Current Distribution In a Delta Star Transformer for 3-PH , Double Phase and Phase to Ground Fault

Поділитися
Вставка
  • Опубліковано 14 жов 2024

КОМЕНТАРІ • 8

  • @rjshtk
    @rjshtk Рік тому

    Superb video! Clarifies a lot of doubts!!

  • @mohdrhaiz8146
    @mohdrhaiz8146 Рік тому

    Good video. Can you also show the effects to the voltage too when the faults happens?

  • @arkaprabhahaldar9570
    @arkaprabhahaldar9570 11 місяців тому

    very helpful. Sir, can you explain why we are taking turns ratio 1.73 ie keeping the primary line voltage = secondary line voltage ?

    • @chagassena1
      @chagassena1 5 місяців тому

      You can understand that analyzing the ratio of the transformer RT. Just like that RT=VAB/(Vab/1,73)=>RT=1,73*VAB/Vab, where RT in PU is 1.

  • @johnreyalforque5577
    @johnreyalforque5577 6 місяців тому

    Hello! sir. have not seen any book or lecture explaining why fault current is 0.86pu for a wye-delta transformer during fault at delta side. Can you also discuss?

    • @chagassena1
      @chagassena1 5 місяців тому

      Because he is taking the three phase fault as reference. The phase to phase fault is about 0,87 of a three phase fault. It' is important to say these values are in PU.

  • @gustavomarcelo7250
    @gustavomarcelo7250 Рік тому

    Hi.Why for Phase ro Phase it is 0.87 pu?

    • @chagassena1
      @chagassena1 5 місяців тому

      Because he is taking the three phase fault as reference. The phase to phase fault is about 0,87 of a three phase fault. It' is important to say these values are in PU.