Adiabatic humidification or evaporative cooling using ASHRAE Psychrometric analysis software

Поділитися
Вставка
  • Опубліковано 13 жов 2024

КОМЕНТАРІ • 7

  • @TAHIRHUSSAINMEPINDUSTRY
    @TAHIRHUSSAINMEPINDUSTRY 3 роки тому

    Excellent explanation. What is name of book & how to get it?

  • @SanjayYadav-fy4dg
    @SanjayYadav-fy4dg Рік тому

    What minimum temperature of air can be achieved during evaporatorive cooling and what will be required sprayed water temp.
    Ex we have air at RH 37% and Tdb is 42 deg C.
    Can i cool the air at 11 deg C and what will be the required sprayed water temp.
    Please explain

    • @rishabhmelwanki1167
      @rishabhmelwanki1167  Рік тому

      Calculate WBT at that point. WBT itself will be ideal min temperature of air that can be achieved and same will be water spray temperature considering zero bypass of air i.e. ideal condition.

    • @javiervillegas4399
      @javiervillegas4399 Рік тому

      @risha so basically in this example the water temperature should be 11 deg C??

    • @SanjayYadav-fy4dg
      @SanjayYadav-fy4dg Рік тому

      @@javiervillegas4399
      In this condition wet bulb temp is 25.1 deg but i need to cool up to 11 deg C. Is it possible to adding chilled water at temp 7 deg C,
      And what will be the makeup chilled water and TR required for chiller load of makup water

    • @SanjayYadav-fy4dg
      @SanjayYadav-fy4dg Рік тому

      @@rishabhmelwanki1167 Can i cool the air below wet bulb temprature by adding chilled water through evaporatorive cooler?
      Ex if i have air at dry bulb temp at 36 deg C and RH 42 % wet bulb 25.1 deg C
      Can i cool the air at 11 deg
      What will be the makeup water flow rate and what temp will be required.
      Please explain with calculation