I have an oddity. Miller M7 furnace. There is a cover that goes over the burner/manifold assembly. When the cover is in place and the t-stat calls for heat, one burner will light and then go out. If I remover the cover and the t-stat calls for heat, all three burners operate correctly and I can then replace the cover and it will continue to operate. I am wondering if I have a partial blockage at the intake on the roof??
😅 I’m editing the video like did I really just call this paper clip a safety pin! 😫 you might get some bloopers every now and then in here haha , thanks for watching Sam 🤙🏽
It was thoroughly cleaned on that top orifice before i reinstalled the manifold i know in the video it cut quick to the re install. i usually only remove them if they are caked up with carbonic build up and necessary. thanks for watchin!
Lots of roll out these days from spiders. Did 3 already.
It’s good done a nice good job you found the culprit clogged the gas hole , checked throughly job well done . Thanks .
thank you!
Great catch
Thanks Wizard! 🤙🏽
I have an oddity. Miller M7 furnace. There is a cover that goes over the burner/manifold assembly. When the cover is in place and the t-stat calls for heat, one burner will light and then go out. If I remover the cover and the t-stat calls for heat, all three burners operate correctly and I can then replace the cover and it will continue to operate. I am wondering if I have a partial blockage at the intake on the roof??
well done
Appreciate ya!
That safety pin is more commonly known as a paperclip 📎
😅 I’m editing the video like did I really just call this paper clip a safety pin! 😫 you might get some bloopers every now and then in here haha , thanks for watching Sam 🤙🏽
It might be a safety clip you never know
@@tabcreedence6553😂😅
So many expert criticisms 🤣🤣
nice vido , so pro
Thank you Fisher I appreciate you! 🤙🏽
What ever was in the orifice is now in the manifold only to plug the orifice again. Why not remove the orifice and blow it out?
It was thoroughly cleaned on that top orifice before i reinstalled the manifold i know in the video it cut quick to the re install. i usually only remove them if they are caked up with carbonic build up and necessary. thanks for watchin!
First Attic furnace I saw wired up to an extension cord...
Furnace rated pig tail , welcome to the west! thanks for watchin
Too easy man
Like figuring out a puzzle! Thanks for watchin bro! 🤙🏽
Never worked on a trailer furnace did you
Been workin on furnaces since 08 man. this is just for fun
Roll outs are never fun.
Scary stuff man! Thanks for watchin Leo 🤙🏽
I hate service titan...
The pricing is crazy but other than that it’s not bad what’s some of your complaints about it?
Please don't post any more videos if you don't know what your doing. Someone might follow your bad advice.
I'll get you a Kleenex.
You’re that guy that tells em all they have a crack in the heat exchanger and need a new unit.