Elevator Fire Service Demo (All Phases)

Поділитися
Вставка
  • Опубліковано 29 сер 2024

КОМЕНТАРІ • 68

  • @flightlevel3608
    @flightlevel3608 Рік тому +5

    3:20 You don't need to leave the key in the "Reset" position. Just turn it to "Off" after resetting for a second or two and the system will complete the cycle itself, even if the elevator is recalling to a different floor during reset.

  • @DatamasterCorporation
    @DatamasterCorporation 4 роки тому +7

    They really should make that indicator say, 'Please exit when doors open' I don't think most people would understand what that symbol means.

    • @h-aandle
      @h-aandle Рік тому

      PL
      EA
      SE
      EX
      IT
      TH
      E
      EL
      EV
      AT
      OR
      WH
      EN
      TH
      E
      DO
      OR
      S
      OP
      EN

    • @h-aandle
      @h-aandle Рік тому +3

      actually wait on some other otises like the series 1 it does say it

    • @IanGSully
      @IanGSully Рік тому +1

      @@h-aandle Most elevators that talk do

    • @flightlevel3608
      @flightlevel3608 Рік тому +1

      This elevator is not equipped with a vocab feature since it's not a mid to high rise building. If it was, it would say that.

    • @thatonecanadian.7102
      @thatonecanadian.7102 13 днів тому

      ⁠​⁠@@flightlevel3608There actually is a voice module on newer Otis elevators like this one (Series 5). They just decided to turn the Module off since like you said, it’s not a mid or high rise building.
      Vocabulary words can be triggered by resetting the elevator (Off and On). Once it’s fully initialized it will start the Vocab (As far as I know).

  • @jonahladuke7607
    @jonahladuke7607 2 роки тому +1

    Well at least I know how to operate an elevator in case of emergency great instructional video I appreciate it I'm going to save it

  • @chrisgonzalez5684
    @chrisgonzalez5684 3 роки тому +3

    Good job you did a nice work

  • @michaelglissonjr9490
    @michaelglissonjr9490 6 років тому +4

    Now this is cool. Nice job!

  • @relevanteaglealarms109
    @relevanteaglealarms109 4 роки тому +3

    It’s is likely an nudge mode during fire mode.

  • @Jamestube8439
    @Jamestube8439 6 років тому +5

    The first test for when the elevator moved to the 2nd floor, how do you reset it? With the phase l fire key switch on floor 1

    • @safetech
      @safetech  6 років тому +3

      That is correct. Fire service mode can be cleared after the initiating device that tripped it has been reset.

    • @Jamestube8439
      @Jamestube8439 6 років тому +2

      Ok, thanks

    • @Jamestube8439
      @Jamestube8439 6 років тому +2

      Awesome, I'll check it out.

  • @toddthegamer
    @toddthegamer 6 років тому +16

    That elevator sounds like it has a dover buzz

    • @smartyblooper4141
      @smartyblooper4141 6 років тому +2

      but on newer thyssenkrupp has grocery store beep

    • @GardenStateElevators
      @GardenStateElevators 6 років тому +3

      Samantha LindenbaumFinch All Otis elevators from the early 1980’s to present have these buzzers for nudge mode and fire service.

    • @smrtc651productions
      @smrtc651productions 5 років тому +2

      and series 1

    • @toddthegamer
      @toddthegamer 4 роки тому +2

      @NeedNova oh ok

  • @seanjuth
    @seanjuth 3 роки тому +2

    It's weird how when you activated the smoke detector in the machine room the elevator re-leveled

  • @seanjuth
    @seanjuth 3 роки тому +1

    Did you have to access the hoistway in order to test the smoke detectors in the shaft? I see you have a full set of Otis keys, but obviously due to how dangerous it is, you probably wouldn't want to be filming, in fear of simplex seeing this.

  • @WheeloveFireAlarms
    @WheeloveFireAlarms 6 років тому +3

    Awesome! I never knew how that worked! That’s really cool.

  • @VOLTRONDEFENDER4440
    @VOLTRONDEFENDER4440 5 років тому +1

    The door close button is a different kind it was probably replaced because the other one doesn’t work

  • @davidredpath4781
    @davidredpath4781 6 років тому +7

    Great video!

  • @212Elevators
    @212Elevators 2 роки тому +1

    If the heat detector in the machine room is activated before the smoke or the smoke in the shaft activates, what does it do?

  • @ruthdelgado6748
    @ruthdelgado6748 6 років тому +2

    not always but some ev you have to enabele to enable phase 1

  • @twentyfour44
    @twentyfour44 6 років тому +7

    What type of alarms were there and how did you disable them on a 4006

    • @ShaunPuzon
      @ShaunPuzon 6 років тому +1

      He said in the description that this building has a separate FACP dedicated to the elevator system. There may not have been any notification appliances connected to that panel.

  • @seanjuth
    @seanjuth 3 роки тому +1

    It looks like Otis didn't properly adjust the auxiliary recall functionality

  • @jorgeflores9381
    @jorgeflores9381 3 роки тому +3

    Question to all fire alarm experts, does turning on fire service trigger a response from the fire department?

    • @safetech
      @safetech  3 роки тому +2

      Not from what i’ve seen by turning the fire service key. However some elevators may have some special configurations to do so.

    • @frazierg0325
      @frazierg0325 Рік тому +1

      NO

    • @flightlevel3608
      @flightlevel3608 Рік тому +1

      Using elevator fire service as a standalone (test and demo) will not trigger a response from the fire department. However, if the FACP is programmed it will send a signal if the entire building alarm system is triggered.

  • @user-tw4vi3uv1r
    @user-tw4vi3uv1r 3 місяці тому

    @safetech An elevator should never be recalled by a manual pull station or detectors in other facility areas unless specified by the AHJ. IS THERE A REASON FOR THIS.

  • @brianthetowerguy979
    @brianthetowerguy979 6 років тому +2

    This was awesome !

  • @embeddedgirl
    @embeddedgirl 6 років тому +1

    Any particular reason why you would want to deticate an entire 4008 just for the elevator? My guess would be to keep programming simple on the main panel. Though regardless of how many floors the elevator services it'd be overkill for 2 or 3 floors, and redundant for 8-12 floors being that's it'd just be easier to program that into the main panel. (Most likely a 4100 series and at that point it's going to take more than a day to program anyway)

    • @safetech
      @safetech  6 років тому +2

      This facility does not have a main fire alarm therefore the 4008 is in place for the elevator safety controls and as a means to dial out to monitoring.

    • @embeddedgirl
      @embeddedgirl 6 років тому +1

      SAFETECH ahhh ok, that makes more sense now. Thanks!

    • @frazierg0325
      @frazierg0325 Рік тому +1

      Some occupancies don't require a fire alarm so the panel is for recall only.

  • @josepeixoto3715
    @josepeixoto3715 3 роки тому +1

    FACP?
    got it: Fire Alarm Control Panel

  • @Emmisullivan14
    @Emmisullivan14 5 років тому +1

    What happens if the smoke detectors are triggered on both floors and there's a fire on both floors at the same time?

    • @edgarmartinez7371
      @edgarmartinez7371 4 роки тому +2

      In situations in which smoke detectors are triggered on all floors, most elevators will send a signal to the machine room and the fire alarm control panel to 'shunt trip (or disable)'; the only form to restore its memory is resetting the FACP and the machine switch

  • @jorgeburgos3405
    @jorgeburgos3405 3 роки тому +1

    The elevator is a Otis Series 5

  • @blue.light.fazbear
    @blue.light.fazbear 6 років тому +1

    What is the buildings main system

  • @Kasey1776
    @Kasey1776 6 років тому +4

    Cool!

  • @Aaronproductions
    @Aaronproductions 6 років тому +3

    Nice man, I love watching what it’s like to be a tech. Does Simplex give you permission to upload these videos? Just wondering Because somone uploaded Simplex videos and the company fired them before.

    • @safetech
      @safetech  6 років тому +6

      Aaron Productions
      Thanks for viewing and for your comment. I would first like to ask where in fact you got the information regarding what your claiming happened? Also, I respect all rights to privacy and never will you see me recording in unauthorized settings or areas not accessible to the general public. All location information is withheld. This is strictly an educational platform. Other than that, anyone has a right to film as long as these guidelines are adhered to and the setting allows for it. Only does it become a problem when careless people start to invade others personal space.

    • @Aaronproductions
      @Aaronproductions 6 років тому +2

      SAFETECH there was a youtuber called “MRTRUEALERT” who had lost his Simplex panels and devices because he released them too early to the public. That’s why he doesn’t upload anymore. And I wasn’t expecting a paragraph about basic laws, I was just asking if your employer is ok with you filming at their costumers buildings. You went in the elevator room which isn’t “assessable to the public” nor eare any of the panels you show so I’m not sure what you were trying to say with that. Sorry I just wrote a big argument essay. Lol I like your videos so keep it up!

    • @safetech
      @safetech  6 років тому +4

      Aaron Productions.
      You are correct in what you are saying. And no I don’t usually need permission to film because I am not leaking private or personal info. That’s where this whole issue begins.Therefore I feel it isn’t warranted. Like I said before, my vids are for educational purposes. If a privacy concern arises the content will be modified or deleted altogether as I have accidentally ran into that a few times myself in the past.

    • @bellum128
      @bellum128 6 років тому +1

      Aaron Productions
      +Aaron Productions What is your source for this? I was trying to find more information on where MrTrueAlert went, but couldn't.

    • @Aaronproductions
      @Aaronproductions 6 років тому +1

      bellum128 he uploaded it to the fire panel forms I believe, but it may have been removed

  • @nickday1984
    @nickday1984 6 років тому +1

    Yes

  • @casualgamer24
    @casualgamer24 6 років тому +2

    why don't u ever talk in your videos? just wondering
    not to be mean but I just want to hear what u sound like

    • @Bill-bj9fn
      @Bill-bj9fn 6 років тому +2

      Evan The gamer Some small youtuber I think SER safety does an interview on this guy

    • @Corvette1658
      @Corvette1658 4 роки тому +1

      And he does talk when he tests voice evc system. Like making the announcements telling everyone that we will be testing the fire alarm system.

  • @OSMDRG91TA
    @OSMDRG91TA 6 років тому +2

    Dover Buzz.

  • @relevanteaglealarms109
    @relevanteaglealarms109 4 роки тому +1

    Otis series 5

  • @shanihowell2327
    @shanihowell2327 4 роки тому +1

    It looks like a otis gen2 and series 5

  • @twentyfour44
    @twentyfour44 6 років тому +3

    Shouldn't it be recalled to the lobby

    • @gnutelliums
      @gnutelliums 6 років тому +4

      If the smoke detector on the second floor tripped, then yes. But since the detector in the lobby tripped, it won't recall to the same floor that the alarm is on. A fire on the second floor would've triggered primary recall, but the ground floor is the alternate recall.

    • @212Elevators
      @212Elevators 3 роки тому +2

      @@gnutelliums What about the detector in the shaft?

    • @IanGSully
      @IanGSully Рік тому +1

      @@212Elevators It will do the same thing if the smoke detector in the machine room goes into alarm. It will cause the “Firefighter hat” indicator that is in the elevator to flash.

    • @212Elevators
      @212Elevators Рік тому +1

      @@IanGSully Hence why it says to exit the elevator when that happens?