In this, for the earth lamp, the transformer will be 440/6v right instead of your marking 220/6v, which is right? Between 2 phases(R,Y) voltage will be 440 right?
Bro actually R,Y,B ethu earth analum short circuit la athu current pass panna try pannum , so bulb has some resistance , and one more resistance must be connected , through bulb resistance and resistor resistance current flow agama short circuit la agum , so that particular bulb will not glow or dimmly glow bro
Sir, If there is unbalance in loading of a 3 phase system there will potential difference at the neutral conductor. In ships how will you over come this problem
In 3 phase 440v supply will not have any unbalance load.but in 220v supply distrubution is have as you said. so monitering 440/220v transformer temperature is important. Appriciate your comment.
In high voltage ships (greater than 1000 voltage) they are using earthed neutral system Source and load both are earthed with hull also source will be connected with NER "neutral earthed resistance" And connected with hull In high voltage ships earthed neutral system even at single earth fault black out will occur it will not wait till for double earth fault like isolated neutral system
@@bt9604 In high voltage system current value is low but in case of short circuit occurs. The fault current flows in alternate path which having low resistance so the short circuit current level will shoots high than the normal level. In this case if any humans touches that short circuit equipment it leads to death also this short circuit current damages the source that's why both source and load are earthed to the hull
10years b4, had collided with gas carrier Only hull damage, no human injuries Have no photos to share. Most of the time these kind of accident happened due to human error only.
Hi Anna .....one doubt one ship Vanganum na eana document vandum and quality erukamum eana process pandanum , second hand and new ship price , ship vangana load eapadi kidikum company aggreement eapadi kidikum ... profitable business ha Anna...... Eadu madari video earum potadu illa anna..... So nenga podunga....then video la eanudiya name solunga DHARMA RAJ
Kili pillaiki solra mari solringaleee bosss....thankyou very much 🔥👍
தமிழில் விவரித்தது மிக்க மகிழ்ச்சி.... Its great effort in marine electrical engineering knowledge... Keep post more. Thanks
உங்கள் விடீயோக்கள் அனைத்தும் மிக மிக அருமை சார்
This channel is a hidden gem 💎 ❤
Your electronics deep explanation in tamil are very useful to me more thanks sir
Perfect explanation and clearly understood❤❤
excellent sir,,,, arumai arumai,,,,,
Earthing in ship Tamil ua-cam.com/video/kYTwG0sGNEg/v-deo.html
Sir neenkal vere level sir.... Neel naal vaazhka..
Earthing in ship Tamil ua-cam.com/video/kYTwG0sGNEg/v-deo.html
Proper Explanation 😊 keep going
Excellent Explanation. Thanks
ua-cam.com/video/kYTwG0sGNEg/v-deo.html
Hi Sir, Can you assist me, Regarding the earth lamp transformer shall I use the 440/12V ratio? or is it mandatory to use 440/6V? please clarify.
Very informative, sir. 👍
அருமையான பதிவு நன்றி
Earthing in ship Tamil ua-cam.com/video/kYTwG0sGNEg/v-deo.html
Thank you brother ❤️❤️❤️❤️❤️❤️❤️❤️🙏🙏🙏🙏
Sir u'r reached 100k subscribers
Congratulations.
Earthing in ship Tamil ua-cam.com/video/kYTwG0sGNEg/v-deo.html
Nice information 😍😍
Sir generator pralleling panrathu epdinu vedio podunga
Sir electronic it's my habby Naa idhaa proposalla maththa ninikkura trying center edhachum eannakku recommend pannungaa
நன்றிகள் ஐயா
High voltage ships la earthing konjam sollunga sir
சார் கப்பல் இடிதாங்கி இருக்குமா
Gud explanation
Super anna ❤
boat and ship wiring எப்படி செய்ராங்க என்பதை விரிவான vedio ஒன்றை தரவும்
Ship mechanical commission technician roles video upload pannunga sir
Thank you so much.
Super bro.
Earthing in ship Tamil ua-cam.com/video/kYTwG0sGNEg/v-deo.html
Are you from synergy sir
Sir ship panel wiring are sama for substation wiring?
ship wiring based on isolated earthing system.
other than that more or less same.
In this, for the earth lamp, the transformer will be 440/6v right instead of your marking 220/6v, which is right? Between 2 phases(R,Y) voltage will be 440 right?
👌👌💐💐🙏🙏🙏நன்றி சார்
Bro actually R,Y,B ethu earth analum short circuit la athu current pass panna try pannum , so bulb has some resistance , and one more resistance must be connected , through bulb resistance and resistor resistance current flow agama short circuit la agum , so that particular bulb will not glow or dimmly glow bro
Super sir.
Nanri anna
Super super brother
Congratulations sir for getting 1L SUBSCRIBERS.
Consistently upload videos in upcoming days.
Bro onga contact number kedaikuma
அருமை
Sir, If there is unbalance in loading of a 3 phase system there will potential difference at the neutral conductor. In ships how will you over come this problem
In 3 phase 440v supply will not have any unbalance load.but in 220v supply distrubution is have as you said.
so monitering 440/220v transformer temperature is important.
Appriciate your comment.
No NEUTRAL Connection are used on Ship only 3 alive phases and they are balanced the loads.
Sir pls make video about Generator working principles.
why we cant use both ( ohms meter and Earth lamb) in same time.//
Sir oru phase bright ta iruku other 2 phase dim ma iruku ..so fault in brighter phase sa .bt told faulty phase become dim.
dim phasethan fault. switch press pannatha pothu ella bulbum same brighta irrukka.
Then why they are not giving this in high voltage ships,
Neural is earthed in it..?
In high voltage ships
(greater than 1000 voltage)
they are using earthed neutral system
Source and load both are earthed with hull also source will be connected with NER "neutral earthed resistance" And connected with hull
In high voltage ships earthed neutral system even at single earth fault black out will occur it will not wait till for double earth fault like isolated neutral system
@@selva-the-sailor77 that's why I'm asking why, because fault current level is low in HV system compared to LV
Then why they ground it
@@bt9604 In high voltage system current value is low but in case of short circuit occurs. The fault current flows in alternate path which having low resistance so the short circuit current level will shoots high than the normal level. In this case if any humans touches that short circuit equipment it leads to death also this short circuit current damages the source that's why both source and load are earthed to the hull
@@selva-the-sailor77 ok, thanks for the explanation ♥️
Nice expalinatiom
In ship, why control transformer's secondary coil is grounded please explain bro
Free energy, fly wheel energy, flywheel energy multiple இதை பற்றிய வீடியோ போடுங்க அண்ணா.
(Flywheel free energy posible or not)
Not possible. Energy ya aakavum mudiyathu azikkavum mudiyathu ondril irunthu ondraga maatra mattumey mudiyum.
Sir neenga use pandradhu yenna software
Earthing in ship Tamil ua-cam.com/video/kYTwG0sGNEg/v-deo.html
Is there any turbulence while ship and ship crossing like vehicle to vehicle crossing on road by wind
Turbulance will be there.only affect small ships.
@@GKSOLUTIONS is there any accidents like to told in your experience to small ships cross your ships
10years b4, had collided with gas carrier
Only hull damage, no human injuries
Have no photos to share.
Most of the time these kind of accident happened due to human error only.
Hi Anna .....one doubt one ship Vanganum na eana document vandum and quality erukamum eana process pandanum , second hand and new ship price , ship vangana load eapadi kidikum company aggreement eapadi kidikum ... profitable business ha Anna......
Eadu madari video earum potadu illa anna..... So nenga podunga....then video la eanudiya name solunga DHARMA RAJ
Sir,how to you use single phase loads, neutral is not available?how 1phase system working?Plz explain
For 220v , have 3phase transformer and nuetral will be there.but not earthed with ship hull.
Air craft carriear ship pathi soolunga sir
Sir if two phases touch the ship hull
At that time human gets electric shock??
no
single phase load eppti use pannuvaka
440/220v 3phase transformer irrukum.Aduvum isolated earth system
@@GKSOLUTIONS thank you sir
sir,60 watts Lamp one hour ran akum pothu.....60watts or 60kwh aa...?
60wh
1000wattshour is 1 unit charged by EB
Thank you sir
கப்பலுக்கும் நமக்கும் என்ன சார் தொடர்பு
🙏🙏🙏
Sir,
Your further videos not posted after Earth system in ship.
Earthing in ship Tamil ua-cam.com/video/kYTwG0sGNEg/v-deo.html
Super sir
Earthing in ship Tamil ua-cam.com/video/kYTwG0sGNEg/v-deo.html
4 to 20milli amps என்றால் என்ன என்று விளக்கம் தாருங்கள்
வீடியோ அனிமேஷன் எப்படி செய்வது என்று வீடியோ பதிவு செய்யுங்கள் சார்
Earthing in ship Tamil ua-cam.com/video/kYTwG0sGNEg/v-deo.html
Anna video podalai ennachu,
Ship la joint panitingala !???
not yet.
from next week new videos will come.
@@GKSOLUTIONS Thank you Thank you 🙏 🙏 🙏 ,
Anna video podunga...
Fly wheel energy,
Flywheel energy multiple electricity ,
Flywheel free energy pathi video podunga.
please Led tester circuit diagram
இந்த மீட்டரை கப்பலில் உற்பத்தியாகும் கரண்டில்தான் இணைத்து சரிபார்க்க வேண்டும். சரியா? நல்ல தகவல் நன்றி.
can check in lab also.
Please post the more electronics videos
Earthing in ship Tamil ua-cam.com/video/kYTwG0sGNEg/v-deo.html
Thanks
Thanks sir
Ship lighting arrested please explain
Earthing in ship Tamil ua-cam.com/video/kYTwG0sGNEg/v-deo.html
Please water level control circuit
Earthing in ship Tamil ua-cam.com/video/kYTwG0sGNEg/v-deo.html
Make practically
Hi Sir
😇
விளக்கத்திற்கு நன்றி குருவே Ultrasonic sealing mechine circuit. Please
Earthing in ship Tamil ua-cam.com/video/kYTwG0sGNEg/v-deo.html
English 😢...
'Glow' ஆகும் இதை கூட தமிழ்ல 'எரியும்' சொல்லக்கூடாதா. பேசாம முழுவதும் ஆங்கிலத்தில் நடத்திவிடும்.
இதுபோன்ற அரிய தகவலை நமக்கு இலவசமா பகிர்வதற்கு நாம் அவருக்கு நன்9கடன்பட்டுள்ளோம் குறைசொல்வது ஏற்புடையதல்ல
Thank you sir