Hi brother video very helpfull Ek help aur chiye agar hum motorised valve ko direct 24v ac se chalana chahein toh kya karein..matlab DC input bypaas karna hai.. Yani jab ahu chale toh valve auto khul jaye aur jab ahu band ho toh valve band ho jaye..kya hum ye system iss same valve me kar sakte hai..
Problem -1 : Valve 50 ya 60% hi open ho Raha hoga because kuch kachda fas ho gaya hoga jisse k wo stuck kar rha hoga. Problem -2 : 10 v ki command BMS de rahe ho, lekin field pe check Karo ke kitne volt ki command AA rhi hai , ho sakta hai k wo 5-6 v ki command AA rhi hogi is liye wo utna hi feed back de rha hai Problem -3: command 10 v ki AA rhi hogi or wo 100 % open v ho rha hoga, but actuator kharab hone ki wajah se wo feedback nahi de rha hai. Problem -4 : feedback K liye extra resistance lagana hoga jo ke laga nahi hoga
@@HVACWorld valve par 10 v pura aa raha hai lekin feedback back kam 5,6 volt dikha raha hai manual open karne par 100% open ho raha hai ab valve control me problem hai ya nhe ye kaise check kare
Flowcone k chhote Wale actuator manual operate nahi hote h....agar aapko valve ko operate krnanh to actuator kholna padega valve k upar se..... Flowcone k bade wale actuator manually operate hote h... actuator k upar ek button hota h jisko daba kr spindle ghumane se valve open hota h
Sir I need your help...plz 🙏 Actually there is a FCU in which oventrop actuator is installed and it continuously move up and down (open/close )....i can share that functioning video if you can give me your contact no. Plz sir 🙏
v well explained
Excellent
Hi brother video very helpfull
Ek help aur chiye agar hum motorised valve ko direct 24v ac se chalana chahein toh kya karein..matlab DC input bypaas karna hai..
Yani jab ahu chale toh valve auto khul jaye aur jab ahu band ho toh valve band ho jaye..kya hum ye system iss same valve me kar sakte hai..
Nice video. Thanks sir.
Sir aap explain kiya one doubt hai t2798i2000 thermostate kaise actuletor me connection krega
Very.NICE
Thank you very effective videos
Good knowledge. Green wire without chalega ?
Ees modulating actuator device par ek video bamni chahiye..
Very good knolege sir
Thanks
Sir without DDC panel ke 10v DC supply kahi or say de skte hain kyaa acutor motor ko
Thermostat laga kr
@@HVACWorld bhai kyaa aisa bhi thermostat milta hai jisse 10v dc out hota ho?
ua-cam.com/video/xHkGxpnBYTc/v-deo.html
@@shaikjuned712 hua aapka kaam fir??
Mujhe bhi same system karna tha.
Plz make videos on chiller control wiring diagram I will waiting your videos
You mean BMS control
No bro he means chiller control panel wiring.
Hi sir . Brwon dc 24 +
Yellow comn ‐
Grey 10 volt .
Yellow and green dead kiya hai to chalega . Kya
Please reply
Chalega. Feed back nahi milega
Kitna percent open hai wo nahi pata chalega
Oventrop k chote Wale actuator bhi ni hote hn manually operate?
Actuator auto me wirk nhi kar rha hai,kya cause ho sakte hai
Honeywell DN40mm actuator open close nahi Hota Hai but pic ho raha Hai shutout kase karte hain
Actuator ka dp setting kaisa Hota hi sir
Bro agar input volt 10v aa raha hai lekin feedback volt 5or 6 volt dikha raha hai to kya problem ho sakti hai
Problem -1 : Valve 50 ya 60% hi open ho Raha hoga because kuch kachda fas ho gaya hoga jisse k wo stuck kar rha hoga.
Problem -2 : 10 v ki command BMS de rahe ho, lekin field pe check Karo ke kitne volt ki command AA rhi hai , ho sakta hai k wo 5-6 v ki command AA rhi hogi is liye wo utna hi feed back de rha hai
Problem -3: command 10 v ki AA rhi hogi or wo 100 % open v ho rha hoga, but actuator kharab hone ki wajah se wo feedback nahi de rha hai.
Problem -4 : feedback K liye extra resistance lagana hoga jo ke laga nahi hoga
@@HVACWorld valve par 10 v pura aa raha hai lekin feedback back kam 5,6 volt dikha raha hai manual open karne par 100% open ho raha hai ab valve control me problem hai ya nhe ye kaise check kare
Kis make and model ka PICV & Actuators hai??
@@HVACWorld siemens skd60 acutaor ahu me laga hai
Output singnal mAh mai bhi hota hai aysa kyou?
Advantage kya hai dc & mAh mai?
Mili amps me hota hai
Hope video me sab clear ho gya hoga aapko
Plz share kijiye video...or dosto ko v subscribe karne k liye boliye...
Kaise pata kare actuator kharab hai ya valve kharab hai
Sir, agar ac se fluctuation hota hai tab 24 v ac kyu diya jata hai closing ke
Red lite or green lite Kya hai
Actuator ko manual kese operate kre ...?
?
Flowcone k chhote Wale actuator manual operate nahi hote h....agar aapko valve ko operate krnanh to actuator kholna padega valve k upar se..... Flowcone k bade wale actuator manually operate hote h... actuator k upar ek button hota h jisko daba kr spindle ghumane se valve open hota h
Sir I need your help...plz 🙏
Actually there is a FCU in which oventrop actuator is installed and it continuously move up and down (open/close )....i can share that functioning video if you can give me your contact no. Plz sir 🙏
Sir please 🙏 bataey
Iski setting kaise kre