Solar SPD Secret | Surge Protection Devices
Вставка
- Опубліковано 5 чер 2020
- #SolarSPD #SPD #SURGE
For Questions/Technical support connect with me.
Subscribe:bit.ly/2XoCPH8
Linkdln:bit.ly/3xG9tQX
Instagram:bit.ly/3jLSV5e
Facebook:cutt.ly/JQDl7Ba
Quora:bit.ly/3iFvM4X
Telegram Solar Group:bit.ly/3iFC2d9
Twitter:bit.ly/3iEYdQw
IMPORTANT Solar Videos
SOLAR DC cable MEGGER TEST - • SOLAR DC cable Insulat...
Solar DC Cable management - • Solar DC cable Managem...
1500VDC Solar Plant - • 3MW Solar Central Inve...
Solar Plant Thermography - • solar plant thermography
Wrong PR%😭 What to do?? - • Solar PR% issue | Sens...
Solar Plant SECRET - • Solar Plant SECRET , ...
Tilt 📐/ Orientation📈 without PvSyst - • Tilt / Orientation wit...
Solar☀️ Plant 🔺 Thermography❗ - • solar plant thermography
Solar 100kw Plant , perfect installation - • 100KW Solar Plant | in...
Solar Plant power Factor🚫- • Solar Plant | Power Fa...
Solar Plant Specific Yield ?? - • Solar Specific Yield ?...
Solar Plant AC/DC earthing ? Why - • Solar Plant Earthing |...
Solar 🌞Net Meter Fault Solution - • Net metering Import v...
Solar 🌞 PID LOSS 📉♻️- • PID loss in SOLAR Pane...
Solar Plant Measurements - • Solar Plant Measuremen...
Solar Plant 🌞Ground Fault - • Solar Plant Ground Fau...
Solar Inverter Derating 🔥- • Solar inverter Deratin...
Solar Plant Overheating Issue🔥- • Solar Plant Over heati...
Solar Eclipse 🌞🌜Genration Analysis - • Solar Eclipse Genratio...
Free Pvsyst software Book ♻️- • Free PvSyst Documents ...
Solar Plant money Payback Calculation 💵- • Solar Plant Money Retu...
Solar🌞 plant LA earthing Calculation in हिंदी में♻️- • Solar Plant LA selecti...
Types of Solar🌞 cell Fault👨🏻🔧 हिंदी में - • Types of Defects in So...
Solar🌞 inverter Selection calculation👨🏻🔧 हिंदी में - • Solar Inverter Selecti...
Solar 👨🏻🔧Parking 🚕Installation 👨🏻🔧 हिंदी में - • Solar Parking | Cost |...
Solar tilt angle & Azimuth experiment🔅- • Video
Middle East Energy expo🔅♻️- • Middle East Energy exp...
How to use PVSYST software🖥️- • Video
Solar AC cable sizing Calculation👨🏻🔧- • Solar AC cable sizing ...
Solar DC CABLE sizing Calculation👨🏻🔧- • Solar DC cable calcula...
Solar DC earthing systems Calculation👨🏻🔧- • Solar DC earthing calc...
Calculate Solar Plant PR%🌞- • Calculate Solar plant ...
SOLAR PV modules comparison🔅- • Calculate How to Selec...
Solar Earth pit resistance Test 👨🏻🔧- • Simple Earth pit resis...
Best Solar panel 🌞cleaning method part 1 - • Best Solar Panel clean...
Best Solar panel 🌞cleaning method part 2 - • Best Solar Panel clean...
Renewable energy India Expo♻️- • REI Renewable energy I...
Solar DC👩🔧 string Fault Rectification method - • Solar DC string curren...
How does solar panels catch fire🔥- • Solar Cell Hotspot, कै...
Solar cell working in Hindi🌞- • Solar Cell Working in ...
Rooftop Solar plant visit🌞- • Understand solar plant...
How to check Solar Delta Inverters👩🔧- • Delta Solar string inv...
Solar Plant thermography test 🔅- • Thermography test of s...
That’s good great work God bless ❤️❤️👍
Tx for detail explanation in simple language with example
Very nice very helpful spd lecture
Thank u so much 😊
Understood very clearly.
Thanks for your support and guidance.
Regards
Thanks for the support
Sir, Your video's are more informative.
Thanks you for this video very informative.
Thanks for the support
Nice explanation Himanshu, may I recommend you to include examples of its failure, disadvantages, cost associated over lifetime of the project (in % vs its monetary advantage), what are usual engineering practice. Keep sharing to our viewers.
Bhaisab aap ne solar ka jankari bahuth acha tarikese UA-cam se logotak jankari dhere apko dhanyawadh
over voltage aaye jab Spd agar red symbol me aayatho inverter ko safe karneke liye Voltage Orthing yaneki Jameen me jatha tab vaha Orthing pipe ke Are me Corrent aaskata huse apneku Denzor hosakta ki.
Very good sir 👍 my ap ky videos dhekta hoo ap bohet achy tariqy say guide karty hy
Thanks for the support
Salam Bhai Ma Sha Allah ur very knowledgeable person Allah ap ko booht booht tariqi de
perfect and very well explained Himanshu
Thanks for the support
Appreciate your information
You are just Love Bro ..
Fantastic Brother &Thank you for Explaining 👌👍
Thanks for the support
@@SustainableEveryDay Why Uc is 385Volt ? It means after 385 volt SPD will earth the extra voltage , right ? So in three phase we have 400 volt (approx) . Please clarify it ?
Very Good. Thanks
Great Teacher, Salute, God bless You
भाई साहब
एक वीडियो अर्थिंग पे बनाइए की हमे सिंगल फेस dcdb में कितने earthing करवानी चाहिए
लाइटिंग अरेस्ट को भी काउंट करते हुए ❤❤
एक।सिंपल वीडियो 5 kw के सिस्टम के लिए ऑफ ग्रिड सिस्टम के लिए ❤❤❤
Very nice information. Please post installation of SPD and diagram of SPD installation.
Excellent informations with technical approach.
Thanks for the support
great instructor.
Very nice explaination himanshu bhai.
Thanks Pranjal bhai
thanks sir ji
Thanks sirji
Very good job thanks 👍👍👍👍👍✌️✌️✌️✌️✌️🙏❤️
Thank you too
Really Appreciating Knowledge
Thanks for the support
Why Uc is 385Volt ? It means after 385 volt SPD will earth the extra voltage , right ? So in three phase we have 400 volt (approx) . Please clarify it ?
Thanku sir ur all video is very usefull sir
Hi sir, ACDB aur DCDB me fix karne waale SPD kawn se Type ke hone chahiye? Type2 SPD for both?
What is difference between SPD n under voltage device?
Recently my lights burst n fans burnt due to over voltage n phase failure on my nearest transformer. I have bus bar installed with ACearthing but still my lights burnt . Now please guide me what should i install for my system protection SPD or under voltage device in my main DP Box .
PLEASE REPLY - is it possible that even if proper AC SPD’s are installed THEN too the inverters fail because of high voltage discharge ( high voltage discharge from discom grid to ground right before the transformer input) ? Many other electronic equipment’s got burnt but no harm to inductive motors, AC SPD’s blasted on one of the site.
Pls explain us.
How can we calculate the size of SPD for AC/DC .
Sir, I need to know that to install an SPD on my solar input line to my inverter, where do I connect the earthing of SPD ? On DC side, AC side or to a separate earthing ?
Thanks for info , can you please make video on AC/DC cable works from module to inverter and inverter to grid plz
Definitely
Excellent job 👏
Why Uc is 385Volt ? It means after 385 volt SPD will earth the extra voltage , right ? So in three phase we have 400 volt (approx) . Please clarify it ?
Great explanation!
Bahut sundar jankari sir jee
Thanks for the support
Nice video.
Once SPD activated, Inverter will run continuously or it will stop??????
Sir ye googles ka bhi solar m use h kya??
Thanks sir 👍👍👍👍👍👍
Thanks for the support Suraj
Well Done
Very informatic thanks
Thanks for the support
Thanks sir.. Please make a video on PR CUF calculation
Sure
Sir my home elcb (robot)trip when rain start. After off ac and dc mcb near solar inverter everything fine. What causes and what i am to do. Pls suggest 🙏
Multiple issues , Elcb trip trip to prevent earth fault , any AC cable is coming in contact with conductor during rain
Sir is SPD IS MANDATORY IN offgrid system of 2 kva?
Great explained
Very nice explained
Thanks for the support
Thanks for the nice explanation!!
Can you please let me know the name of the paint app you have used.
Sir how to select the rating of SPD for ACBD. I have an ABB inverter of 12.5 KW.
Sir, in one of my site ac spd os getting blown at B phase only i have replaced it twice but still issue isn't resolved . Kindly explain the issue and provide the solution
Bhai agar indication half me hi red ho gaya ho aur remains half me green rah gaya ho to ye spd kam karega transient condition me ??
New grid tie inverters already have internally integrated type ii spds on both dc and ac side, do we need to install extra externally as well.
Because in case of surge it may void the warranty of inverter
V good sarad
Thanks for the support
Outstanding
Is it necessary to have earthing when you have SPD?
Hi, can you please define what is different between external SPD and internal inverter SPD. Thanks
Hi, what shoud be MOV rating on Inverter?
👍 👍
Please share SPD selection excel calculator just like you did it for wires
Kindly let me know connection of 3 phase SPD.
ALSO PLEASE LET ME KNOW RATING OF HRC FUSE IF USING 65 KA or 70 KA SPD.
Short & Simple explanation 🙏🙏
1)Kindly Share manufacturing details of PV modules 2)Explain Name plate Details of Pv modules
Please text your inquiry on my LinkedIn
sir agar kisi jagha earthing na ho to kia wesy hi spd use karny pe breaker trip hoga spd blast hony pe.
👍👍👍👍👍
Thanks for sharing valuable content 👍🏻
Thanks for the support
Sir kya ham 4 pole ki spd ko 2 phase ya phir single phase me use kar sakte hai. kya ham Bina nutral ke 4 pole spd ko use kar sakte hai ya phir spd me nutral ka connection jaruri hota hai
Aapka vidio informative hai. Thanks for guide us.......
In some cases we found that installer uses varistor instead of spd, Kindly also explain which one is good , how we can find what value of varistor is suitable for site and right way to install it..
SPD is also a varistor , The rating is decided as per Overvoltage range for system protection
Thanks for explaining:
I have one earthing connected with lightning arrester. Can i give same earthing to dc and ac SPD’s ?
My panels are placed at 4th floor roof the height approximately 40feet from ground.
I have 12 panels of 5kw.
Plz suggest 2nd earthing compulsory or i can use same earthing for spd’s and inverter.
Use the same no issues
@@SustainableEveryDay Thank you very much for the reply. Can you share any video in which we can test the SPD's or earthing without earthing meter.
Now days string inverter have high ac volt 800 volt , which , is there any ac spd for 650 to 800 ac volt
can we install both the SPD and voltage protection device in the same system? or how to decide that I need an SPD or voltage protection device for my system (if only one can be used for a system at a time). Thanks.
Yes you can do it for higher level of protection
Keep it up Sir..
You are doing great... 👌
i like your video. english translation please
Hi, please guide should I connect AC SPD single phase at the imput of MCB or at the output. Waiting for your reply, Regards, Satyendra
Correct at Input of MCB yes
good
I think you have not included spd specification which protect over surges meanwhile maximum continuous voltage, nominal voltage & max. rated capacity kA. How to connect mov with included RC & LC filter.
In SPD neutral and earth internally connected?? Does solar need separate Earth for both ground and to SPD???
Thank you for this information sir,
Thanks for the support prasad
Hello sir,
Agar voltage suddenly down ho jaaye, tab kya karna chahiye??
Kitne kilowatt system per ki konsi rating ki SPD lagaye
Can we use Over/Under Voltage protector as an alternate to SPD?
Sir
Aapne yah chasma konsa laga rakha hai...
Yah kya kaam aata hai..
Kya yah eye ke liye safety ka kaam karta hai
Dc SPD 24v 375w ke aspas milta hain kia? Dc SPD kitne volt or amps ki milta hai? Please reply sir
meray pas 2 invertor 5.2KW k parallel kit se linked hein ..
so my question is
1 SPD lagaun ya dono k liyay separate 2 SPD lagaun
Thanks for sharing knowledge 🙏🙏🙏🙏
how inverter will behave incase of there is no SPD ? it doesn't have any builtin protection towards high voltage ?
and one more question:
if we install Volt - Ampere Protector of 40 Ampere , will it give protection in case of there is no SPD ?
Without SPD during surge the IGBT of inverter will blow
Good
...
Thanks for the support
Sir solar Outside ( out put) AC armoured cable ke size ka kase pata kre ki kitne Sq mm lagani h
Bhai pehle to Calculation part hai uska , I have uploaded a video on it , or else armoured cable pe likha hota hai
sir samaj gaye ki is se hum home ups ko asmani bijli ke dammage se bacha saktein hain aksar solar solar panel se aane wali bijli ki current teez hoti hain woh palak japak ne jaise sahi hain sir
Correct
Mere 1 system me bhi AC SPD short ho gyi, and baad me bhi client k LT panel me short circuit hua to mera Inverter bhi faulty ho gya.
Yadi customer time se inform kar deta to inverter bach jata.
Correct
How SPD is selecting,depend on voltage or current?
Dear aik solar system k lie kon konci earthing zaroori ha?
sir MAKE A VIDEO ON MAKEING OF ACDB, DCDB FOR 1KW , 2KW , 5KW 10KW 15 KW ROOF TOP SOLAR FULL DEATAIL
Sir Hamada inverter 5kw panel 4kw inverter pv voltage 450 which type 2 spd which range need pls tell me
bhai agar radiation up and down yani jaise cloudy hota hai to PR ghatne ya badhne kyo lagta hai. Kabhi ghata hone par badh jata hai aur dhoop nikalne par ghat jata hai aur fir kabhi kabhi iska ulta ho jata hai yani ghata hone par ghatne lagta hai
Bhai PR k formula mai radiation ki value division mai hoti hai , iska matlab radiation increase hoga toh PR decrease hoga , Lekin agar genration increase hogi sath mai toh PR constant bana rahe ga , agar aap k PR ki value affect ho rahe hai toh aap k plant under perform kar raha hai
5 KVA ka off grid Solar setep me acdb and dcdb box must Hai.
Ac spd ki jagah dc spd laga sakte he kya
Bhai mrri spd 2 month main 3 times expire hoi hai transformer. Burning hoti spd expire hojati hai what can I save my spd
is spd connected in series or parallel with inverter sir
Parallel
@@SustainableEveryDay
Thanks sir
I have installed Huawei sun2000 100kt inveter. So the question is that can we use DC SPD on each string ?
Sun2000 series don't require additional DC SPD protection
Sir L&T aur ABB aur Schnider me se konsa sabse best dcdb aur acdb hai sir please bataye sir
All are good , but ABB after sales service is better
What is the difference between SPD and MCB in our regular house for general knowledge of a common man
SPD is a switch , you can turn it ON & OFF , while SPD is a protection devices which will operate on its own you don't have to touch it
What should be the thickness of the wire for the earthing connection from SPD.