Advanced Electrical Troubleshooting

Поділитися
Вставка
  • Опубліковано 5 вер 2024

КОМЕНТАРІ • 3

  • @fpplsoftwashpressurewashin8757

    When trying to use the half method from the controller and if the acc2 has an over-current, it will shut itself down (module) and you will not be able to do a wire test from 'decoder diagnostics' down the line. So you definitely have to use an outside 24V transformer to test the line for short or open circuit.

  •  10 днів тому

    If I have a icd 400 and one of the station isn't working and the solenoid is good do I have to replace the whole icd-400

    • @Hunter_Industries
      @Hunter_Industries  День тому

      If solenoid works and you can hear it click, that tells you that the controller, wire path, and solenoid are all OK. Look for valve or water supply obstructions.