DP Flow Transmitter Calibration- Transmitter Zero and Span Adjustment

Поділитися
Вставка
  • Опубліковано 3 гру 2024

КОМЕНТАРІ •

  • @dedyapria1177
    @dedyapria1177 2 роки тому +2

    At 0:46 Why don't you close the high pressure block valve first instead?

  • @yassertantawytantawy184
    @yassertantawytantawy184 2 роки тому +1

    Thanks you for your video
    But I think the sequence to back the transmitter to service it's first open the valves of process isolation and close the equalizer in the end to prevent sell damage
    Because the low side have atmosphere pressure and high side well have process pressure and it's high delta pressure can cause cell damage

  • @mathewgeorge1576
    @mathewgeorge1576 Рік тому +1

    Thanks sir ji ✋

  • @janetawuah2535
    @janetawuah2535 3 роки тому +1

    Thanks for your great videos...but I thought the square root extractor function is in built in the flow transmitter, so why ignore the mA readings due to the square root extractor when calibrating? Can you please explain I'm a beginner

    • @InstrumentCalibration
      @InstrumentCalibration  3 роки тому

      Thanks for asking. All SMART transmitter comes with function to select square root extractor. If you do not select square root extractor at transmitter side. Then you need to select at PLC or DCS side.

  • @abysebastian2597
    @abysebastian2597 2 роки тому +2

    Sir, how this arrangements comes practically possible. This is because LP and HP are kept close together. Since the equalizer is open, will not the air pressuse applied in HP go into the atmosphere through LP..?

    • @InstrumentCalibration
      @InstrumentCalibration  2 роки тому

      Thanks for asking this question.. When we do calibration, both HP & LP Valve remains closed, and equalizing valve also remains closed. After this, open up LP vent valve, and apply pressure through HP vent valve.

  • @Nicofish2023
    @Nicofish2023 2 роки тому +1

    Please can you do this with a 5 way manifold showing all the steps of calibration

  • @mohamadsyahirsabar4097
    @mohamadsyahirsabar4097 2 роки тому +1

    Can u explain in details how the DCS do the calculation to get (from sqrt of mA to the flow rate in GPM). Why do we need the sqrt mA?

    • @InstrumentCalibration
      @InstrumentCalibration  2 роки тому

      Hello I don't have calculation formula for DCS. Flow rate is directly proportional to square root of differential pressure. In order to convert, dpt' s output into linear, We use square root extractor in dpt.

  • @bino1336
    @bino1336 3 роки тому +1

    Without assuming
    Correct dp can u tell me that

  • @mikegrande4957
    @mikegrande4957 20 днів тому

    Valve positions during calibration?

  • @mohammadimtiyaz5824
    @mohammadimtiyaz5824 2 роки тому +1

    Sir during calibration when apply pressure, low side and equalise keep open or close, plz clear my doubt

    • @InstrumentCalibration
      @InstrumentCalibration  2 роки тому

      Hello Mohammad
      when you apply pressure, low side and equalize both valves should be in closed position.

  • @abdulkader-lh9mj
    @abdulkader-lh9mj 5 місяців тому

    How to get analog output ma from del p inwater column?

  • @denildavis3561
    @denildavis3561 3 роки тому +1

    Where we connect calibrator when we use 5 way manifold

    • @InstrumentCalibration
      @InstrumentCalibration  3 роки тому +1

      You need to connect pressure calibrator to bleed valve after putting PT in service mode

    • @denildavis3561
      @denildavis3561 3 роки тому +1

      @@InstrumentCalibration ok thank you sir

    • @InstrumentCalibration
      @InstrumentCalibration  3 роки тому +1

      @@denildavis3561 You are welcome. Feel free to ask me any question

  • @bobbyyoung2831
    @bobbyyoung2831 7 місяців тому

    Need to close the equalization valve Before pumping up. AND the pressure calibrator needs to be liquid...Air compresses. Nice video but left out a few things.

  • @bino1336
    @bino1336 3 роки тому +1

    Sir
    How to calculate the applying pressure?

    • @InstrumentCalibration
      @InstrumentCalibration  3 роки тому +2

      It depends on your range. For example, if your dpt's calibration range is 0 to 100 inch H2O. Then divide 100 inches H2O into 5 equal part, and apply the pressure according to it.

  • @bino1336
    @bino1336 3 роки тому +1

    For flow transmitter

  • @abdulrozak514
    @abdulrozak514 2 роки тому

    whats name the calibrator?

    • @InstrumentCalibration
      @InstrumentCalibration  2 роки тому

      Hi dear , i would recommend use the calibrator attached in the link below. It is efficient and easy to us
      amzn.to/3LIy93f

  • @hardyferrysian4813
    @hardyferrysian4813 2 роки тому +1

    in my humble opinion the step for calibration is
    1. open the equalizing valve
    2.close together high and low block valve
    we need eqaulizing first, if we close the low or high block valve before equalizing valve then the transmitter will damage
    flow transmitter have Differential range maximum base on maufacture data sheet

  • @الطيرالمهاجر2012
    @الطيرالمهاجر2012 3 роки тому +1

    The sequence of return it back to service is not accurate

  • @nomnamecpp
    @nomnamecpp 3 роки тому

    Don't call it calibration
    It's calibration check

    • @InstrumentCalibration
      @InstrumentCalibration  3 роки тому

      Yes... you are right. It is Verification Test

    • @janetawuah2535
      @janetawuah2535 3 роки тому

      Can you please explain the difference? I'm a beginner.

    • @nomnamecpp
      @nomnamecpp 3 роки тому

      @@janetawuah2535 what part you didn't understand?