Plumbing Base Inspection

Поділитися
Вставка
  • Опубліковано 7 лют 2025
  • Here's a crash course on plumbing base inspections in the Pikes Peak region. In this video we go over what our inspectors are looking for and the common mistakes they run into out in the field.

КОМЕНТАРІ • 112

  • @je-niseghana7377
    @je-niseghana7377 11 місяців тому +2

    This is by far one of the best plumbing inspection videos i have everwatched. thanks for making this

    • @PPRBD
      @PPRBD  11 місяців тому +2

      Thank you for the feedback. We hope the video was helpful.

    • @je-niseghana7377
      @je-niseghana7377 11 місяців тому

      @@PPRBD very helpful

    • @billbell5495
      @billbell5495 5 місяців тому

      Great job, I'm a old LA City plumbing inspector for the city of L.A. Great

  • @johnpeters9903
    @johnpeters9903 Рік тому +3

    Nice video, very Informative for the audience. I am retired after 49 years in the trade and never had an inspection that complete. The homeowner is definitely getting their money's worth.

    • @PPRBD
      @PPRBD  Рік тому

      Thanks for the feedback John. Enjoy that retirement.

  • @medmuscle
    @medmuscle 3 роки тому +11

    Awesome video. It was very informative. I really appreciate people taking the time to put informative videos on UA-cam to help other people learn.
    I'm the only code enforcement officer in a small town. While we do have a couple of building inspectors and a building official in our department, the city is encouraging me to get into building code to help out. I decided to start with plumbing.
    I loved your presentation in this video. It was easy to understand. Excellent work!

  • @rustycarpenter1219
    @rustycarpenter1219 Рік тому +4

    Nice one, around here we do 10' of water head for testing pressure

    • @farrlaterry1365
      @farrlaterry1365 7 місяців тому

      Is that an UPC requirement?
      Are they allowed to use air tests for plastic pipe or I'm seeing something else?

    • @keystoneplumber
      @keystoneplumber 9 днів тому

      That is 4 ½ psi almost

  • @mark_Hershey
    @mark_Hershey 2 роки тому +12

    Wow, ky plumbing contractor here. I am amazed at the lack of vents some states have. We are required to vent EVERY fixture. Zero wet venting allowed. Just thinking how easy it is to plumb there.

    • @ImYourHucklebery117
      @ImYourHucklebery117 2 роки тому +3

      Yep, the way he had the combo close with the ptrap with no vent in-between was kind of worrying

    • @winterfar2814
      @winterfar2814 Рік тому +2

      Wet venting and combination waste and vent is used all the time and works. A lot of people just don’t understand how to design it properly so they just add vents everywhere wasting time and money.

  • @TeslaBoy123
    @TeslaBoy123 3 роки тому +2

    In state of Illinois all underground plumbing drains pipe size 4" minimum vents 2" are allowed

  • @dialac1
    @dialac1 Рік тому +1

    Thanks so much for this video. Answered my questions about venting

    • @PPRBD
      @PPRBD  Рік тому

      Excellent. We're glad it was helpful.

  • @quickthailesson1113
    @quickthailesson1113 3 роки тому +25

    Music does not add to video. It only makes it harder to hear the voice.

    • @maestrovso
      @maestrovso 3 роки тому +2

      It is so ingrained that people think they have to add some cheesy soundtrack on any video, even with professional productions. For me silence is golden, and bad sound is noise. If they pay for a "audio designer" he just want to hijack the video thinking people are here to listen to his poor taste in music. And he likes to constantly mess with the sound mixing board as he is strung up with coke.

  • @bp4170
    @bp4170 3 роки тому +6

    Thank you for a clear explanation.

    • @PPRBD
      @PPRBD  3 роки тому +3

      Hey Brian, thanks for the feedback. We hope the video was helpful

  • @lorenzohernandez4540
    @lorenzohernandez4540 Рік тому +1

    Thank you so much 😊

  • @rbspider
    @rbspider 2 роки тому +2

    I think they should have checked that the pipes were vertically plumb too . I bought a condo where the toilet flange was not even close to being plumb . Try putting in a tile floor and toilet , what a nightmare and you could clearly see that the lab at this site was way out , wonder how the other two pipes were?

    • @rustycarpenter1219
      @rustycarpenter1219 Рік тому

      They often aren't, usually end up tilted at 90 to the dvw stack which is on 1/8 bubble or 1/4 bubble

  • @ImYourHucklebery117
    @ImYourHucklebery117 2 роки тому

    1:45 you also want to check the schedule of the pipe, schedule 40 is better underground, you can see behing the orange glove the pipe marking in blue "Coex Cellular" this pipe is usually used aboveground

    • @PPRBD
      @PPRBD  2 роки тому +1

      Hello Mr. Slayer. The code allows Coex cellular piping to be installed above or below ground. Hope this helps.

    • @tannerwest6823
      @tannerwest6823 2 роки тому

      Here in NC we use the hell out of some foam core underground. Works just fine

  • @Skateforlifelad
    @Skateforlifelad 11 місяців тому

    First inspector I've ever seen place a level on any pipe.

  • @TimBruce1
    @TimBruce1 4 роки тому +1

    Great video. Very good presentation and descriptions.

    • @PPRBD
      @PPRBD  4 роки тому

      Thanks Tim. We hope it was helpful.

  • @mswvette
    @mswvette Рік тому +1

    What are the circle things on the pipes for the floor drains called?

    • @PPRBD
      @PPRBD  Рік тому

      If we're talking about the same circle thing, I believe those are called Quad drains. Hope that helps.

  • @tomdavis3495
    @tomdavis3495 2 роки тому +5

    On the wet venting of the bathroom group, the toilet flushes by the tub and cuts off the wet vent from the lav. Red Tag! The tub should be caught on the 2" wet vent before the toilet. Plumbing 101.

    • @Robertz37
      @Robertz37 2 роки тому

      3” pipe on a wet vent system can carry a total of 12 dfu’s so it is oversized and will accommodate for the venting. Although I can’t picture how the system will be vented from the lav when it has exceeded 8’ with a 1/4 “ fall. I see the vent rising above the horizontal plane of the wet vent system and with the lav going at the same time as the toilet or tub there would not be a vent or it would create siphonage. What are your thoughts?

    • @tomdavis3495
      @tomdavis3495 2 роки тому

      @@Robertz37
      Basically, a toilet can't flush by another fixture without that downstream fixture (the tub in this case) being vented first by the lav wet vent (3:44). So, John the inspector was either taught wrong or he has been breathing that thin air up in Pikes Peak too long. ;))) Actually, I see this situation as acceptable in many western US videos, but here in the southeast that is a no-go situation. The hydraulic gradient situation you are referring to would refer to the fixture arm that is being vented off of the wet vent. In this case, it would only refer to the toilet arm and the tub arm, not the wet vent pipe from the lav.

    • @Robertz37
      @Robertz37 2 роки тому

      @@tomdavis3495 What plumbing code are you under where you’re located?

    • @tomdavis3495
      @tomdavis3495 2 роки тому

      @@Robertz37 Hi Robert We use the Florida Building Code which is based on the International Building Code. Due to our area receiving higher winds (hurricanes) than many places across the country, the Florida Building codes are much stricter in the structural areas due to these wind issues.

    • @Robertz37
      @Robertz37 2 роки тому

      @@tomdavis3495 Right on. Makes sense. Where I am at in Colorado we go by the International plumbing code. It seems more strict then the UPC code but from what you’re saying not as strict as Florida code which makes sense from the information you’ve given me. Thank you for your comments and insights. May you have a safe and prosperous journey in your plumbing career. Thanks for your time.

  • @johne.meyerconstructionser7507
    @johne.meyerconstructionser7507 3 роки тому +3

    you have read the code ref air vs when water available and dont need a 10head anymore but cities can require it. 5' head is minimum.
    they have way too much developed length between those pipes. the potable water had no air on it and was not above the sewer line enough. it was done the way we see all the time but not up to snuff. pvc doesnt have an issue with cement against it-by requiring a foam wrap on anything other then a toilet which isnt needed now either since you are allowed to use a 4x3 90 the flange will glue in and be tapconned down on second phase.you make a weep area for ground water and bugs your inspector did good except for foam and air on sanitary when water is better-code will allow air when water not possible. no air on main potable water main in. and it wasn't stepped above sanitary line. you get a like because he bent over and checked pitch and walked on main to see if it bowed anywhere-well done.

  • @Innovative_Drafting.Design
    @Innovative_Drafting.Design 9 місяців тому +1

    in 2024 is it 1/4" per foot drain for 3" pipe or still 1/8" ?

    • @PPRBD
      @PPRBD  9 місяців тому

      The current 2021 IRC has not changed that requirement. 1/8’’ per foot for 3’’ is still ok

  • @stanalaka821
    @stanalaka821 4 роки тому +1

    Respect for what you do

    • @PPRBD
      @PPRBD  4 роки тому

      Thank you Stanley. Our plumbing team is awesome and they put a lot of hard work in. Our team normally does about 3,400 plumbing inspections each month.

    • @saltypipefitter4618
      @saltypipefitter4618 4 роки тому

      How much does a plumbing inspection cost ? If you fail do you get a time frame to fix it ? Or pass fail then pay again ?

    • @PPRBD
      @PPRBD  4 роки тому

      @@saltypipefitter4618 With the Pikes Peak Regional Building Department the cost of the inspection is factored into the permit. Once a permit is obtained you have 180 days to call in an inspection. If that inspection fails you have another 180 days to make corrections and request another inspection. If the project fails too many times and/or the inspector notes are being ignored, a triple fee could be applied and that must be paid before another inspection can be requested. Hope this helps.

  • @df4480
    @df4480 3 роки тому

    My brother just pass his master on plumbing. Better learn this stuff great video.

  • @backwoods7678
    @backwoods7678 2 роки тому +1

    Since when can the water supply be in same ditch or level as your sewer main ..that has always been a cross contamination issue .. I've worked many states to .. The 10 state's I've been in require. A foot above sewer and a foot beside .. Also some states use vacuum test and not air now .. I see many other questionable things that in m9st states will not pass.. This state would be cake walk .. Just was wandering that's all

  • @AHoney-xl9ux
    @AHoney-xl9ux 2 роки тому

    Nice video but tell us, how much pressure require for testing drain pipes as per plumbing code.
    I think 25 PSI ? Please correct if I am wrong.

  • @CarlosAntonio-im7uw
    @CarlosAntonio-im7uw 3 роки тому +2

    Lot of great information. Thank you. If I make one suggestion for your videos, either turn down the music and make it totally background or lose it. It is too loud in this video and it complete distraction and difficult for The Listener to follow along with the inspector

    • @PPRBD
      @PPRBD  3 роки тому

      Hi Carlos. Glad the video was helpful. Thanks for the feedback on the music.

  • @saraalcala1621
    @saraalcala1621 Рік тому

    Loved it! Thank you.

    • @PPRBD
      @PPRBD  Рік тому

      Thanks for watching. We hope the video was helpful.

  • @phrepster
    @phrepster 4 роки тому +1

    Basement bathtub trap needs 2 pipe sizes of pipe between itself and the next fitting?

    • @PPRBD
      @PPRBD  3 роки тому +2

      Hello Jake, the tub trap needs 2 pipe sizes from the vent. Not necessarily the next fitting. Feel free to contract our Chief Plumbing Inspector Joel if you have any more questions. His email is joel@pprbd.org. Hope this helps.

  • @manueldiazcu
    @manueldiazcu 2 роки тому

    2:20 two floor drains are not vented. Developed length more that 8 feet on two inch is a red tag 100%

    • @PPRBD
      @PPRBD  2 роки тому

      Hi Manuel, thanks for watching the video. Both drains are vented and our inspector explains that at about the 2:26 mark.

  • @marcelaabrach734
    @marcelaabrach734 2 роки тому

    I love this video! For the pressure test, where should we place the test plug? Does it need to be after the drain has exited the building? Thank you!

    • @PPRBD
      @PPRBD  2 роки тому

      The plug or cap can be placed at the end of the pipe outside of the building or a test tee is installed immediately inside the building which will allow the plug to be installed in the test tee.
      Hope this helps.

  • @jorgerobles4820
    @jorgerobles4820 3 роки тому +2

    Have much is slope en 3 inch pipe? Thanks

    • @PPRBD
      @PPRBD  3 роки тому +3

      Hello Jorge, minimum slope for 3” drain pipe is 1/8” slope per 1 ft. Hope this helps.

  • @jamiboothe
    @jamiboothe 3 роки тому

    This was very very good to see.

    • @PPRBD
      @PPRBD  3 роки тому +1

      Hope it helps Jami. Have a great day.

    • @jamiboothe
      @jamiboothe 3 роки тому

      @@PPRBD It was certainly helpful. I am a first time owner builder, and am currently negotiating the build process.

  • @Nyck461
    @Nyck461 2 роки тому

    What I am wanting to know is how the plumber start and how he takes measurements to dig the trenches and and run all the pipes to the designed locations in a land where nothing is yet built.
    How everything (bath, kitchen, laundry, etc) matches to the precise location after the house is built?

    • @Chuckysdad19
      @Chuckysdad19 Рік тому +1

      The plumber would have to use the architectural drawing and string line to lay out the relevant walls. The drawings should have measurements from the foundation to the walls. The exact location for fixtures is critical to avoid having to chip concrete and move the pipes later.

  • @buck-johnson
    @buck-johnson 3 роки тому

    Great video.

  • @MyFortressConstruction
    @MyFortressConstruction 2 роки тому

    0:34 You could feel his soul getting sucked out as he explained what a failed 5 lbs test would would show, "There wouldn't be 5lbs on the gauge........sigh........."

  • @sodapuffs
    @sodapuffs 4 роки тому

    excellent job

    • @PPRBD
      @PPRBD  4 роки тому

      Thanks Allie. We hope the video was helpful

  • @markbone5028
    @markbone5028 3 роки тому

    Does an air test on PVC void the manufactures warranty? Air test on PVC are dangerous.

    • @TeslaBoy123
      @TeslaBoy123 3 роки тому

      Water leak test or 5 pounds air are allowed

    • @dtm6215
      @dtm6215 2 роки тому

      Been testing with air for decades . Who said it’s dangerous ?

    • @philweiand4564
      @philweiand4564 2 роки тому

      3.5 psi max , you can explode pvc .

  • @keithrichards4513
    @keithrichards4513 4 роки тому +1

    Thanks ,Very informative!

    • @PPRBD
      @PPRBD  4 роки тому +1

      Thanks Keith. We hope it helps

    • @byronluca9041
      @byronluca9041 3 роки тому

      pro tip: you can watch movies at flixzone. Me and my gf have been using them for watching loads of movies recently.

    • @ericjesse3753
      @ericjesse3753 3 роки тому

      @Byron Luca yup, I've been using Flixzone} for years myself :)

  • @andrey162000
    @andrey162000 Рік тому

    That tub will syphon when flushing w.c

  • @vincentchato519
    @vincentchato519 4 роки тому

    Nice job. From a New Mexico JP

    • @PPRBD
      @PPRBD  4 роки тому

      Glad we could help our neighbors to the south. Have a great day.

  • @Karim-lj5er
    @Karim-lj5er 2 роки тому

    Very useful

    • @PPRBD
      @PPRBD  2 роки тому

      Thanks for the feedback. We hope the video helps.

  • @achristianson4059
    @achristianson4059 3 роки тому

    Hey thanks john

  • @sakyiebenezer2941
    @sakyiebenezer2941 2 роки тому

    Please am plumber in Ghana I need work in your place

  • @kevinhornbuckle
    @kevinhornbuckle Рік тому

    The music is distracting and too loud. Otherwise, vital info.

  • @brandong550
    @brandong550 2 роки тому

    The background music is a bit much. Difficult to hear and focus.

  • @heyheyjaytube
    @heyheyjaytube Рік тому

    This guy sounds like me doing pretrip inspection in front of Dot tester

  • @HoosierGroyper
    @HoosierGroyper 2 роки тому

    Music is very irritating. Couldnt focus on what the inspector was saying.

  • @tomverdi8030
    @tomverdi8030 2 роки тому

    Your tub drain isn't vented

    • @PPRBD
      @PPRBD  2 роки тому

      Hi Tom. As John explained in the video the tub is part of the wet vent system for the bathroom group. Hope this helps.

  • @a7med088
    @a7med088 2 роки тому +1

    What is the benefit of the music in the background ???
    🤬😩🤯🤯🤯🤕

    • @vanmonroe4346
      @vanmonroe4346 2 роки тому

      I thought the same thing ---- pointless ---- I want to learn something about plumbing, and cutesy upbeat generic music doesn't help.

  • @sssanitary8557
    @sssanitary8557 3 роки тому

    Can you give me a pipe fitting job?

  • @Saltcracker007
    @Saltcracker007 2 роки тому

    At 3:46 that bathroom group is not properly vented

  • @vivianvasquez6966
    @vivianvasquez6966 2 роки тому

    good video but music I couldn't watch it

  • @zonatimetraveler5019
    @zonatimetraveler5019 3 роки тому +1

    Please, no background music. Or at least something very banal and low. Otherwise, informative!

  • @henrythompsonIII
    @henrythompsonIII 2 роки тому

    Yes, the music is extremely distracting.

  • @martindekker8203
    @martindekker8203 8 місяців тому

    Why the music? get rid of it had to hear him.

  • @landontucker6824
    @landontucker6824 Рік тому

    Wet vent fail

  • @highway2run
    @highway2run 3 роки тому

    Turn the. Music off

  • @pauljohnson8154
    @pauljohnson8154 4 роки тому +1

    Plumbing code requires 3" stack for a washer drain

    • @pauljohnson8154
      @pauljohnson8154 3 роки тому

      @Supa Trending Daily only if the 2" branch runs to a 3" vertical stack. Has been code for a while read the code book.

    • @TeslaBoy123
      @TeslaBoy123 3 роки тому +1

      3" toilet washer 2" vertical drain are approved in many states

  • @MarleneSargeant6846
    @MarleneSargeant6846 Рік тому

    Stop the music please!

  • @umbasa01
    @umbasa01 4 роки тому +1

    Hard to hear over music. Weak hearing.

  • @GreenGrow-ck3pg
    @GreenGrow-ck3pg 7 місяців тому

    I guess I'll make a video explaining everything unlike u

  • @EvgeniiIudin
    @EvgeniiIudin 7 місяців тому +1

    Thank you so much!

    • @PPRBD
      @PPRBD  7 місяців тому

      No problem. We hope the video was helpful.