Another really interesting video James. Ref Ev issue with PME, we are told that to assume a Tns is a Tncs( unless the DNO can confirm a true TNS) does this then mean that the bonding/earthing of this supply would then be sized for a PME?
I would recommend to always size for PME then. 10mm minimum. The difference in your quote to the customer will be negligible and you have peace of mind always then
Thanks Michael, I'm glad you found the video interesting. If you are working on the basis that it could be a TNC-S then yes, I would select the bonding and earthing conductors for a PME. Regards James