You'll either blow a fuse in your DMM, damage your DMM, or explode your DMM (depending on the voltage across your DMM leads when you take the reading and the safety features inside your DMM).

    • @michealplater9007
      @michealplater9007 Рік тому

      Yes, you are correct regarding continuity. I have seen electrician's test with a meter, its open circuit. No, your meter has a maximum of 2k, anything over this will show open circuit. You need to read the meter manual and understand its limits.

    • @atmacm
      @atmacm Рік тому

      On flukes the continuity setting is usually below 80 ohms

  • @jacobplank
    @jacobplank Рік тому +5

    Thanks for the great video!! Definitely helpful in understanding it. I do use continuity alot for troubleshooting. Have an outside project (still not finished) alot receptacles In the yard where over time got covered over with dirt and multiple shorts in the circuit, I take sections at a time and test continuity and finally figure out where and which wire. It's been a nightmare job and still a few left to do.

  • @miguelsword9611
    @miguelsword9611 Рік тому

    Very informative. He clearly knows his business. Excellent presentation.

  • @williamcash4126
    @williamcash4126 Рік тому +1

    i am a master electrician and hvac tech over 30 years .I am disabled now .Everything you said is correct .the first thing l was taught about electricity is it all ways looking for the ground and you don`t want to be the best way to it! all ways turn the load off before turning on power!Because a loose connection under a load is the same a welder. it heats up and makes a bigger gap and bigger arc every time load comes on! and a breacker matches the size wire to protect the wire from heating up and burning!The nuetral is the designated path to ground and it just as hot as the power wire under a load!

  • @cecillec2331
    @cecillec2331 9 місяців тому +2

    Thank you very much for the great explanation.

  • @berthongo8531
    @berthongo8531 Рік тому +3

    We would get sent out to work on a customer's turbine with a "known" issue. That is, until we got on site and found that the customer's "known" issue didn't make sense. I finally figured out that the best thing to do was to start shooting the breeze with one of the operators and find out what they were trying to do when the "known" issue popped up. It usually had nothing to do with what the office people said it was. It usually also pointed out that they did something stupid or that something else on site caused the issue to begin with and the turbine was collateral damage. Really cut down on the troubleshooting. Know your knowns. I like that.

    • @Hvn1957
      @Hvn1957 Рік тому +1

      This is SO true. We tell all out clients, very politely, to just describe the problem without any speculation. Of course, if someone spilled their coffee on the control panel, I’d like to know that too 😏😏.

  • @cadillacphilli
    @cadillacphilli 6 місяців тому +1

    I love your channel, you are awesome! Very helpful and you explain in a way that a less experienced person like myself can understand. Thank you so much for being here.
    Kind Regards.
    Philli.

  • @Jaxemus
    @Jaxemus 6 місяців тому +1

    This video helped me fix a lighting issue , thank you!

  • @dmz6973
    @dmz6973 Рік тому +1

    This video is like the gold rush, because I'm finding lots of gold nuggets in here! Thanks for the great info Dustin!

  • @trentthompson5734
    @trentthompson5734 Рік тому +9

    I'm in hvac but we do some of our own electrical. Making me a better tradesman. Thank you

  • @JustinLorenzo63
    @JustinLorenzo63 Рік тому +1

    Keep doing videos like this,I really appreciate them

  • @hliz8818
    @hliz8818 Рік тому +2

    When checking continuity you have to turn off breaker right? So you dont damage your multimeter..?

  • @ryanhoffman5864
    @ryanhoffman5864 Рік тому +23

    Dustin, could you please do a video with tips and tricks to troubleshooting with both a multimeter and a clamp meter? I’m an industrial electrician that’s been with my company for a year, and I’d like to get into service calls and learning how to use my meters to help with troubleshooting. Love your videos, and I would appreciate it a lot. Thanks in advance if you do this.

    • @gp3646
      @gp3646 Рік тому +1

      Trouble shooting with a clamp meter? Are you talking about an amp probe?

    • @repro-rt6lu
      @repro-rt6lu Рік тому

      I do industrial as well 3y in....I believe it's a fluke 375 that measures in rush.....I'm wondering if I clamped the neutral close breaker and got a inrush value turned around and did the same for ground how they would compare...the expectation is to try and catch the one drawing excessive current to determine short circuit or ground fault...

    • @Willeeum8293
      @Willeeum8293 Рік тому +1

      @@gp3646 amp clamp

    • @jones0618
      @jones0618 Рік тому +1

      Be prepared to be humbled. Service work and troubleshooting is a whole different animal than commercial/industrial new construction. But it will be good experience for you and I highly recommend every apprentice down both new construction and service work. I'm a journeyman and still struggle with troubleshooting at times and using my meter. When you install for awhile and do nothing but bend pipe you get a little rusty when you actually have to think like an electrician. Hell just last week I had to look up how to calculate a lighting load using ohms law. I had brain dumped all that and haven't done a calculation in God knows how long.

  • @unrachna
    @unrachna Рік тому +1

    Thanks for your teaching!❤❤❤

  • @banggugyangu
    @banggugyangu Рік тому +7

    This was an excellent video with wisdom that applies to fields far outside of just electrical. Great troubleshooting advice for all troubleshooting.

  • @TonyParker-lh5ct
    @TonyParker-lh5ct Рік тому +1

    thank you for the explanation. The ways to explain this was some simple. 💯

  • @zacharyhottell8251
    @zacharyhottell8251 Рік тому +4

    Make sure the power is off. Disconnect the wiring to speed things up.
    Remember you will a always read continuity or "ohms" over a coil such as a heating element but you should more resistance over a coil then a derect short.

  • @matthewblankowski2265
    @matthewblankowski2265 Рік тому

    This connected some really important dots for me. Thank you.

  • @stevenfoust3782
    @stevenfoust3782 Рік тому +1

    I like when flames come out of the breaker when you reset it and your hand is on the breaker along with a nice pow.

  • @ThommyGunnGaming
    @ThommyGunnGaming Рік тому +4

    Great video! Wish I saw this last year, had a similar issue and did all kinds of troubleshooting to figure out it was a simple fix in the junction box, felt dumb.
    BUT hey, I have a random question, as a DIY homeowner, I have a couple spots I need to run new Romex to where the existing is 12/2 and I need 12/3. Talking to people I work with they all make it sound so simple, attach the new to the old and pull through DONE. Wrong, because from what I know and, in my situation, the installers staple it to studs in the wall. So how does a professional replace Romex in a finished wall? or do you cut open the wall, patch it up, and paint when done? Trying to avoid that, but it might be my last option. Thanks, appreciate the easy-to-understand info.

  • @ericksonfilpo1604
    @ericksonfilpo1604 Рік тому

    You have to be the best instructor in the world, thanks for your video

  • @arthurburke3771
    @arthurburke3771 Рік тому +4

    Fantastic job on explaining how to troubleshoot a circuit issue! Many times the first thing people think is that it must be a wiring problem without considering the possibility that it could be something running off the circuit.

  • @seankaran3490
    @seankaran3490 Рік тому

    Excellent video. Thank you!

  • @michealplater9007
    @michealplater9007 Рік тому +63

    99% of the time it's not the wiring, it's the equipment connected. Disconnect the equipment and check if the breaker will reset. Depending on the fault a multimeter may not show the fault and an insulation resistance tester (Megger, trade name) may be required.

    • @iwenive3390
      @iwenive3390 10 місяців тому +4

      90% of the time it’s a loose wire in the breaker

    • @myselfsula6720
      @myselfsula6720 Місяць тому

      %100

  • @kevindick7485
    @kevindick7485 Рік тому +12

    Nice job . However it may be to make sure all power is lock and tagged out if possible and no live power going to the circuit you are checking for continuity . I saw a guy in class one time blow up his meter because he did know to have no power when checking continuity . A little tid-bit for your next presentations. I can not stress the one little thing like that you did not mention !

  • @johnmaranuk1842
    @johnmaranuk1842 Рік тому +6

    Dustin, you're awesome!
    Experience comes from years on job. We always learn everyday. No way we can know it all.
    I was taught at early age, "we stop learning, when we allow ourselves to not want to take anymore in".
    Best tip to apprentice is, do not say ya know, if ya don't. Always ask questions, its better to ask the 'why' , then to just keep doing, cuz you're told so.
    That will show interest in trade and jman will appreciate it ( well, most would, lol).
    Cheers from Pennsylvania!

  • @donmoore6931
    @donmoore6931 Рік тому +5

    Dustin. Very helpful. Question: It is necessary to de-energize a circuit before you test for continuity, yes? Were you assuming that with a tripped breaker, the circuit is by definition de-energized?

    • @tedtenny
      @tedtenny Рік тому +3

      Good way to destroy your meter when checking for continuity if you did NOT DE-ENERGIZE your circuit! Continuity testing or resistance, (same circuit within the meter) relies on its own internal power.

  • @jmrgoldable
    @jmrgoldable Рік тому

    Thank you so much...knowledge is power!!

  • @BobSmith-vq3uo
    @BobSmith-vq3uo 6 місяців тому

    Great teaching. Thanks for sharing this.

  • @akamomakawife4928
    @akamomakawife4928 Рік тому

    Thanks for your time an videos iam sure I have a short going on with my dryer now got to find it but u save me with this video ty.

  • @milesharlan1
    @milesharlan1 Рік тому

    Dustin, Thank You ...Another great learning tip!!

  • @christophermiller8075
    @christophermiller8075 8 місяців тому

    Keep up the great explanations!

  • @watertech011
    @watertech011 5 місяців тому

    Great advice on gathering the "knoiwns" , in the process you will get to the problem.

  • @spark5558
    @spark5558 Рік тому

    Thanks for the advice

  • @phwlee
    @phwlee Рік тому +1

    Great video. Very informative. Which model multi-meter is the one in the video? Looks like maybe the MM720

  • @BlackHoleForge
    @BlackHoleForge Рік тому +3

    Hey when I was in college studying networking, we had a tool called a Fox and Hound. It sent a signal Through the Wire, and you could pick it up with a handheld device. Is that possible for electrical wires? Like if the wire did find a shortcut, could it be used to find where the shortcut is?

  • @kamakaziozzie3038
    @kamakaziozzie3038 3 місяці тому

    something to also keep in mind. Ground faults are not only created by hot conductor(s) touching metallic frames or equipment grounds.
    I do a lot of outdoor lighting troubleshooting and can’t tell you how many times tripped GFCIs are caused by junction boxes located in the soil that have moisture contamination. Enough current is able to find its way to earth ground that it trips.

  • @lalmuanpuiamizo
    @lalmuanpuiamizo Рік тому +1

    Nice demonstration. Unplug/disconnect then probe to isolate to see which side of the circuit... zoom in. That's how I do

  • @josephnicolas2158
    @josephnicolas2158 Рік тому

    Amazing video as always!

  • @MJQuintana
    @MJQuintana Рік тому

    Great and on-point!

  • @Kaiser.Alexander.I
    @Kaiser.Alexander.I 3 місяці тому

    The best from the video was with the knows! It’s a life reminder.

  • @brianmcdermott2430
    @brianmcdermott2430 8 місяців тому

    Great info. Thanks.

  • @until11
    @until11 Рік тому +1

    I've always used the term ground fault to refer to an issue that happened on a switched return circuit.

  • @randtemple2332
    @randtemple2332 Рік тому +1

    I use a light socket. Black from pigtail goes on breaker and neutral goes to the load. Short or ground fault circuits will cause light from bulb. When fault is cleared light goes off

  • @navidnikraz2299
    @navidnikraz2299 Рік тому

    Great explanation

  • @vicferrmat4492
    @vicferrmat4492 5 місяців тому

    Thank you, I was trying to understand this for some tìme.

  • @traditionaltools5080
    @traditionaltools5080 Рік тому +2

    True, sort of. You can have a ground fault with as little as a few milliamps of current. Often from a small cut or break in the insulation and often intermittent. That's why it's so important to megger new installations. Especially if you're using conduit.

  • @bencoss7003
    @bencoss7003 7 місяців тому

    The gentleman is right, correct terminology on the job gets the job done correct and efficiently, and when you have those two it means that you done the job safely to, German if you ever do any job that has anything to do with electricity what you got to remember is your multimeter so you could test before you start, and the best way to find any problem in an electrical circuit is the start where your source comes in and follow it out.

  • @joelniimensahafoteylewis4475
    @joelniimensahafoteylewis4475 Рік тому +1

    hi Dustin, can you make a video on the complete tutorial of the multimeter, as in how and when to use certain button.. on it ?

  • @rmcq6287
    @rmcq6287 Рік тому

    nice to hear someone talking that knows what they are saying.... lol.... thank you for what you do!

  • @waynegram8907
    @waynegram8907 Рік тому +1

    DUSTIN, A Ground Fault is considered the Hot wire is directly connected to the Green wire Ground? a Short circuit is considered if a piece of the equipment's internal wiring or internal load is shorted from hot to neutral or the load is shorted from hot to chassis? How I would troubleshoot a ground fault or short circuit is shut off the breakers then disconnect the Hot, Neutral and Ground wires to the load/equipment, then use my DVM meter to test if the wires are shorted or if the equipment/load is shorted. This method is better because you can diagnose if the load/equipment has an internal short circuit or an internal wiring ground fault. If you don't disconnect the H,N,G wires and multiple pieces of equipment/loads are on the "Same Branch/Same Breaker connected "in parallel" you will be guessing, because a short circuit and ground fault will measure both the same in "milliohms". What is even worse to troubleshoot when you have a short circuit that crossed over in a wiring harnesses in the wall or internal inside a piece of equipment/load to another wiring harness that is on another breaker which you will have "leakage current" or Ghost measurements". This would be a good video lesson about "ghost measurements" and leakage currents.

  • @UpperAquatics
    @UpperAquatics Рік тому +5

    Thanks for the video! I'm studying for my aptitude test to join IBEW. I know this isn't going to be on the test but its helpful to know for the interview and boot camp. Anything I can do now to get a leg up is helpful.

  • @alejandroquinones5439
    @alejandroquinones5439 Рік тому

    Dustin, could a grounding cable physically go up a structure (let's say 8 ft.) and then be routed downward towards the ground?

  • @bearbongo
    @bearbongo Рік тому

    Love your stuff!!

  • @anthonymwangi1661
    @anthonymwangi1661 Рік тому

    Good piece.

  • @cautiouscommenter
    @cautiouscommenter 5 місяців тому

    Still not subscribed. But, this is me commenting on yet another video. Good job on this explanation. You've broken down Root Cause Analysis into a very basic structure. 👍

  • @rtmproject
    @rtmproject Рік тому

    New subs here. Thanks for this video, it helps a lot.

  • @llanbull
    @llanbull Рік тому

    I got a question, how do you find a good ground when testing a panel or machine. Like which place is best to put the black lead of the tester if there is no obvious ground screw? I was testing a micro switch and I failed the exam bec. I can't find a good ground in the machine. Bec. normally you put the black lead on the ground and the red on the circuit you gonna test to find the voltage.

  • @DanielCojocaru-bt5ws
    @DanielCojocaru-bt5ws 3 місяці тому

    Good explanation

  • @TheWickerShireProject
    @TheWickerShireProject Рік тому +1

    Dustin I made a recent video trying to figure out an Aims Inverters Meaning by a Floating Neutral.
    I ended up coming to the idea I HAD to unbond my neutral to ground by removing the GREEN bonding screw in the Mains panel.
    It was in my mind the only way to achieve this.
    Anyone here is free to advise on this topic and look over what they mean by " Warning! Do not bond the neutral to ground. This may or will damage the unit."
    I am off grid. I have been using the inverter in RV application but I will Need to wire it for a grounding rod as my Tiny home needs better protection and my loads will increase.
    Again any one can suggest or advise a better wiring technique. I'm out of options.
    I got to this point after exhausting my limited DIY knowledge.
    This is a very common thread on these types of inverters and has so many people in confusion.
    My system is a 6,000 watt 48v Aims low frequency pure sine with a Ground, L1 L2 in / and a L1 L2 N out. It has a case ground terminal block on the unit.
    There is a ( Looped ) set of of ground wires as well for a Mobile application.
    Once I use a Grounding rod for a more permanent install my neutral bond to ground comes into play.
    Please help my Mind is Grounded out! heh Thanks!

  • @user-hs5vf3wi8e
    @user-hs5vf3wi8e 6 місяців тому

    Hoping for info regarding testing continuity from an alternator. If I test across positive terminal on alternator to positive battery terminal I get a steady tone (beeeeeeeeep) and then when I test from alternator POS to ground I get a consistent broken tone (beep, beep, beep...). I ensured that both leads are making good contact at all times. Any idea what is happening with the broken beep? Thanks for any help.

  • @CH-dr7nm
    @CH-dr7nm 2 місяці тому

    A lot of light fixtures will give you continuity between neutral and hot conductor you always got to keep that in mind as well when troubleshooting

  • @haywoodjohnson2865
    @haywoodjohnson2865 Рік тому

    Thank you very much

  • @sumofool7399
    @sumofool7399 Рік тому +9

    Good stuff Dustin, would love to see some more 3 phase 480V troubleshooting videos as an industrial electrician I would love to hear your take ! Keep pumping out this great content love it

  • @vicvict4172
    @vicvict4172 Рік тому

    Wooooooo. using words properly . Im excited 😁

  • @gabrielf6126
    @gabrielf6126 11 місяців тому

    Hi there; question for you. I moved in into my home a year ago, the house is only 8 years old,and when changing some outlets in a bedroom to replace them with usb built-in I came across one outlet with the ground looped on the neutral side. The wiring is the original from when the house was built 8 years ago. If I undo the ground loop and turn the breaker on , it tripped (nothing connected to any of the outlets)
    I pulled out all of the outlets and switches to see if something was amiss. I turn the breaker back on without the loop and it didn’t trip but the connection that continues from this outlet (master bathroom) stopped working. Connecting the ground loop back to the neutral as I found it, resume power to the master bathroom
    I know without seeing it is hard, but do you have an opinion as to what’s going on?

  • @paulnormandy6247
    @paulnormandy6247 Рік тому +3

    Could you unplug everything on that circuit breaker and plug them back in one at a time to identify which appliance is causing the fault?

    • @Sembazuru
      @Sembazuru Рік тому +3

      This is a perfectly valid troubleshooting technique to narrow the fault down to a specific appliance or identify if the building wiring is the fault if the fault still shows with everything unplugged/disconnected.

  • @lyokss
    @lyokss Рік тому +3

    I had the opportunity of being present when a 480v/1200a breaker was constantly tripping and it was a sight and sound to experience. It was an ice maker for a food processing plant, and the reason it kept tripping was too much in-rush current when the control system fired up the compressor(s) soft starts. I just needed to increase the breaker in-rush settings, so I learned some troubleshooting techniques that day.

  • @user-vn8hq7ot4k
    @user-vn8hq7ot4k 11 місяців тому

    Dude gotta be my favorite sparky to watch

  • @davekrave2
    @davekrave2 Рік тому

    dude! thank you so much! Really!!!

  • @electricalproblemsolve
    @electricalproblemsolve 10 місяців тому

    Thanks for your good information. i known that there is huge support my jobs. 😍😍

  • @mariannebest2536
    @mariannebest2536 Рік тому

    You mentioned that you should never have continuity between a hot and a ground..I agree with that on an appliance, however, it can tone out with lightbulbs sometimes. Can you touch on that and explain it?

  • @cjvillarreal217
    @cjvillarreal217 Рік тому

    Dustin, I work in the cable communications field. I commonly come across voltage on the ground wire of the house. Often times it causes our 18 awg coax cable to melt. Is this considered a ground fault? What are some ways that I can test for this issue to show the customer that it’s an issue with their electrical service? Us as cable technicians seems to always catch the blame. Thanks in advance!

  • @network_king
    @network_king Рік тому +1

    If you do the breaker thing just make sure the circuit is turnded off if doing continuity. Usally when i try to diagnose somehting I start as close to the source as i can and or the simplist to get to. I hade a table was that was acting odd for a bit then just stopped turning on. I tried a few different outlets played with the internal breaker, switch. I then unplugged turned on checked continuity to between the hot and neutral was open. So then tore into the switch, breaker, checked the cord they were all fine. That pretty much left the motor, checked that open circuit, checked from each line to each brush one was open so figured either a winding failed, thermal cutout, or maybe a bad connection. Ended up tore apart was a loose spade terminal on the brush holder fixed good as new.
    I'd do similar for something like this remove anything that would show like a load then start from source and work back until you find somehting that seems off.

  • @yellow8954
    @yellow8954 Рік тому +1

    More troubleshooting videos please

  • @jdjohnson2131
    @jdjohnson2131 3 місяці тому

    In commercial remodeling, we come in AFTER they screw something up, have a tripping breaker, but do not know the load, the correct neutral, etc. Knowing both sides makes it trivial.

  • @freddesgarage
    @freddesgarage 9 місяців тому

    Hi!
    I have a Hyundai Tucson 06 with a irbag light on,scanner states B1326 code (FIS) Front impact sensor short to ground Drivers side.
    How would you trubleshoot this?
    Thanx in advance
    //Fredde

  • @MiceNine9
    @MiceNine9 11 місяців тому

    Is there such a thing as a ground fault that doesn’t trip the breaker on my main panel? Have a sump pump that trips the GFCI at the outlet, even when the pit is dry. but when I temporarily plugged it into a standard outlet it worked fine, doesn’t trip anything at the panel. Replaced the gfci with a new one and it still trips when the pump is plugged in.

  • @garyme7201
    @garyme7201 4 місяці тому

    Dustin, what are the steps to find a partial short in an a/c circuit? I have a multiple outlet circuit along with a garage opener. The garage opener motor burnt up and is disconnected. The circuit now has a low voltage of 46 volts.
    Gary

  • @ChristianRamosELCRVEVO
    @ChristianRamosELCRVEVO 7 місяців тому

    Ok I see what you did between hot and neutral. Can I test each conductor to ground? Like test for continuity to see if 1 of the wires is going to ground?

  • @JustinLorenzo63
    @JustinLorenzo63 Рік тому +1

    If all the wires were black,how could I identify the neutral and ground wire?

  • @goodolsparky9386
    @goodolsparky9386 Рік тому

    Great video !

  • @larrygwinn6649
    @larrygwinn6649 Рік тому

    Hi, how do you find a ground fault. I've checked all connections and replaced wire nuts and receptacle

  • @raulbotero982
    @raulbotero982 Рік тому

    Excelent video.

  • @kellyjaramillo9382
    @kellyjaramillo9382 Рік тому +1

    Can you do a video on fuses and what the interrupting rating means?