Samsung air source heat pump handover for Homeowners. How to use the controller and how it works g5

Поділитися
Вставка
  • Опубліковано 25 лип 2024
  • This video explains to homeowners how to use and operate the Samsung range of heat pumps from 2015 - 2018. We explain how to use the unit, how it works and how to get the best out of it.
    Have you seen my new heat pump book? Its here on amazon. www.amazon.co.uk/dp/B0B1LY7MP...
    Or here graham-hendra.sumupstore.com/
  • Наука та технологія

КОМЕНТАРІ • 61

  • @assegai1816
    @assegai1816 6 років тому +2

    Just excellent, thank you. Clear, well paced and straightforward explanation.

  • @michaelgreen5515
    @michaelgreen5515 6 років тому +2

    Really useful thanks

  • @jeffjeffjeff2
    @jeffjeffjeff2 6 років тому

    Excellent video with a nice clear explanation. Could you show how to adjust the high temperature setting for the heating on the RC090MHXEA unit please?

  • @B7BREMAPPING
    @B7BREMAPPING 5 років тому +1

    Really useful thank you. Apparently My aux controller does not start the heating in the house.

  • @Loopyengineeringco
    @Loopyengineeringco Рік тому

    Great video, thank you - helpful for lots of people. Can you explain how to change the WC curve on the Samsung system?

  • @burakokumus6040
    @burakokumus6040 Рік тому

    Thank you very much!

  • @caitlinlewis6320
    @caitlinlewis6320 Рік тому

    Hi Graham, thanks for this video. Just moved into a new house and trying to work out how to work this heating system, as the house is freezing. Can you tell us about the “Temp” setting on the bottom left? The place that you said should say “AU” says 5 degrees on ours and I can’t seem to change it 🤔

  • @bryandonoghue1429
    @bryandonoghue1429 3 роки тому

    My heat pump outside is covered in ice us this normal.should the filling loop on the tank be opened or closed

  • @edwardobrien4614
    @edwardobrien4614 Рік тому

    Hi, was just wondering if you had a video on how to set up weather compensation, I have a Samsung 12kw 5 generation, Regards eddy

  • @lloydowen6900
    @lloydowen6900 7 місяців тому

    You know the taps on the water circulation pump for the radiator, are they to adjust the flow rate? Like on a brass garden tap?

  • @trelamenos250
    @trelamenos250 3 роки тому

    Hi. I would like to ask how do I put the system on AU.i do not see anywhere this symbol in my controler. I bought my heatpump 1.5 year ago.

  • @doityourselfprojects5744
    @doityourselfprojects5744 5 років тому

    Hello ! Does it worth it to buy a Samsung gen 5 heating pump? Is it reliable this model/brand ? Thank you !

  • @mattpotter7941
    @mattpotter7941 2 роки тому

    I repeatedly set the DHW to ‘standard’ (2dots), but each day it will automatically rest to ‘power’ (3dots). Even lowering the target water temp to 42 degrees, it still does the same. Any ideas how to overcome this?

  • @Demise09732
    @Demise09732 Рік тому

    Got the same heating pump outside the house, I think it's might be a Gen 3, but not 100% sure. Can you please let me know what the error 911 is?

  • @paraicomeara6833
    @paraicomeara6833 2 роки тому

    Great video, thanks. Any idea how to adjust the date and time settings on the main Samsung controller? Shouldn't need a technician for such a task I feel. Thanks.

    • @paraicomeara6833
      @paraicomeara6833 2 роки тому

      All good, I found what I was looking for in your other video - ua-cam.com/video/vaYSq9z5XUY/v-deo.html
      Thanks a million, that has been really bothering me for quite some time!

    • @Anyaro
      @Anyaro Рік тому

      @@paraicomeara6833 hey this video doesn’t seem to work, could you explain how to adjust the day and time?

  • @rop44991
    @rop44991 3 роки тому

    Excellent, so the system should not be running any timer nor daily or week for optimum usage ?

  • @Tom69873
    @Tom69873 3 роки тому

    Hi. Can I change somewhere temp of the water in the installation? I wonder if current temp will be comfortable at the winter time. When radiator is heating I can fell just a bit warm(but temp in the room is raising+very good isulation)
    And also, sometimes when the heating is on, temp. of. the water in the installation is 36,last time was 42.
    I'll be gratefull for advice

    • @myheatpumpchannel7577
      @myheatpumpchannel7577  3 роки тому

      yes you need to set it all up in the field settings there are water setting in there.

    • @Tom69873
      @Tom69873 3 роки тому

      @@myheatpumpchannel7577 there is lot of water parameters there 😂 I don't want fucked up, this is rented house

    • @ninjamon1984
      @ninjamon1984 2 роки тому

      Hi, I have just moved in the new house and have the same issu as you have, temperature is set at 27 degrees but radiartors are just mild worm, however in the house its worm, just wandering in winter time will this be the same?

  • @abigailm7043
    @abigailm7043 5 років тому

    Hello, when you say you should see the au letters/sigh on the bottom left hand corner. I don't see that on mine. I see the the temperature numbers on mine. Is this OK?

    • @myheatpumpchannel7577
      @myheatpumpchannel7577  4 роки тому +3

      yes you have a newer version of the same controller, au on old controllers 0.0C on new

  • @imaaplumbing9417
    @imaaplumbing9417 3 роки тому

    Hi, how do you add the liquid into the system after installation sir

  • @ronanmcdonagh5793
    @ronanmcdonagh5793 3 роки тому

    How do I cool down the house? It's showing 30c on thermostat. The heater has the sun symbol-is there a way to cool it?

    • @myheatpumpchannel7577
      @myheatpumpchannel7577  3 роки тому

      if im honest, no its a heating device, if you have it wired and configured for cooling it can do this but you cant do this through radiators and underfloor heating

  • @kensutherland2086
    @kensutherland2086 3 роки тому

    My boiler is set at 0, but where i live (in the North of Scotland) but the house is cold when the weather is very cold. How do I increase this ?

    • @myheatpumpchannel7577
      @myheatpumpchannel7577  3 роки тому

      you really need to set the field setting 2021 and 2022 higher but boost the setting on the screen from0 to plus 2 uising plus button and it should help, its best to get your installer to set this up for you though.

  • @JT-mj3gz
    @JT-mj3gz 3 роки тому +1

    Hi! When DHW is on system sometimes heats floor systems water through the water tank which then drops temp in the tank and then turns on DHW heating. That is not cost effective.
    Why is this happening and how do I fix this?

    • @myheatpumpchannel7577
      @myheatpumpchannel7577  3 роки тому +1

      sounds like you need someone to come and wire it up properly. best call the installer back to cehck it out

  • @ronanmcdonagh2677
    @ronanmcdonagh2677 3 роки тому

    I don't see the heat symbol in top left. Any ideas? Its brand new installation

  • @liammadden118
    @liammadden118 Рік тому

    Moved into 5 year old house recently with radiator Samsung heat pump. Should the heat pump be running all the time even in the night time? Could I switch it all day and off at night?

    • @fieldvole
      @fieldvole Рік тому

      It should run all day and night. You can set it to run at a lower temperature at night.

  • @paulrush-1478
    @paulrush-1478 Рік тому

    Thanks Graham, much appreciated. It's a shame Samsung don't do a better handbook.
    Do you know anything about the WiFi Controller Kit? Before I get one I'm wondering if it will control the hot water. Again, the manual on the Web is rubbish!

    • @myheatpumpchannel7577
      @myheatpumpchannel7577  Рік тому

      dont buy the wifi kit there are much better internet controllers, heatio, homely fhp cloud etc that work much better

    • @paulrush-1478
      @paulrush-1478 Рік тому

      @@myheatpumpchannel7577 that's great thank you, I assume that they have to be wired in much the same way as the Samsung one?

  • @alfredmanner6881
    @alfredmanner6881 11 місяців тому

    Hope to get some advice, so some rogue builders plumbers installed my air source geothermal heating system, for hot water and heating, the outdoor unit is a Samsung ae050rxydeg, the system went live a week ago, now got tap water works fine but my radiators aren't getting hot, when I turn the temperature up on my EHP RF thermostat, the outdoor unit comes on and the heat source loop heats up but both the radiator outlet, radiator return remains cold, I suspect either the radiator have not been filled to the correct pressure bar so the system is not circulating radiator water or the pump for the radiators have not been wired in correctly, any advice is appreciated

    • @myheatpumpchannel7577
      @myheatpumpchannel7577  10 місяців тому +1

      you need to get the installer back, they have clearly not commissioned it properley

    • @alfredmanner6881
      @alfredmanner6881 10 місяців тому

      Thanks for the prompt reply, I found that some of the radiators had a lot of air and needed bleeding, having done that myself, I went to the hot water tank and saw the radiator pressure was 1.2 bar where I've read it should be 2 bars on a cold system, so I'll need to top it up but at the moment the master feed to the radiators is a little more then warm but the return is ice cold. I think it might be just setting for the weather compensation, I don't think these incompetent lot set any of that.
      They'll probably just set the temperature to max so the immersion heat element is always running. You're video is really helpful.
      Thanks

  • @hkareno
    @hkareno 3 роки тому

    I have e911 error and I think the water flow is too low. How to increase the flow?

    • @myheatpumpchannel7577
      @myheatpumpchannel7577  3 роки тому

      clean the filters first then get the plumber back and get him to check the pipework, remove air and any crap in the system etc good luck

  • @matthewhandley2340
    @matthewhandley2340 2 роки тому

    Radiators only warm not getting hot when thermostats kick in, brand new house

    • @myheatpumpchannel7577
      @myheatpumpchannel7577  2 роки тому

      i dont know who installed this but this is correct, they need to tell you this. search for the handover video i explain all

  • @silentswordg4644
    @silentswordg4644 Рік тому

    Instead of the AU, it shows temperature. Any idea why?
    Also, the radiator is not heating up but the water is warm.

    • @kevinferry1181
      @kevinferry1181 Рік тому

      Mines is the same, no AU symbol just says setting 0.00

  • @Nick-sd4lr
    @Nick-sd4lr 8 місяців тому

    How do unlock the keyboard ?

  • @mattyjamess7818
    @mattyjamess7818 3 роки тому

    Hello, mine doesn't say AU just says 0.c is that okay ?

    • @myheatpumpchannel7577
      @myheatpumpchannel7577  3 роки тому +1

      yes its just a newer or older version

    • @will1569
      @will1569 Рік тому

      @@myheatpumpchannel7577 this is the same as mine and it can be changed. What should it be set at for the winter ? Or what does it actually do. It can go to minus 5 and + 5

  • @aileenfoley7182
    @aileenfoley7182 3 роки тому +1

    What do you do if the sun symbol doesn't come up after the electricity was turned off for 20 minutes. . .the tap and other symbols are there just not the sun 🤔

  • @mariusstelu6799
    @mariusstelu6799 2 роки тому

    hi there, my name is Marius, i have a heat pump like this, i need to instal a room thermostat, can you send me a electrical diagram?

    • @myheatpumpchannel7577
      @myheatpumpchannel7577  2 роки тому +1

      how i do this through you tube is anyones guess. if you watch the training videos for midea wiring it shows how to connect the stat up

  • @ginofellino69
    @ginofellino69 4 роки тому

    On my controller, when in heat mode, it only allows me to adjust between -5 and +5 degrees in .5 increments.
    What temperature should I set this too? What does this temperature do?
    Appreciate any help!

    • @myheatpumpchannel7577
      @myheatpumpchannel7577  4 роки тому +1

      always set it to 0, the temperature is controlled by the ambient temperature outside you cannot change this from the controller unless you are in the service mode

    • @ginofellino69
      @ginofellino69 4 роки тому

      @@myheatpumpchannel7577 thank you! 🙏