High impedance busbar protection

Поділитися
Вставка
  • Опубліковано 8 лип 2018
  • This video introduces the basic principles behind HIGH IMPEDANCE BUSBAR PROTECTION, and is a sample from the 2.5 hour long course ELECTRICAL CONTROL AND PROTECTION PART 3 available on UDEMY, use the following link to access the course..
    www.udemy.com/course/electric...
    If you need a $10 discount voucher please drop me a message!!
  • Наука та технологія

КОМЕНТАРІ • 35

  • @JyullianoRocha
    @JyullianoRocha 5 років тому +6

    Please, keep creating more content about electrical systems protection. Amazing lecture.

    • @Electricalsteve
      @Electricalsteve  2 роки тому

      Hi,
      Go to the Udemy website, search for courses under my name ( Stephen brooks ) & use the voucher code WETT1001 to get them for $9.99
      Regards
      Stephen Brooks

  • @satyayadav9535
    @satyayadav9535 3 роки тому

    Thanx Mr. Steven for doing great job for educating the young engineers.
    I pray God to give you peace and prosperity in your life.
    Satya
    From India

  • @alfabiro7226
    @alfabiro7226 5 років тому

    Thank you for this useful video!

  • @alliservices8885
    @alliservices8885 2 роки тому

    Thank you Mr. Brooks.

  • @abhishekpatel8038
    @abhishekpatel8038 Рік тому

    So nicely explained Sir. Is there also a video on case where a Feeder CT saturates during external fault and explanation on the stabilizing resistor and MOVs?

  • @anithaid894
    @anithaid894 6 років тому +1

    Thanks, upload more. Its very useful.

    • @yogeshwaranramanathan6116
      @yogeshwaranramanathan6116 6 років тому

      This high impedance relay same time voltage also developed please mention developing voltage

    • @Bitcoinminds
      @Bitcoinminds 5 років тому

      Hi anitha what degree u r doing

  • @MrJasonmkennedy
    @MrJasonmkennedy 2 роки тому

    The 5 A secondary rating of the CT always raises questions with students when they see 65A of current flowing during a fault! Intuitively they don't expect to see any current greater than 5 A.!

    • @Electricalsteve
      @Electricalsteve  2 роки тому

      Hi Jason,
      Agreed!! I have seen CT wiring connected to telecoms terminals through tiny wiring as the installer doesn’t appreciate that the primary system fault current of 1000’s of amps gets fed through to the CT secondary wiring….
      steve

  • @abbasdairawy390
    @abbasdairawy390 8 місяців тому

    thank you

  • @TatanziAnita
    @TatanziAnita 4 роки тому

    great lecture

  • @vipulwadkar8502
    @vipulwadkar8502 11 місяців тому

    Informative 👍

  • @rahulwable9231
    @rahulwable9231 6 років тому +1

    Nice video, you have explain current on incoming side of main bus bar, please explain on outgoing side of current rating, and bus bar sizing

  • @bharathi6898
    @bharathi6898 4 роки тому +1

    Nice job sir... I hav one doubt
    while any fault occurs in busbars how could you say current flows only in B feeder is null.... there Busbar is common for all the feeder isn't?

  • @user-qd4lf7bd4k
    @user-qd4lf7bd4k 3 роки тому +1

    During the Short circuit moment why do the feeder B C D's currents are not becoming zero?

    • @Electricalsteve
      @Electricalsteve  3 роки тому

      Hi,
      Because the generators are feeding energy ( current ) into the fault, this will continue until the protection operates ( which it should ) or the generator voltages collapse. steve

  • @FPV-TV419
    @FPV-TV419 5 років тому +1

    Steve great great videos. How do I find your content on the university site? I can't seem to search you as a teacher?

    • @Electricalsteve
      @Electricalsteve  5 років тому

      Hi,
      Go to the Udemy website, search for courses under my name ( Stephen brooks ) & use the voucher code WETT1001 to get them for $9.99
      Regards
      Stephen Brooks

  • @RK20505
    @RK20505 4 роки тому

    hai sir, have great lectures a may i know what software you have use to expliantion ?

  • @shazebhashimkhan3009
    @shazebhashimkhan3009 2 роки тому

    Why Feeder B breaker is OPEN when fault occurred at BUS

    • @Electricalsteve
      @Electricalsteve  2 роки тому +1

      Hi Shazeb, for the example shown the fault was on feeder B, outside the busbar protection zone. The protection correctly identifies this and only opens the feeder B circuit breaker, disconnecting the fault from the system
      Regards
      steve

  • @delosmark18
    @delosmark18 4 роки тому

    Aside from udemy where can i buy your videos? I have problem in linking my paypal/cc with udemy

    • @Electricalsteve
      @Electricalsteve  4 роки тому

      Hi,
      Go to the Udemy website, search for courses under my name ( Stephen brooks ) & use the voucher code WERD1001 to get them for $9.99, vouchers expire in 5 days.
      Regards
      Stephen Brooks

  • @softurial8123
    @softurial8123 4 роки тому

    If 2 Incomer 1 Buscoupler scheme employed then what will be the connection of CT.

    • @Electricalsteve
      @Electricalsteve  4 роки тому +1

      Hi,
      Go to the Udemy website, search for courses under my name ( Stephen brooks ) & use the voucher code WERD1001 to get them for $9.99, vouchers expire in 5 days.
      Regards
      Stephen Brooks

  • @Onepiece-hp1ih
    @Onepiece-hp1ih 4 роки тому

    Please sent me sir single line diagram up stream to down stream please