Diagnosing Daikin U0 Error⎪2

Поділитися
Вставка
  • Опубліковано 1 бер 2023
  • HVACR⎪HVAC⎪REFRIGERATION⎪AIR CONDITIONING⎪AIR CONDITIONER VIDEOS
    In this video I attend a break down where the unit is displaying a U0 Fault Code and won't run. I found the Outdoor Printed Circuit Board to be faulty.

КОМЕНТАРІ • 41

  • @robalexander7348
    @robalexander7348 Рік тому +1

    Nice vid Mitch, and good to see you on the job bright n early 08.10 👍 and luv the way that outdoor compressor is only mounted on loose bricks, also No 240v isolator 🙄

    • @maracservices
      @maracservices  Рік тому

      Definitely wasn’t installed by me that’s for sure 😂

    • @robalexander7348
      @robalexander7348 Рік тому

      @@maracservices Mate, it's sure not your work, we all now your quality work by now, maybe the owner would agree to wall mounting brackets being fitted as well 👍

  • @BERESHIDA2008
    @BERESHIDA2008 Рік тому +1

    Great videos

  • @liqfx982
    @liqfx982 Рік тому +2

    Informative video mate. I’m Keen to see the board replacement if you film it when you go back

    • @maracservices
      @maracservices  Рік тому +1

      Thanks mate, I’ll definitely record it but I’m not sure when because according to Daikin’s Global Data Bank there are no PCB’s available in Sydney. Which normally means none in Australia. Hopefully soon though.

  • @softroadingnewzealand5210
    @softroadingnewzealand5210 Рік тому +1

    I need to ship you a proper LA Dodgers hat haha. Great video and learning a lot from your channel…

    • @maracservices
      @maracservices  Рік тому

      Haha this hats the best mate. Been through a lot together!

  • @nguyenthechung
    @nguyenthechung Рік тому

    Thanks for your's share...!

  • @MentalLapse09
    @MentalLapse09 Рік тому +3

    Yeah definitely agree that inverter air conditioning pcbs are fragile when it comes to storms/surges.
    I like to put surge diverters in my quotes as a recommended option.

    • @maracservices
      @maracservices  Рік тому +1

      That’s a good idea. I’ll have to start doing the same thing!

  • @FreedomInMindtv
    @FreedomInMindtv Рік тому +1

    Nice one Rodney 🤙🏻

  • @kcomfortsystemshvac7060
    @kcomfortsystemshvac7060 Рік тому

    Nice video 👍 let’s say if you the unit it short the gas …what the best away to add r32 ? What type tecnic are you use it ? Thank you

    • @BERESHIDA2008
      @BERESHIDA2008 Рік тому +2

      when ever posible with a scale by weight , the unit has a label indicating how much the unit takes

    • @maracservices
      @maracservices  Рік тому

      Find the leak, fix the leak, evacuate the system and then weigh charge the gas back in 👍🏻

  • @nettoyageplusplus4947
    @nettoyageplusplus4947 3 місяці тому

    Comment vous avez testez la carte électronique ? Merci

  • @rodneycooper5474
    @rodneycooper5474 Рік тому +2

    Hey mate just wondering why all the resistance readings the same? For single phase shouldn’t the highest be between run and start, then start and common, then run and common?

    • @maracservices
      @maracservices  Рік тому +1

      It’s because it’s a 3 phase DC Compressor mate.
      Good question though!

    • @BERESHIDA2008
      @BERESHIDA2008 Рік тому

      In iverter motor it should read the same reading

  • @marzgtp
    @marzgtp Рік тому +1

    what is a U4 long beep? And what should I look for on my Daikin unit

    • @maracservices
      @maracservices  Рік тому

      Communication error between indoor and outdoor unit. It could be a fault in the interconnect wiring but most likely a faulty PCB.

  • @Rayray_unicornplayz567
    @Rayray_unicornplayz567 Рік тому +1

    Are you going to make a part 2 for it?

    • @maracservices
      @maracservices  Рік тому

      I am however Daikin don’t have any of those PCB’s in stock so we are currently waiting unfortunately.

  • @ClimateAdaptation
    @ClimateAdaptation Рік тому +1

    If the fuses don't have continuity could you replace them to try and get the PCB working again?

    • @maracservices
      @maracservices  Рік тому +1

      Yeah definitely however unfortunately in this case the fuses are fine and do have continuity. The issue is in the board.

    • @adrianvisintin1961
      @adrianvisintin1961 Рік тому +1

      @@maracservices I love how air conditioning company’s don’t put replaceable fuses 😅 . Can I ask what props you use to test small components

    • @maracservices
      @maracservices  Рік тому +1

      @@adrianvisintin1961 I know it’s so ridiculous hey.
      So my fluke meter came with prongs that I use 99% of the time but I found a really cheap no name multi meter laying around that had really sharp prongs. So basically I put the prongs in my bag to test plugs and what not. So to answer your question, I use no name Chinese leads for plugs and decent fluke leads for everything else haha.

  • @olliebulldog951
    @olliebulldog951 Рік тому +1

    Hi, have you ever had a u0 04 error?
    Daikin cant seem to figure it out and blaming airflow, however system was working fine for 3 years through many 40c days.
    Gas has been reclaimed and checked.
    Indoor coil thermistor replaced.

    • @maracservices
      @maracservices  Рік тому +1

      If it’s not short on refrigerant and a technician has confirmed this. You need to test the low pressure transducer is actually working. It might think it’s low on refrigerant when it actually isn’t.

    • @bmiadmin5784
      @bmiadmin5784 7 місяців тому +1

      Change brand next time mate, this brand is too much problem and gives you headaches....

  • @chiller-on
    @chiller-on Рік тому +1

    Well, at least they put it on the stones, they could just put it on the ground😁

  • @thomasmarchant4054
    @thomasmarchant4054 Рік тому +2

    Had this error before turned out to be eev. System was pumping itself down into a vacuum.

    • @josephwhite373
      @josephwhite373 7 місяців тому

      Was there frost on one side of eev

  • @myrah_adzy
    @myrah_adzy Рік тому +1

    hi mate ever had an e5 error?

    • @maracservices
      @maracservices  Рік тому

      Yeah mate that’s just an error code that comes up when the compressor gets to hot. Unfortunately there’s many things that could cause that so it’s impossible to tell you the exact problem without checking stuff but I can tell you that the compressor got too hot. Error comes on when the thermal overload is tripped which is located on top of compressor.

  • @tarekabuhijleh5638
    @tarekabuhijleh5638 5 місяців тому

    U0 error REFRIGERANT SHORTAGE

    • @maracservices
      @maracservices  5 місяців тому +1

      lol I know but it was not short on refrigerant. It had a faulty board

    • @tarekabuhijleh5638
      @tarekabuhijleh5638 5 місяців тому

      @@maracservices ok