GIS BUS BAR HIPOT TEST

Поділитися
Вставка
  • Опубліковано 29 сер 2019
  • GIS BUS BAR HIPOT TEST
    I am going to do Bus bar hipot test
    Before going into Test we have to check the following things
    1. Open earth switch.
    2. Rack out VT
    3. Check The barricade around Testing Area.
    4. IR test has to conducted before hipot testing.
    5. Check the humidity of the place.
    In GIS we have to use a special termination cable for doing hipot
    In this video i have show only for Y phase hipot full video without cut and editing

КОМЕНТАРІ • 28

  • @abidali.6873
    @abidali.6873 8 днів тому +1

    Very interesting

  • @syeduddin1789
    @syeduddin1789 2 роки тому +1

    👍👍👍

  • @nafeesakhtar796
    @nafeesakhtar796 4 роки тому +1

    What is the permissible leakage current for a successful Hipot of 33 kV GIS?

    • @khawajaadil4780
      @khawajaadil4780 3 роки тому +2

      there is no certain value of leakage current . actually it depend the no of switch gear under test. i will explain you more . if the leakage of one no swg is 10 ma then suppose your switch gear is of 4 no then obviously the leakage court will be 4X10 =40 ma and so on for 10 no switch gear it will be 10X10=100ma. Generally it depend upon the bus bar length. longer is the length higher is the leakage also note down that the capacity of the test set is very important . as the leakage current is coming from the test set now you calculate the capacity of the test set. suppose the you are excepting current 100ma at 70 kv then the capacity of the step up transformer will be 0.010X70000=7000watts=7.0 Kw. so in size du to high insulation it will be of big size and it be difficult to build and hence cost will be more. Now come to the point the high voltage test is a "go" or "no go" test as for as insulation is not break down the test will be declared pass the amount of leakage current is not a deciding factor.

  • @safwank2652
    @safwank2652 Рік тому

    Thankyou Dear

  • @aftabraj1865
    @aftabraj1865 4 роки тому +1

    Please add more videos related with GIS

  • @moussedekfarouk5843
    @moussedekfarouk5843 7 місяців тому +1

    Hello can you tell me how to discharge the switchgear to ground

    • @baranitech1026
      @baranitech1026  4 місяці тому

      after testing we have to use discharge rod thank you.

  • @miteshgorfad2637
    @miteshgorfad2637 2 роки тому +1

    What is MA current following is abnormal condition???

  • @user-fq1ij3sn8t
    @user-fq1ij3sn8t Рік тому

    How much leakage current accept for AC Hipot test?

  • @eng_mohammadaljazairy4082
    @eng_mohammadaljazairy4082 2 роки тому

    What do you mean by IR test ?

    • @baranitech1026
      @baranitech1026  2 роки тому

      to check the insulation level of the equipment

  • @velusamypothiraj2300
    @velusamypothiraj2300 4 роки тому

    Is this AC hipot kit or dc hipot

    • @nafeesakhtar796
      @nafeesakhtar796 4 роки тому +1

      Hi sir
      How DC Hipot???
      but the formula you used here is of AC Hipot 80%Vp plz explain??

    • @user-fq1ij3sn8t
      @user-fq1ij3sn8t Рік тому +1

      Busbar Hipot test AC, cable Hipot test DC used. 2E+1 80 % kV accept for 1 or 5 minutes depend upon on customer Requirement.

    • @velusamypothiraj2300
      @velusamypothiraj2300 Місяць тому

      @@user-fq1ij3sn8tSO,HERE AC HIPOT BEING TESTED, what about dc HIPOT voltage limit

  • @ajithrojaajithroja
    @ajithrojaajithroja Рік тому

    Need to give 2.2 times of rated voltage of bus bar in highpot test

  • @fahmiramadhan2328
    @fahmiramadhan2328 3 роки тому +1

    Dinesss

  • @haruntangdiarrang8897
    @haruntangdiarrang8897 Рік тому

    Oh indonesian Objecct

  • @abidali.6873
    @abidali.6873 8 днів тому +1

    Very interesting