  • When would a higher pressure stream reverse direction to the source of another stream that is at a lower pressure?
    00:00 Recap of mixing pressures
    01:18 How do you stop the lower pressure stream flowing?
    02:29 Capacity
    04:08 Non-return valves
    Process with Pat is the place to come for perspective and to ask stupid questions. I want you to leave more knowledgeable, confident, motivated, and most importantly, curious. I also want to invigorate a field that seems tired and uninspiring, at least if you get your perspective from internet forums. These are not lectures. This is a place for you to leave thinking “Oh! That’s why...”
    This channel is not only for chemical engineers - anyone who works with processes should be able to find something of value here.
    #ProcessEngineering
    #ChemicalEngineering
    #ProcesswithPat

КОМЕНТАРІ • 18

  • @eepower
    @eepower 11 місяців тому

    Great explanation Pat. Thanks for sharing your knowledge.

  • @ChemEngWeekly
    @ChemEngWeekly 2 роки тому +1

    Interesting video Pat! Good job 👍

  • @FirstnameLastname-fn6ik
    @FirstnameLastname-fn6ik 2 роки тому +1

    I think this is the second video you made to answer one of my questions lol (I'm the farticle guy), I can't thank you enough! I plan on watching all your videos, I'll try not to ask too many weird hypothetical questions that are out of my league. Sometimes my thoughts get ahead of my knowledge and I start asking questions when what I really ought to do is read a book.

    • @ProcesswithPat
      @ProcesswithPat  2 роки тому

      You’re going to have to start charging for royalties at this rate… Keep ‘em coming! Hope the explanations help, and if not then let me know!

  • @mavairick
    @mavairick 11 місяців тому

    Great, this was bothering me on the first video, now I understand ! thank you :)

  • @abdullahaidarous5290
    @abdullahaidarous5290 Рік тому

    Thank you very much for the amazing explanation

  • @affanbhaijaan65
    @affanbhaijaan65 2 роки тому +4

    Great insights which we can't get in university teaching 👌👌

    • @LaplacianDalembertian
      @LaplacianDalembertian 9 місяців тому

      I had this in my bedroom pipes with hot/cold water. Result is that temperature of mixed water is very hard to control with changing the outflow. In reality there could also be unstable outflow results with changing parameters, cause flow will be chaotic. If Reynolds number of the flow gets into some "periodicity" range, then mixed components will change over time periodically.

  • @bipl8989
    @bipl8989 11 місяців тому +1

    It is equally important what the upstream pressure does to the pressure at the junction. You have simply assumed those pressures fixed and then varied the flow rates as required to make those assumed pressures true. If you assume flow rates, rather than upstream pressures then, while holding downstream pressure constant, the upstream pressures must be adjusted to make the flow rates true. Or equally as valid, you can assume both upstream pressures and a downstream pressures as fixed, then calculate flow rates in all pipes to make the overall pressure drop true. It is NOT ONLY what the downstream pressure is that controls junction pressure. It is everything. Its only the downstream pressure that determines flows and junction pressure, because you assumed that and calculated the flows. If you assumed the flows, then you would have to calculate the downstream pressure, and as such, it would be the flows that controlled that result.

  • @dominicdelacruz1563
    @dominicdelacruz1563 Рік тому

    Is the NRV sufficient for reducing backflow if system dP is 12 bar and source a and b are 12 bar and 10 bar respectively?
    If the system dP is 10bar and you want to maintain the flow at converging point to be the sum of source a and b, can you just put an NRV and pressure reducing valve on source A so they have equal pressure at the tee?
    Asking as designing a water treatment system for data centre cooling where I need to mix mains water with ro water to dilute it and mains water is 8.5 bar (from booster set) and ro water is at 1 bar.
    Thanks

    • @ProcesswithPat
      @ProcesswithPat  Рік тому

      I can't really answer with a plain yes/no. NRV's leak, their seats erode, they aren't perfect. A theoretically perfect NRV doesn't care about the downstream pressure, it will stop reverse flow at any downstream pressure.
      But you do not need to install an NRV to get the right pressure at the point of mixing - the mixing pressure will always be equal, and that mixing pressure is a function of the system curve *downstream* of the mixing point.

  • @medotedo8410
    @medotedo8410 9 місяців тому

    If the downstream delt P = 10 bar then how can we achieve that the 10 bar stream will move downstream ?!
    I very very much appreciate and like your videos. I would suggest in the future adding a full example with a DEFINITE parameter (with magnetite) and working on it for better understanding.

  • @robcozens4432
    @robcozens4432 Рік тому +1

    Hello Pat, Thanks for posting this. I am considering changes to my water system, and this video (plus your video "Pressure, head, and pumping into tanks") seems to confirm my plan would work. However some people tell me my plan won't work, and I would really like the opinion of a person who understands hydrodynamics.
    My water source is a spring. The output from the spring is piped some distance downhill to a transfer tank and then pumped to storage tanks located at the highest point on my property. From the storage tanks the water flows downhill to a gully, uphill to the main building pad, and downhill again to a lower pad through the distribution line.
    Before I installed the transfer tank and solar pump the system was gravity-powered using a Highlifter pump located at the lowest point on my property, so the tank and pump were located near the existing input line. This makes the system difficult to maintain as I age and can no longer climb up and down the hill like a mountain goat, so I am considering moving them to a point near the spring and pumping the water into the storage tanks via the distribution line.
    In this scenario the storage tanks would occupy the 15 bar location on your diagram, the pump from the transfer tank would occupy the 10 bar location, and the tee to the house would be the mixing point. I have been told that pumping water back into the storage tanks via the distribution line will cause 'back flush" issues when I turn on a faucet or flush the toilet. I don't see why this should happen.
    If the pump is not running, the water will flow into the house from the storage tanks as it does now. If the pump is running, the water flowing into the house will come from the transfer tank, as the pump is operating at a pressure sufficient to lift the water all the way to the storage tanks. I can't see how it would make any difference whether that water going into the house flows in from the storage tanks via gravity or is pumped in from the transfer tank.
    Your comments would be greatly appreciated; thank you.

  • @asafj77
    @asafj77 11 місяців тому +6

    Hi Pat,
    I don't think the first part of the video is correct.
    If both streams are identical in terms of pipe size and configuration, at the mixing point they won't have the same pressure and the higher pressure stream will block off the lower pressure stream. You have to design the system so that they reach the mixing line in an equal pressure

    • @adershfrancis4981
      @adershfrancis4981 9 місяців тому

      Exactly. People are confusing fluid Statics with fluid dynamics

  • @affanbhaijaan65
    @affanbhaijaan65 2 роки тому

    Waao💥💥

  • @jeffreysokal7264
    @jeffreysokal7264 11 місяців тому

    With a positive displacement (gear) pump, never; with a centrifugal pump, always; this assume a liquid circulating system. If a gas system where pressure is controlled by a regulator, never, the 10 PSIG system's gas regulator would simply never open, so no reverse flow.

  • @icebluscorpion
    @icebluscorpion Рік тому

    Next up Tesla valve