Williamson Gas Boiler Turning Off Before High Temperature Set Point

Поділитися
Вставка
  • Опубліковано 9 січ 2022
  • Fairly new Williamson by Weil McLain GWA-75 gas boiler that is turning off well before the aquastat high temperature set point. Another contactor condemned the temperature/LWCO probe - and we installed it at the clients request. Then we tested. Watch and educate yourself - as page 50 is missing from the manual!
  • Навчання та стиль

КОМЕНТАРІ • 47

  • @deancook558
    @deancook558 2 роки тому

    Great video.Thanks.

  • @decsurvey
    @decsurvey 2 роки тому +1

    What makes a great YT channel is first and foremost the personality on camera and then content. Mikey definitely has the personality. If a elderly person or elderly veteran needed a steep discount but wants no one but MP, would you do it say for cost of parts and let labor be written off?

  • @jkbrown5496
    @jkbrown5496 2 роки тому +2

    Found a Heating Help discussion when I searched for the controller part number. Seems this is common that after a couple years the boards cut out at 140 F. And they only last a couple years when replaced. One commenter mentioned he thought it was in the temp control knob as he was able to get it to go to 180 but after it cut out on high limit it still didn't cycle properly.

  • @jkbrown5496
    @jkbrown5496 2 роки тому +1

    Found a manual online, with the wires identified on page 32, lower right corner. But they still don't identify orange. White common, reds thermistor 1 and 2.
    You could get a resistor decade box or just a few resistors so you can hook up the resistance for whatever temperature across the plug and see how the control board acts. or a variable resistor and then check the resistance with your meter.

  • @norbertmartelwautosporteng4098
    @norbertmartelwautosporteng4098 2 роки тому +1

    Let’s go Bosch

  • @greekmaster1001
    @greekmaster1001 2 роки тому +1

    Not sure if you checked but between every single video you posted so far you have more than 6.2 million views

    • @greekmaster1001
      @greekmaster1001 2 роки тому

      @@PipeDoctor if you look into your UA-cam account you will see it

  • @eddiew.6485
    @eddiew.6485 2 роки тому

    Mikey Pipes……..doing Gods work during this🥶 Cold spell. I’m sure your customers are appreciative of your work!👍

  • @realestateservicessaleshea99
    @realestateservicessaleshea99 2 роки тому

    The manual never lies.
    Thanks again for the videos!
    🥃🥃🍺🍺🍺🎯🏌🏻‍♀️
    Stay safe.
    Retired (werk'n)keyboard super tech. Wear your safety glasses!

  • @pookguy
    @pookguy 2 роки тому

    Hey looks like you do great work. Anyone you recommend to service NNJ

  • @Jimbobo162
    @Jimbobo162 2 роки тому +2

    Mikey you have exactly the same number of subs as the grumpy plumber. 28.6

  • @mercurymadness9005
    @mercurymadness9005 8 місяців тому +1

    Tell the customer to change his battery and his smoke detector lol

    • @PipeDoctor
      @PipeDoctor  8 місяців тому

      They all are the same

  • @redneckbryon
    @redneckbryon 2 роки тому

    Do you guys work on more Boilers or Forced Air Heating and Cooling Systems??
    I know hot water is very efficient, but isn't Forced Are more economical since you can do Heating and Cooling with just one system.

  • @Trainman0401
    @Trainman0401 2 роки тому +2

    What am I missing? Did you finally get the part? Did you change it? Did it solve the problem?

  • @Danimal.69
    @Danimal.69 2 роки тому +1

    Space heaters / ovens are really stupid to use when there heating issues. I hope the next video will comment about what happen in the Bronx

  • @stephwaylonwells3218
    @stephwaylonwells3218 2 роки тому

    👍

  • @pubchat2913
    @pubchat2913 2 роки тому

    What were you going to do with the paper clip?

  • @atlasfueloilinc.2421
    @atlasfueloilinc.2421 2 роки тому

    To many boards to carry. Good thing I have I heat in my house. Owner needs 2 boards one for next year. Good content

  • @kc0eks
    @kc0eks 2 роки тому +5

    How people just ignore smoke alarm chirps is beyond my abilities

  • @wyattritchie6779
    @wyattritchie6779 2 роки тому

    Lol the sell man of the year 😂 🤣 jk rock on

  • @kkovler1
    @kkovler1 2 роки тому

    why didn't you show us the part where you replaced the probe?

  • @atlasfueloilinc.2421
    @atlasfueloilinc.2421 2 роки тому

    Put Sensor in garage can and install L4006a and end the b.s. use instructions to raise temperature in room by lighting on fire.

  • @Explore531
    @Explore531 2 роки тому

    have you notice they Mikey's Hat matches his Eye color 1:36

  • @buixote
    @buixote 2 роки тому

    Yeah, bumps & long vehicles... I remember the back seat in the bus used to command a premium, if you wanted to *launch*!

  • @v-modsolutions6946
    @v-modsolutions6946 2 роки тому

    I can't believe that the client ran out and bought a well.....I knew that wouldn't fix it....

  • @gomerhondo7249
    @gomerhondo7249 2 роки тому +1

    Change their smoke/co alarm battery = safety issue!

  • @steveblake8766
    @steveblake8766 2 роки тому

    127 Thumbs UP

  • @CoolerQ
    @CoolerQ 2 роки тому +1

    I hope you tested the resistance of the new part with the control board disconnected, otherwise the board could mess with your readings. My money is on the wiring harness.

  • @RjsEpicAdventures
    @RjsEpicAdventures 2 роки тому

    Nutrients balalalalalalalalalalala

  • @judahexodus7958
    @judahexodus7958 2 роки тому +1

    Clean the boiler sensor to the left of the control or just put in a new one

  • @kevinpoore5626
    @kevinpoore5626 2 роки тому +1

    Feed me Mikey feed me now LOL keeping your boots dry

  • @rwarren4757
    @rwarren4757 2 роки тому

    Don't pick on us in Floridar, especially us in south Florida. where we only have to wear winter clothing 1 month out of the year. 🤣🤣😁

  • @jparrish
    @jparrish 2 роки тому +2

    1st Comment

  • @kevinpoore5626
    @kevinpoore5626 2 роки тому +1

    He took a week off during winter but he went to Florida LOL he didn't go to Wyoming

    • @kevinpoore5626
      @kevinpoore5626 2 роки тому +1

      And I haven't watched his vid yet but came out today while he's on vacay

  • @EliBleu
    @EliBleu 10 місяців тому

    It's actually page 32. not 50 .. that drove me nuts

  • @jaxsonhugh9334
    @jaxsonhugh9334 2 роки тому +1

    WTF…………Can’t people clean up a bit before service people come over????

  • @nitebird500
    @nitebird500 2 роки тому

    Those control units are crap. Replaced 3 of them.

    • @nitebird500
      @nitebird500 2 роки тому

      @@PipeDoctor guess the ones I’ve gotten were made on a Friday :(

    • @baratono
      @baratono 2 роки тому

      Those boards usually fail stuck at around 140F max temp. You can usually get it to run up to the setpoint by fiddling with the temp. setting knob or rebooting the control, but the next heating cycle it'll be stuck at 140F again. I've never seen a failed temp. sensor on those.

    • @nitebird500
      @nitebird500 2 роки тому

      @@baratono exactly.. I had a brand new fail within a month or so, and since I wasn’t a ‘professional’ installer, I couldn’t return. I wonder if the one with a digital display is better for the Weil mclains , but you need need that new harness, correct ?