York Package Units: Issues every Service Technician should know

Поділитися
Вставка
  • Опубліковано 18 вер 2024
  • In this video i found a York package unit with the York Smart Equipment control board. It had a bad Condenser coil sensor and outdoor air sensor. I go through how to change them out and advice we have gotten from York on how to make the repair. Water/moisture can make these sensors act up so be aware. I also show hot to pull up temperature reading on the Control board display. Another bit of advice is if you are getting continues fault read outs on the control board it likely will need an update.

КОМЕНТАРІ • 87

  • @denniscarlton9290
    @denniscarlton9290 Рік тому +1

    Good vid. Thanks for pointing out to write in the panel what has been done for future techs and reference. I have done that for years.

  • @albotiger7268
    @albotiger7268 3 роки тому +3

    Thanks for the video! We have a ton of contracts with these kind of York units and have come across seeing a lot of those kind of fault codes on them. Cheers!

    • @mohammedhusham7893
      @mohammedhusham7893 Рік тому

      Pls, can you help me ..
      I have many questions about this type and I need the and troubleshooting list

    • @mohammedhusham7893
      @mohammedhusham7893 Рік тому

      The service catalog also please if you can

  • @chaseheatingcoolinginc.2758
    @chaseheatingcoolinginc.2758 Рік тому +1

    Thank you! Been dealing with a few of these lately
    And have found zero info until I saw your excellent video. Much appreciated!

  • @dylanroper8064
    @dylanroper8064 4 роки тому +5

    Alot of the sensor faults could be solved from a simple Relearn. Can also test the sensors by doing DC Voltage across the sensor tabs. Use a 10K chart. dont even have to go into the board or find the sensors.

  • @jaimepadilla6530
    @jaimepadilla6530 4 роки тому +3

    Good information well done 👏

  • @fishinking8414
    @fishinking8414 Рік тому +1

    i just ran into this but the eva coil temp 2 sensor failure. great video

  • @rosalinotapia2828
    @rosalinotapia2828 Місяць тому +1

    Thanks for the advice

  • @CarlosRodriguez-co5un
    @CarlosRodriguez-co5un 4 місяці тому +1

    What do you recommend when a york unit package unit alarms saying c1 locked out due to coil freeze. I checked air filter, check blower belt , make sure it's tight not loose, all supply vents are open and return grills are clean?? After when it runs it says excessive supply air temp that's next alarm? What do u recommend?

  • @whitesheatingairappliancer7101
    @whitesheatingairappliancer7101 2 роки тому +4

    I would use Dielectric grease to keep the moisture out of the connectors

  • @jfoley1968jf
    @jfoley1968jf 3 роки тому +2

    Thanks for the great information!!

  • @sumeshbabu3812
    @sumeshbabu3812 2 роки тому +1

    Sir very useful video I would like to get more videos from you sir

  • @gysgtware
    @gysgtware 3 роки тому +1

    Wired the replacement sensor incorrectly! The idea is to run the yellow excess cable ALL the way back to the harness on the SSE control board. It alleviates moisture and corrects the issue. Just cut about 6 inches from Harness and wire nut in the electrical cabinet.

  • @DragonflyAcres2022
    @DragonflyAcres2022 3 роки тому +3

    Nice job 👍

  • @mohammedhusham7893
    @mohammedhusham7893 Рік тому +1

    Pls could you help me.. I have (Idle) appear in main board what should I do and what this word is mean

  • @MEP.ENGINEERING.WORKS92
    @MEP.ENGINEERING.WORKS92 2 роки тому +1

    Good work friend

  • @joemikhaiel3710
    @joemikhaiel3710 2 роки тому +1

    I appreciate this great information

  • @terencole1854
    @terencole1854 2 роки тому +2

    When the display screen remains on idle what does that mean??

  • @brettrussell1
    @brettrussell1 2 місяці тому

    I have a 30 ton York that started to turn off the screen goes blank and then turn back on . Sometimes is stay on for 2 to 3 minutes sometimes goes through it complete cycle and satisfied. You think it could be low voltage
    Thank

  • @mark.r8900
    @mark.r8900 Рік тому +1

    Hi, my york rtu unit is giving a HS1 limit switch error on the smart simplicity control. I've checked the high limit switch and it seems fine. The manual for the control says the LS1 has tripped 3 times within an hour. This results in the HS1 LIMIT SWITCH LOCKOUT. Any help would be greatly appreciated. Thanks.

    • @stevenbarney8002
      @stevenbarney8002 Рік тому

      i am having the same issue as well need helpp !!!!!

  • @Holop88
    @Holop88 2 роки тому +1

    I just bought same sensors 4 of each kind. Haven't done any software updates.

  • @rubenschell8943
    @rubenschell8943 3 роки тому +1

    thanks for this video the same problem with model zxe14a2b1aa1a111a2,in south Florida

    • @vwhisp1394
      @vwhisp1394 3 роки тому

      You mean the zxe14a2b1aa1a111a1, not 2 in NORTH Florida! Smh, rookie!

  • @SoutheastHVAC
    @SoutheastHVAC 2 роки тому +1

    Do you know of any way to put these boards into test mode? Just as running through cooling/heating etc?

  • @germane3955
    @germane3955 4 роки тому +1

    Looking good

  • @jonnywagner8472
    @jonnywagner8472 3 роки тому +1

    Use dielectric grease in your electric connection

  • @allprecisehvacr6273
    @allprecisehvacr6273 3 роки тому +1

    Nice information

  • @ramonmolina2394
    @ramonmolina2394 2 роки тому +1

    Thank you,

  • @Justarandomspacemonkey
    @Justarandomspacemonkey 3 роки тому +1

    Thank you for this

  • @MariosACandRefrigeration
    @MariosACandRefrigeration Рік тому +1

    thanks for sharing,do they use 10k thermistors ?never mind just got back,they are 10k got 5 for 10 bucks.

  • @romeromx1585
    @romeromx1585 Рік тому +1

    Hello, do you have the main board UCB manual, how can I get it?

  • @amfmechanicbowlingcommunit5048
    @amfmechanicbowlingcommunit5048 2 роки тому +1

    Great video! I have 5 of those York units Model Number ZJ090N12R2B1BAF1A2 in my place and I after 2 years old I have a quite a few sensor errors displaying, Where do you download the software for that particular York unit from?
    Also if you can share with us the part number for that sensor? Where do you order the parts from? Appreciate it thanks

    • @HVACServiceTechnicianTalk
      @HVACServiceTechnicianTalk  2 роки тому +1

      I don't have the part number unfortunately. You can get the software download from your reginal tech support rep. We also order the parts from our local HVAC York dealer.

    • @amfmechanicbowlingcommunit5048
      @amfmechanicbowlingcommunit5048 2 роки тому

      Aren’t those units set to update automatic on its own. I am looking up my Units manual and it says that it can be updated automatically and Manually. Since this is my first time doing the update, I am not sure what is the difference and if you have the answer since you already done it. Thank you for your time!

  • @gordonpotts753
    @gordonpotts753 Рік тому +1

    Nice job. Good info. T.u.

  • @victorbejarano351
    @victorbejarano351 2 роки тому +1

    U have a fault reading excessive a temp do you know what the issue

  • @cholonon
    @cholonon 3 роки тому

    A lot of these units have a short cycling problem.
    Where in goes into a vac.
    Have you ran into that situation?

  • @ericmodernel9205
    @ericmodernel9205 2 місяці тому

    What is the ohms on that sensor??? 10,000 ohms??

  • @isaacmendoza1952
    @isaacmendoza1952 2 роки тому

    I having an issue with this unit. The board reads Excessive Supply Air Temp Cooling. It is a ZEH060 model number. It keeps saying it is on IDLE. Does it need an update?

    • @Menik559
      @Menik559 Рік тому

      Did you ever find out what that fault code was?

    • @jorgeuribe4512
      @jorgeuribe4512 Рік тому

      You have to go into details and lower the cooling temp for the sensor on the Evap coil.. i had the same isue and that fixed it

  • @wendywoodward6907
    @wendywoodward6907 2 роки тому

    Have you ever seen a York ac / swamp cooler unit??

  • @sholapuramtoday1596
    @sholapuramtoday1596 Рік тому

    Hi sir one problem York package unit fs1 compressor lock out error how to slove the prblm

  • @ericmodernel9205
    @ericmodernel9205 2 місяці тому

    Sad that the HVAC tech have to fix the BS that York has to fix at the factory

  • @mrtheloverboy89
    @mrtheloverboy89 2 роки тому +1

    Where do I download pcb update?

  • @jameswood102
    @jameswood102 2 роки тому

    Came across one hs1 limit switch lock out on a heat pump have no clue where it is nothing in the book ever heard of it?

  • @spartan6005
    @spartan6005 Рік тому

    What if it’s says failure

  • @MEP.ENGINEERING.WORKS92
    @MEP.ENGINEERING.WORKS92 2 роки тому +1

    Hi friend how are you I am your new youtube family friend stay connected

  • @dennisvo5416
    @dennisvo5416 2 роки тому

    Hi do you have the YORK tech support number? Thanks

  • @ureno831
    @ureno831 2 роки тому +1

    Need help with a excessive air supply ...shuts off.. room does not get to temp .... This is our newest AC at the plant so I'm not too familiar with all this newer technology all the other AC units here are all junk and old 😂

  • @jacquesdaoud4263
    @jacquesdaoud4263 3 роки тому +1

    Thank you for posting I'm 13.01smarter 😏

  • @rogersamaniego7392
    @rogersamaniego7392 3 роки тому

    Do you have an email address?? Can you send it thanks!