КОМЕНТАРІ •

  • @Abc_Heating
    @Abc_Heating Рік тому +2

    Please Like 👍🏼 and Subscribe 🔔 to this channel. It encourages me to create new content to help others. Please leave a comment as all feedback is welcomed. Follow us on 📷Instagram @abc_heat. Thanks for watching.

  • @AdnaneLondon
    @AdnaneLondon 7 років тому +1

    Thanks for sharing ..very interesting and well presented ..

  • @richardkoita4795
    @richardkoita4795 7 років тому +5

    I learnt a lot from this video, thank you
    if you have any more where can I find them, I'm a newly qualified engineer and I find such clips very helpful

    • @Abc_Heating
      @Abc_Heating 7 років тому

      Hi Richard, visit my site abcplumbingltd.co.uk
      if you need any help email or text me.

    • @ibrarsheikh329
      @ibrarsheikh329 6 років тому

      How can I turn off my water supply to the heat exchanger on my Viallant turbomax boiler

  • @sproutyDP
    @sproutyDP 2 роки тому +2

    Very helpful video - thanks for uploading

    • @Abc_Heating
      @Abc_Heating 2 роки тому

      You're welcome, glad it was helpful.

  • @kevinhancock4064
    @kevinhancock4064 Рік тому +1

    Great video I'm having the issue of water runs cold and not always firing up

  • @orukosaki
    @orukosaki 2 роки тому

    TNX for this VIDEO

  • @noelcortez358
    @noelcortez358 4 роки тому

    hi! we had a grundfo's pump & sensor fitted 2yrs ago and last 2 months ago we had problem with hot water and sensor was changed but now having this F.75. Pump dead but upon checking with screw driver it's spindal is rotating. Does it mean the pump is broken again in just 2years? Could it well be just the capacitor & if ever can I put any brand of capacitor as long as it's the same size and voltage. I'm desperate as it is only Saturday. I have booked for the fixed service fee but it is for Tuesday. Hope you can help as it's so hard without hot water & heating this time of the year. I would really be grateful for the reply. Thanks so much !

  • @eatdrinkasmr9333
    @eatdrinkasmr9333 5 років тому +2

    Thank you so much you save me £50. You are genius

  • @gregorydavison3421
    @gregorydavison3421 5 років тому +2

    isn't there something you have to do after fitting new/reconned HEX? Just saying...

  • @anishab6376
    @anishab6376 Рік тому +1

    Wow great video thanks for the accurate information. When will we get a face reveal

  • @Mamoo480
    @Mamoo480 5 років тому +1

    Very good nicely done

    • @davelaye7003
      @davelaye7003 3 роки тому

      not really, the part is totally reusable and easy to clean. wasted loads of money for the customer

    • @Abc_Heating
      @Abc_Heating 3 роки тому +1

      @@davelaye7003 Not really, as I replaced it with a serviced one. I then take that dirty 1 to service and place it in my stock. saves me the time of doing it on site which in turns saves the customer money. So without knowing the facts you shouldn't assume.

  • @LatifYahya
    @LatifYahya 4 роки тому +1

    Great video as I have exact same boiler and same issue where there is no hot water (although the heating works fine). Where can I order this part please? Is there a part number etc? Thanks

  • @wlondoner
    @wlondoner 6 років тому

    Hi. I have an issue with aqua plus 362-7. I have hot water but not hot enough. I can have a shower with DHW dial full on and shower mixer only on hot water - NOT mixed with cold water-. The bath isn’t too far from the boiler it’s literally installed on the other side of the bath wall. I wonder if you could help. Many thanks

    • @Abc_Heating
      @Abc_Heating 6 років тому

      wlondoner Hi, your boiler has a inbuilt 15 litre power store which if different to the boiler in the video. Which means there are more components involved in delivering you hot water.
      Does it happen on the basin or the kitchen sink?

  • @ashleylewis5771
    @ashleylewis5771 3 місяці тому

    @Abc_heating No its not straight forward to remove, what did you use to remove the lower left hand compression nut on the plate.

    • @Abc_Heating
      @Abc_Heating 3 місяці тому

      Hi, I haven't done one of these for a long time, but I believe I used pump pliers to undo that nut

  • @Fokus_1977
    @Fokus_1977 5 років тому

    @abcheatingservices hi I have burning radiators but no hot water from taps. Green light fires up. Rad inside boiler hot both ends. Pressure seems to drop too any ideas? No leaks

    • @Abc_Heating
      @Abc_Heating 5 років тому

      The pressure drop could be the expansion vessel. The hot water issue could be the diverter valve stuck in the heating position.

  • @danieIlondon
    @danieIlondon 2 роки тому +1

    How did you put it back on? I cant get the top right port to attach properly. Have tried everything

    • @Abc_Heating
      @Abc_Heating Рік тому

      It can be difficult but the direction need to checked. A tip is to look at the top side of the heat exchanger and the dirty side should be the top. Sorry for taking so long in getting back to you.

  • @Miniorpernik
    @Miniorpernik 2 роки тому

    Hi...i have got the same boiler.It keeps coming on and off on its own.The heating doesn't work.It would come on for 4 secs ,reach 70 C and then come off.No fault codes and plenty of water pressure...Plenty of hot tap water following an exchanger swap....

  • @racheldehaan2760
    @racheldehaan2760 6 місяців тому +1

    Is it an costly job my ecotec pro isn’t giving me any hot water

    • @Abc_Heating
      @Abc_Heating 4 місяці тому

      Apologies for the late reply, I hope it's sorted now.

  • @AUTOHAUSEUROPA
    @AUTOHAUSEUROPA 2 роки тому

    Does this apply to when the boiler delivers hot water slowly. In my case it needs to run at medium speed ( so tap not opened to the max ) to produce hot water?

    • @Abc_Heating
      @Abc_Heating Рік тому

      Yes, if there is lower flow the water can heat up with less heat

  • @clarkfarrell7192
    @clarkfarrell7192 6 місяців тому

    Have you got a video of you replacing the heat plate exchanger as it skipped from stripping it to it being installed .

    • @Abc_Heating
      @Abc_Heating 5 місяців тому

      Sorry I'm afraid I don't. This is a very old video.

  • @jordanlamb6102
    @jordanlamb6102 2 роки тому

    Hi any ideas why there would be a 50 percent reduction in hot water flow coming from a turbo max it's the same at all hot taps?

    • @MG63
      @MG63 2 роки тому

      I'm no expert but it could be the problem in this video or your pump maybe failing. If the pump is failing it won't be able to pump the right amount of hot water through the pipes. I'm having this problem at the moment. Just had a new expansion vessel fitted in my boiler and I asked the engineer why my water isn't so hot and he tested my pump and said it was stuck. He dislodged the impellar in the pump and the water came through hotter but it's not perfect. He said it's probably failing, so will have a new one fitted at some point. Don't know if there are other problems which cause lack of hot water.

  • @realabzhussain
    @realabzhussain 5 років тому

    So on an vaillant ecotec plus 837, what would cause the boiler to fire up and then stop firing within a few seconds when demanding hot water and repeat this cycle? Keep getting bouts of hot and cold water. Central heating working ok .

    • @ln1809
      @ln1809 4 роки тому

      Abz Hussain did u find out what was causing this problem with your boiler? Mine will act normal and then just run cold like I have a set amount of hot water and I’ve ran out. Does it every day. Can’t work out what the problem is

    • @nilsfrahm1323
      @nilsfrahm1323 2 роки тому

      Could be sensor for tap water, if unstable. You could try opening taps at maximum, to make it easier for it to senss the flow.
      Some boilers have an electronic chip which detects turbulence around a small object in the pipe.
      Others had a small wheel that rotates when water flows, I think.
      The ones with chip may need more water flowing to read properly.

    • @nilsfrahm1323
      @nilsfrahm1323 2 роки тому

      You can have a problem also with burning, if fan is jammed, it will stop. If exhaust pipe is clogges, it will stop. There is also a pressure sensor, when fan runs, it should detect lower pressure in the exhaust area, meaning smoke will go out properly.
      If that pressure sensor is not working fine, or a blockage in exhaust, it will stop as safety measure. You don't want exhaust fumes/gas to remain in the boiler, it may come into the room.

  • @ln1809
    @ln1809 4 роки тому

    Hi I have a valliant ecotec plus 832 so the problem is that its almost as if there’s a set amount of hot water for daily use and once all used the water runs cold...I will have to reset the boiler to gain a bit more hot water from it before it’s realised what I’ve done and goes cold again. In a day I’ll be able to run 1 full bath but on running a second one it will just run cold and it does this every day. What could be causing this?

    • @nilsfrahm1323
      @nilsfrahm1323 2 роки тому

      maybe it's overheating, it has an extra protection, believe at 80C in boiler and 60C for hot water. The idea is to not give you water too hot, as it will burn your skin.
      Possibly after a while, temp increases slowly until in triggers this protection.
      Reset may not work right away, due to water still being hot inside, but I think it should work after 1hour, so u don't wait a full day before resets.
      Believe it's either dirt on temperature sensor, or sensor bad that needs replacing.

  • @manlokchin809
    @manlokchin809 4 роки тому +3

    i want to ask if there is no hot water coming out of the taps but the radiators heat up, what is the possible cause of this fault?

    • @malcolmdown9170
      @malcolmdown9170 4 роки тому

      Man Lok Chin I think only the hot water circuit of the heat exchanger gets blocked.

    • @nilsfrahm1323
      @nilsfrahm1323 2 роки тому

      Can be sensor for hot water not sensing the flow, i.e. water requested by opening the tap.
      Could also be the threeway valve, which switches water flow to radiators or hot water tap, if that is jammed, it will not be able to give hot water.

  • @ruhinmadamx4075
    @ruhinmadamx4075 4 роки тому

    Hi, can you help me please need advice. What could be wrong with my gas fired boiler? The central heating comes on but it doesn't fire up for hot water. Says its on heating mode. What does that mean & how can i resolve it? Its a vaillant ecotec 415 boiler. Any info will be of much help. Many thanks

    • @nilsfrahm1323
      @nilsfrahm1323 2 роки тому

      Could be a sensor that detects cold water flowing through boiler, so it can't "see" that u need hot water.

  • @kevinhancock4064
    @kevinhancock4064 Рік тому

    I noticed u had green flashing light I've got old baxi 80he instant . Heating seems OK but hot water hit n miss may start hot then go cold. I had hot water upstairs at 1 point it was dsmn hot 🔥. But if I rub tap in general on its own it don't seem to activate the fkame only if I run 2 taps

    • @Abc_Heating
      @Abc_Heating Рік тому

      It's possible the boiler is not sensing the draw off of water

    • @kevinhancock4064
      @kevinhancock4064 Рік тому +1

      @@Abc_Heating it's OK ww git a new 1 I think it was flow switch /sensor

  • @Zeczam
    @Zeczam 5 років тому +1

    If you have a magtech type filter in your heating system, does that prevent this problem from happening?
    Also, random fluctuations of water pressure at taps, can this be a possible cause?
    Thanks a lot

    • @Abc_Heating
      @Abc_Heating 5 років тому

      Hi zeczam no the fluctuating of water pressure when no have anything to do with this fault. The magnetic filter will give a basic level of protection, which is better then not having one at all.

  • @woodbine66
    @woodbine66 7 років тому

    And that system water looks like sump oil. Never been changed since the poor boiler was installed.

  • @stephensmith5648
    @stephensmith5648 6 років тому +4

    Hope that's your basin that you're scratching up!! Joke

  • @sergiuberinde9587
    @sergiuberinde9587 7 місяців тому

    Have you drained the boiler before removing the heat exchanger via drain valves on the boiler itself? i am asking because mine doesn't have them and i was wondering how to remove the exchanger without having to drain the whole heating system...Thanks in advance!

    • @josue_kay
      @josue_kay 7 місяців тому

      You have to drain the boiler before removing the heat exchanger. The pressure relief valve is an option if you don't have a dedicated drain valve.

    • @Abc_Heating
      @Abc_Heating 4 місяці тому

      Yes I did

  • @mauricemoon8033
    @mauricemoon8033 Рік тому

    Hi ! I would like to descale the boiler ... but I can't figure out where I have to connect the pump to the cold water pipe in and out of the boiler's hot water .. !! In the manual it says cold water connection and hot water connection. Thank you !

    • @Abc_Heating
      @Abc_Heating Рік тому

      It's better to remove the dhw plate and do it like I have in the video. Hope that helps

  • @leepy120
    @leepy120 7 років тому

    hi I had this problem about 4 years ago, engineer changed dhw and boiler fine . last week it's started again with same problem as before. can you make a vid from start to finish on changing dhw or is it a job for an engineer. Can't really afford a engineer just now but would love a hot shower. thx Lee

    • @Abc_Heating
      @Abc_Heating 7 років тому

      Lee Pirate I wouldn't recommend you try this on your own. You may even lose the little hot water you're getting. I think you need to address the main issue which is sludge in the system.

    • @kevinhancock4064
      @kevinhancock4064 Рік тому +1

      @@Abc_Heating so prob needs a flush and some inhibiter ?

    • @Abc_Heating
      @Abc_Heating Рік тому

      @@kevinhancock4064 Yes, a full system powerflush cleans the complete system.

    • @kevinhancock4064
      @kevinhancock4064 Рік тому

      @ABC Heating Services thank you prob could do with it tbh . Last year bg done lots if work new parts etc but wouod need to check which parts were replaced

  • @davelee88
    @davelee88 4 роки тому

    Would an aqua sensor make any difference?

    • @Abc_Heating
      @Abc_Heating 4 роки тому

      Aqua sensor is part within the boiler which detects if the hot water has been turned on. It would not have anything to do with the debris in the system. I hope that helps.

  • @darrenwebb2779
    @darrenwebb2779 7 років тому +1

    Yes but what if it is not a blocked plate heat exchanger and the water is hardly discoloured?

    • @Abc_Heating
      @Abc_Heating 7 років тому

      Its possible you have a diverter valve issue, can be tested by turning the hot water on and checking to see if the radiators heat up.

    • @darrenwebb2779
      @darrenwebb2779 7 років тому

      Thank you for that suggestion. I have a new diverter valve.
      The Status Code is S.53. So if I have the radiators on ( S.4 ) and turn on hot water tap it goes S.11 to S.14
      and then S.53. The underlying error code is F.22 Dry Fire.
      The repair contact company have said "Power Flush" otherwise we take the matter no further.
      I can just about believe lime scale is in the boiler anywhere from in cold water to the primary heat exchanger to the diverter valve and after the diverter valve and into the secondary plate heat exchanger.
      I will get in a power flush provider, make sure they do not just go radiator happy but also flush from the cold water pipe.
      Thanks for your video all the same it is one of the better ones on you tube.

    • @Abc_Heating
      @Abc_Heating 7 років тому

      Darren Webb Hi Darren, it does seem possible you have a sludged system. Having sludge and lime scale are too different problem. If you contact me through my Web site I can help you further. All the best

  • @brad1908
    @brad1908 3 роки тому

    Hi. Are alpha laval plate heat exchangers any good?

  • @danielclark7681
    @danielclark7681 2 роки тому

    Hi I am currently having trouble with mine. Low flow on Dhw, which is highlighted more so on the shower. I've changed the thermostat cartridge. I've also just changed the heat exchanger on the combi. I have good pressure on the mains. Only thing left is the diverter valve I think. It drives ok and I can't feel any water going to the rads when calling for dhw. Could the problem still be with the diverter and reduce the DHW flow so much?

    • @Abc_Heating
      @Abc_Heating 2 роки тому

      Hi Daniel, the way to test the diverter valve would be to fire the boiler on hot water when the system is cold, then feel the flow and return pipes under the boiler. (22mm pipes) If there is no temperature difference then your diverter valve should be fine. Does the hot water work on the basin and kitchen taps?

    • @danielclark7681
      @danielclark7681 2 роки тому

      @@Abc_Heating Hi. Thank you for your reply. The hot water works on the taps. No heat getting through diverter to the rads when hot water required. I removed the cold water mains filter the other day and cleaned it up, which improved it a bit. I have now ordered a new flow limiter/reducer (mains water in) and new filter as hoping this might be causing issue 🤷‍♂️ existing one roughly 16 yrs old and may well have perished. The flow has slow got worse over the last few years.

    • @kevinhancock4064
      @kevinhancock4064 Рік тому

      @Daniel Clark where does the mains water in filter go buddy ? You're obviously quite clued . I got heating but hot water mostly ends up cold and 1 tap on its own won't activate flame a headache I've ordered a cartridge fir diverter for*

    • @danielclark7681
      @danielclark7681 Рік тому

      @@kevinhancock4064 Hiya, the bottom right of your heat exchanger is the mains water in. The part connected to this is a solid brass "aqua sensor" that bends back on itself. The filter is inside of that at the start. If you follow your mains water along where it meets this brass aqua sensor, that's where it goes. You will need to unscrew your mains water pipe to the aqua sensor, it's a bit awkward to get at, bit doable. If you look up "turboMAX spare parts pdf" you should be able to download a file.
      My low pressure was down to a pressure reducing valve, that I eventually found, fitted further back on the system before it got to my combi. This was clogged and pressure was down. Just had to replace that in the end.

    • @kevinhancock4064
      @kevinhancock4064 Рік тому

      @Daniel Clark ah ok great info pal cheers ..the oressure is going back down to a decent 1 bar after heating is off .my issue us my hit water going cold . Could be heat exchanger thermasist. Diverter cartridge or else ggrr

  • @pussycatsable
    @pussycatsable 3 роки тому

    Hi got a Vaillant ecomax in a house I'm due to move into
    Rads ok (could b hotter I think)
    But only get hot water for about 10minutes then goes cold
    any ideas plz 🙏

    • @TonyAFC85
      @TonyAFC85 3 роки тому

      I have the exact same issue. Only started happening after my service. Did you find a fix? If I turn my tap on only half way the temperature goes back up.

    • @nilsfrahm1323
      @nilsfrahm1323 2 роки тому

      believe water flow sensor not working well, can be due to age and sediments in the system, may need cleaning.

  • @UmarKhan-ww8jl
    @UmarKhan-ww8jl 4 роки тому

    Where are u located I have problems with hot water and another boiler with noise I am based in Willesden???

    • @Abc_Heating
      @Abc_Heating 4 роки тому

      I'm based in Leicester.

    • @UmarKhan-ww8jl
      @UmarKhan-ww8jl 4 роки тому +1

      ABC Heating Services awesome job, I wanted u to fix my boilers had one issue with boiler noise and the rattling pipes and the other boiler in another property with no hot water just cold coming out... anyways ur too far in Leicester but well done for ur job awesome plumber !!! 👍🏼

  • @anjamnoshad6749
    @anjamnoshad6749 3 роки тому +3

    Good but you don't show how to change and replace the part thanks

    • @Kiers80
      @Kiers80 9 місяців тому

      Absolute nightmare putting the new one in

    • @Abc_Heating
      @Abc_Heating 8 місяців тому

      It's difficult if you're doing it for the 1st time. I remember I almost cried when I did this the 1st time. As an 18-year-old, just qualified it was an overwhelming experience for my 1st dhw descale.

  • @deadalus888
    @deadalus888 Рік тому

    Hi Bro. All my hot water taps are hot apart from the one to the bath only gets lukewarm. Do you know why?

    • @Abc_Heating
      @Abc_Heating Рік тому

      Hi, there could be many reasons why! If it's only one tap then I would be looking at that bathroom tap 1st. Check to see if the cold water is not mixing with the hot water when you have just the hot side opened.

  • @balbindersingh3458
    @balbindersingh3458 3 роки тому

    Hi getting warm water when taps are fully open when quarter open getting hot, radiators are hot what can the problem be

    • @nilsfrahm1323
      @nilsfrahm1323 2 роки тому

      believe it's the three-way valve, a small motor switches the pipe through which the water flows, for radiators or hot water pipe. If getting clogged, can't fully switch to hot water and water also goes to radiators.

  • @mironabramson
    @mironabramson 5 років тому

    thx for the video. I have problem that when I open the hot water I se the fire light up but the water are worm and not hot

    • @Abc_Heating
      @Abc_Heating 5 років тому

      Hi it's possible you the the same problem shown in the video.

    • @mironabramson
      @mironabramson 5 років тому

      @@Abc_Heating Thanks for reply. Also I noticed that the fire is sometimes high and sometimes very low. That is the case here?

    • @Abc_Heating
      @Abc_Heating 5 років тому

      @@mironabramson yes that is what would happen if the boiler is over heating.

  • @ajmalkhan7173
    @ajmalkhan7173 Рік тому

    Hi I have an issue with vaillant ecoto pro 30 hot water colour is brown any reason of this issue ? Waiting for your answer

    • @Abc_Heating
      @Abc_Heating Рік тому

      Sorry for the late response. I hope your issue is resolved.

  • @ibysplumbingvideos9684
    @ibysplumbingvideos9684 4 роки тому

    Good job fixed blocked heat exchanger now maybe need to fix blocked sink.

  • @bigt8699
    @bigt8699 5 років тому +2

    How do I isolate the water going to the heat exchanger? How to drain?

    • @Abc_Heating
      @Abc_Heating 5 років тому +2

      The cold water going into the boiler needs to be isolated. Then drain the boiler from the flow or return valve, which has a drain point.

    • @bigt8699
      @bigt8699 5 років тому +1

      Thank you sir and great video👌

    • @cindersberry725
      @cindersberry725 4 роки тому +3

      If you have to ask then you should not even be touching a boiler

  • @bobtheobald5466
    @bobtheobald5466 2 роки тому

    Domestic ur ur ur.what did you call it.

  • @wlondoner
    @wlondoner 6 років тому

    It seems I don’t know my own boiler. What do
    you mean 15l power store!!!!
    It’s noticeable when I have a shower. Temperature Of the shower, no where near hot. As I said I could have shower straight from the boiler with no cold water mixed with max temperature setting.
    Regards

    • @mrbachittarsingh9243
      @mrbachittarsingh9243 6 років тому

      Sounds like the wiring harness has got a water leak or the gaseous valve

  • @davelaye7003
    @davelaye7003 3 роки тому +1

    why on earth would you fit a new heat exchanger? use a strong cleaner or One-Shot, and its like new, saving the customer well over a hundred quid. terrible

    • @nilsfrahm1323
      @nilsfrahm1323 2 роки тому +1

      dude, he said heat exchanger that has been cleaner already, not new.
      He may take it to his shop, clean it, then put it in next customer boiler.
      This way he doesn't have to bring lots of heavy stuff to clean his system, he does this at the shop.
      They do this also with pumps, which rarely fail, mostly they get dirty and seize up.

    • @Abc_Heating
      @Abc_Heating Рік тому +1

      It not a new heatexchanger that's been fitted in the video. I've used another heatexchanger which has been cleaned with a pump and chemicals.

  • @julianperez1373
    @julianperez1373 6 років тому +1

    Porque paras vídeo. No has solucionado nada. Lo el vídeo entero para ver cómo cambias la pieza.

  • @Oxford8888
    @Oxford8888 3 роки тому

    So many leaking problem with my vaillant combi boiler. I am an engineer. Inside the boiler,I couldn't believe it is Germany company. It is bad,bad designed.

    • @petergee1395
      @petergee1395 3 роки тому

      It is an incredible design and is in fact better than many on the market today. It is just complex and in order to fix it takes much understanding of the complex nature of the device. So often it is condemned by plumbers as do not understand it they want to fit a new one. It is the "Sherman Tank" of boilers and will last for decades with care.

    • @davelaye7003
      @davelaye7003 3 роки тому

      you're, an engineer and you think Vaillants are a bad design??? they are best boilers on the market, the Worcesters are miles behind them

  • @robertwhitehead2787
    @robertwhitehead2787 2 роки тому +2

    Would not be happy with engineer cleaning parts in my ceramic wash basin.

    • @thedirtychips8556
      @thedirtychips8556 7 місяців тому

      Shut up, it’s just a bit of dirt that can be cleaned you wet tissue

  • @wolfgangmueller1529
    @wolfgangmueller1529 2 місяці тому

    Bitte übersetzen auf deutsch.danke.

    • @Abc_Heating
      @Abc_Heating 2 місяці тому

      Sie sollten in den Einstellungen Untertitel erhalten können.

  • @cindersberry725
    @cindersberry725 4 роки тому

    Why are you dumping the muck in the customers basin. Dumping g the 2 plates in their could have chipped it.

    • @Abc_Heating
      @Abc_Heating 4 роки тому +3

      Could've but didn't. Thanks for the comment.