Electrical Master, thank you for the video explanation. What can be used to protect single-phase load if the government electrician by mistake swapped the neutral wire with one of the phase wires? this causes 2 phase wires bringing in the power instead of one phase and one neutral, which means 415 V. I am indian, In Africa, yesterday it happened and I lost my single-phase stabilizer.
nahi dost SPD me earthing ka connection krna bahut jaruri hai, warna SPD lganeka koi fayda nahi hoga, or iske input me phase connection Kiya jata hai, output earthing Kiya jata hai, earth cable ko proper grounded hona chahiye,
Video is good and information shared is very useful What is capacity of that 4 pole MCB? 16A, 20A,25A ?? Above SPD there is 4 pole MCB what is the capacity of that MCB?
Appreciate! dear first of all spd for overall panel board protection not for individual circuit, you can follow the main breaker current rating for overall protection.
Hello, I have one question What is the difference between SPD and GIC MD73BH voltage monitoring relay SM 500? Which is best option out of these two For lift/elevator application Thanks!
@ElectricalMaster4u मुझे 2 pole single phase SPD (Surge Protection Device) खरीदनी है कृपया करके बताएं के SPD को कैसे चेक करें की सही है या खराब अगर उसका इंडिकेटर सही जानकारी नही दे रहा हो? क्या हम मल्टीमीटर से उसे चैक कर सकते हैं?
Hello, I have one question What is the difference between SPD and GIC MD73BH voltage monitoring relay SM 500? Which is best option out of these two For lift/elevator application For voltage fluctuations Thanks!
Kya ye sabke ghar me zaruri hai? Aaj tak to kabhi bijli nahi giri gharme na hi 11K volt ka surge hua, kuch video boht dara rahe hain k ye lagana chaiye sabko. Kya ye zaruri hai sabke liye?? maine PCCB aur Over under volt protection device le liya hai
Bro, apka kahna sahi hai or mai samjh raha hu, aapko pata hai na har din ek nayi technology arahi hai, koi jaruri nahi hai na k jab koi accident ho tabhi ham protection device lagaye, hamesha advance me hi protection device laga kar rakhe, ki haada ka intezar nahi kre khud bhi safe rahe or dusron ka bhi khayal rakhe. waise apka concern sun kr acha lga.. PCCB ye sab over ya under voltage protection hai, SPD surg protection hai dear
nai SPD ki koi zarurat nahi hai, ye sirf youtubers amazon affiliet link ki commission ke liye faltu me advertise kr rhe hain logo ko darane ki. Lekin RCCB aur voltage protection device is very important.@@Electricalmaster4u
ji, isme neutral ka bhi connection Kiya jata hai, aap dekh sakte hai isme L1 L2 L3 + neutral bhi hai, or out put Jo hai use direct ground krdiya gya hai
कोई भी अपने एसपीडी डिवाइस के बारे में बताने वाले वीडियो में यह कभी नहीं बताता कि एक बार डिवाइस में हाई वोल्टेज होने के बाद कार्टिज खराब हो जाती है और उसके बाद करंट अर्थ लाइन में ट्रांसफर हो जाता है या फिर उसके बाद भी करंट घर में चलता रहता है और घर असुरक्षित रहता है। या फिर करंट सप्लाई चलती रहती है या रुक जाती है। हमे बार बार जाकर चेक करना पड़ेगा कहीं डिवाइस खराब तो नही हो गई। MCB से आगे दो जगह कनेक्शन जा रहे है, एक तो घर या ऑफिस में और दूसरा एसपीडी में । एसपीडी तो हाई वोल्टेज के कारण खराब हो जाएगा लेकिन MCB से आगे जो सप्लाई जा रही है उसका क्या? ऐसे बहुत सारे सवाल हैं। सभी को बस वीडियो बनाने से मतलब है, आधी अधूरी इन्फॉर्मेशन देकर जनता को गुमराह करते रहते है।
very good bro... wah kya baat h, aapne sahi analysis kiya bhai. ye Spd se wire bypass hokar ja rhe h unka kya?? mere khyal s ye High voltage k liye nh bna ye aasmani bijli s protection k liye bna hoga, us case m ye aasmani bijli ko zamin m utar dega or saheed ho jayga. baki aap btao bhai aapko kya lagta h
Ma sha Allah good information
Keep working
Thank you, I will
Well explained 🙏🏻👍🏻
Glad you liked it
Thanks for making video about the SPD 😊👍
U r wlcm
@@Electricalmaster4u yyy u Tb bhi 7 un lp
@@Electricalmaster4u yyy u Tb bhi 7 un lp
How many amps is the circuit breaker used to protect SPD? How many kA is the IC value?
Iss device ko submergible pump voltage manage karne ke laga sakta hu kya
yes, ap sum pump k panel me ise install kr sakte h
Electrical Master, thank you for the video explanation. What can be used to protect single-phase load if the government electrician by mistake swapped the neutral wire with one of the phase wires? this causes 2 phase wires bringing in the power instead of one phase and one neutral, which means 415 V. I am indian, In Africa, yesterday it happened and I lost my single-phase stabilizer.
3 phase ki spd ko ham kya 2 phase me us kar sakte hai . Agar nutral na ho to bh kya ye kaam karega
Kya ye bina earthing ke bhi kam karta hei aur 2 phase power me bhi protection dega
nahi dost SPD me earthing ka connection krna bahut jaruri hai, warna SPD lganeka koi fayda nahi hoga, or iske input me phase connection Kiya jata hai, output earthing Kiya jata hai, earth cable ko proper grounded hona chahiye,
Question :- Neutal disconnect hone kae baad SPD kya karta hai ?
nahi
Telangana ke Hyderabad city me koi well qualified
ITI kiya huwa experience electrician
Agar pata ho to jankari share kare
Nice video and thank
So nice of you
Without earthing spd laga sakte hai
Laga sakte hai, lekin wo kaam nahi karega jo SPD ka working principle hai, waise earthing connection jaruri hai
@@Electricalmaster4u thanks you
Dear without earthing are spd not working ...
Video is good and information shared is very useful
What is capacity of that 4 pole MCB? 16A, 20A,25A ??
Above SPD there is 4 pole MCB what is the capacity of that MCB?
Appreciate!
dear first of all spd for overall panel board protection not for individual circuit, you can follow the main breaker current rating for overall protection.
Hello,
I have one question
What is the difference between SPD and GIC MD73BH voltage monitoring relay SM 500?
Which is best option out of these two
For lift/elevator application
Thanks!
@@Electricalmaster4u .
Telangana ke Hyderabad city me koi well qualified
ITI kiya huwa experience electrician
Agar pata ho to jankari share kare
Good
Sir which single phase spd is better.... 275v uc or 330uc
Hir sir. Among spd1 2 and 3, which one is best for solar system
dear, it's depends on your inverter output voltage rating,
@ElectricalMaster4u मुझे 2 pole single phase SPD (Surge Protection Device) खरीदनी है कृपया करके बताएं के SPD को कैसे चेक करें की सही है या खराब अगर उसका इंडिकेटर सही जानकारी नही दे रहा हो? क्या हम मल्टीमीटर से उसे चैक कर सकते हैं?
Hello,
I have one question
What is the difference between SPD and GIC MD73BH voltage monitoring relay SM 500?
Which is best option out of these two
For lift/elevator application
For voltage fluctuations
Thanks!
SPD ke sat isolater conection karna jaruri he kya ??
yess dear!
Home me konsa aur kitne retig ka SPD lgaye
agar aap voltage rating ke bare me puch rhe hai to, single phase me 220-240 volt hota or three phase me 440 volt rating ka hota hai
Spd ko jalne se bachne ke liye kya kare
why uc 440vac we can install in single phase but uc is more
SPD mein earth connection separate Rahega ya common
common
but lightning arrester keliye separate karna chahiye
SPD ka rate kitna hai 40 MPA ka single pol
Kya ye sabke ghar me zaruri hai? Aaj tak to kabhi bijli nahi giri gharme na hi 11K volt ka surge hua, kuch video boht dara rahe hain k ye lagana chaiye sabko. Kya ye zaruri hai sabke liye?? maine PCCB aur Over under volt protection device le liya hai
Bro, apka kahna sahi hai or mai samjh raha hu, aapko pata hai na har din ek nayi technology arahi hai, koi jaruri nahi hai na k jab koi accident ho tabhi ham protection device lagaye, hamesha advance me hi protection device laga kar rakhe, ki haada ka intezar nahi kre khud bhi safe rahe or dusron ka bhi khayal rakhe. waise apka concern sun kr acha lga.. PCCB ye sab over ya under voltage protection hai, SPD surg protection hai dear
nai SPD ki koi zarurat nahi hai, ye sirf youtubers amazon affiliet link ki commission ke liye faltu me advertise kr rhe hain logo ko darane ki. Lekin RCCB aur voltage protection device is very important.@@Electricalmaster4u
Isme neutral diya jata hai ya sirf RYB diya hai
ji, isme neutral ka bhi connection Kiya jata hai, aap dekh sakte hai isme L1 L2 L3 + neutral bhi hai, or out put Jo hai use direct ground krdiya gya hai
What is the difference between spd and over voltage under voltage device rely?
एसपीडी लगाते समय कैलकुलेशन कैसे करें कहां कौन सी लगानी है
please share full board of SPD Panel
We size should be for three phase and nutral
Selectivity module switch about please
SPD kaishe jala sakate hai
कोई भी अपने एसपीडी डिवाइस के बारे में बताने वाले वीडियो में यह कभी नहीं बताता कि एक बार डिवाइस में हाई वोल्टेज होने के बाद कार्टिज खराब हो जाती है और उसके बाद करंट अर्थ लाइन में ट्रांसफर हो जाता है या फिर उसके बाद भी करंट घर में चलता रहता है और घर असुरक्षित रहता है। या फिर करंट सप्लाई चलती रहती है या रुक जाती है। हमे बार बार जाकर चेक करना पड़ेगा कहीं डिवाइस खराब तो नही हो गई। MCB से आगे दो जगह कनेक्शन जा रहे है, एक तो घर या ऑफिस में और दूसरा एसपीडी में । एसपीडी तो हाई वोल्टेज के कारण खराब हो जाएगा लेकिन MCB से आगे जो सप्लाई जा रही है उसका क्या? ऐसे बहुत सारे सवाल हैं। सभी को बस वीडियो बनाने से मतलब है, आधी अधूरी इन्फॉर्मेशन देकर जनता को गुमराह करते रहते है।
very good bro... wah kya baat h, aapne sahi analysis kiya bhai. ye Spd se wire bypass hokar ja rhe h unka kya?? mere khyal s ye High voltage k liye nh bna ye aasmani bijli s protection k liye bna hoga, us case m ye aasmani bijli ko zamin m utar dega or saheed ho jayga. baki aap btao bhai aapko kya lagta h
Over voltage aega to kya hamari vfd ko bhi ziyaada voltages milengy ya phr vfd ko normal hi milengy ?
ye SPD hai isse lightings arrestor ke through thunderstorm ke fluctuations ko ground krta hai.
Spd vs overvolatage relay
Price kaya hai
its install .5 meter from main incomer not so far
no issue, u can install
Wrong inform...
Konsa standard h power sytem colour code ka ...?
My ans...
3phase k liy
Red yellow blue and neutral k liy black use krte h
aap ek baat kai baar repeat karte hain
Spd
> 300, 000, 000 volts and > 30, 000 amps
1 Phese ka spd milta he
ji, milta hai, single phase 2 pole ka lena hoga
Some where if we haven't earthing
Meens If earthing is not done in any location then what is the function of SPD in such a location😂😂😂😂