Fire alarms keep going off at middle school EST quick start problems Saturday troubleshooting

Поділитися
Вставка
  • Опубліковано 2 жов 2024

КОМЕНТАРІ • 442

  • @nics-systems-electric
    @nics-systems-electric  Рік тому +14

    Thanks for watching. If you're interested in seeing more of these portables check out one of my favourite videos here ua-cam.com/video/NEqfLdOITAE/v-deo.html

  • @kc0eks
    @kc0eks Рік тому +186

    I'm an IT guy and this entire process reminds me of so many times tracking down weird issues. Makes you go insane then that final moment where you find the problem it is just amazing.

    • @Wtfinc
      @Wtfinc Рік тому +6

      It kills having other people with me like that. Usually distracting. Sometimes very helpful tho.

    • @zombieregime
      @zombieregime Рік тому +5

      Never trust labels that can be moved 100%, even if you did them yourself.

    • @devinbaeten13
      @devinbaeten13 Рік тому +1

      Came here to say this lmao

    • @lawrenceplays
      @lawrenceplays Рік тому +4

      I'm from an IT background and if I had a problem where the monitoring /diag tool says it's one device but that device is showing its operating normally, then my first instinct is to look at all the other devices to see if they are working normally.

    • @HogwartsBasement
      @HogwartsBasement Рік тому +4

      You need to completely destroy the place demolish all the buildings and then you realise that Janice the cleaner unplugged the power cable to vacuum

  • @mewing-gawd
    @mewing-gawd Рік тому +43

    next video: welcome back to durability testing today we’re testing est panel

  • @FloppyDiskMaster
    @FloppyDiskMaster Рік тому +69

    No idea what any of this is, but thanks for helping me procrastinate from cleaning for another 70 minutes

    • @nics-systems-electric
      @nics-systems-electric  Рік тому +27

      This is one of my favourite comments I don't have to give some complicated response lol

    • @SundayBoy72
      @SundayBoy72 Рік тому +2

      Me too.. it’s so fascinating seeing the troubleshooting… so z z z z … I’m back 🥹😬

    • @Goofy-ahh-veshremy
      @Goofy-ahh-veshremy 5 місяців тому

      It's a fire alarm dumb

  • @Zinojn
    @Zinojn Рік тому +44

    This is fascinating to me -- I work in the tech/IT side of systems engineering but have always been curious what sys engineering means to some of my peers in other industries! Subscribed.

  • @nics-systems-electric
    @nics-systems-electric  Рік тому +74

    Update on the situation we had a technician come out on Monday. Me and the tech put every portable into trouble temporarily one at a time to get all the modules labelled properly. The problem module was working perfectly fine so we did not replace it personally I would have anyways, however the tech left us a spare module to put in place if it acts up again. The long-term solution is to replace the system. We did have our company that deals with notifier go through a walk-through of the building with us. So we did get a quote to replace the system with notifier. It would not be a full addressable swap, but a direct replacement with addressable smokes and modules and leaving conventional zones. But replacing bells with the one for one upgrade of horn strobes for now and then likely coming back later and adding more as horn strobes are not as effective as bells. However this summer is extremely busy with other system upgrades and annual testing as well as moving several portables school to school. so this upgrade would not be done until spring break or winter break of the 2023/2024 school year.

    • @josephfrye7342
      @josephfrye7342 Рік тому +4

      oh bloody hell with these quickstart series. :\ sometimes Simplex and Edwards are decent brands except Quickstart series.

    • @nics-systems-electric
      @nics-systems-electric  Рік тому +4

      @@josephfrye7342 some of EST's products are not bad. Simplex products aren't terrible however their customer service is so as a company they are not good

    • @achannelwithnopurpose1977
      @achannelwithnopurpose1977 Рік тому +5

      @@nics-systems-electric Simplex is mainly recognized for their products. If it wasn’t for JCI (and mostly their business model), Simplex would be even more prevalent and probably run circles around Honeywell’s brands. But it’s nice to see the quickstart finally get what’s coming to it. Please keep it and durability test it. Plug the slc into 120v and watch the carnage.

    • @nics-systems-electric
      @nics-systems-electric  Рік тому +5

      @Marc Leslie as far as coolness and the nice sound I do prefer the bells but I have to look at it from a realistic standpoint and realize that the strobes are the future with less current draw more reliable

    • @adamcrane1436
      @adamcrane1436 Рік тому +1

      Good morning ​@@nics-systems-electric

  • @Kaarlamari
    @Kaarlamari Рік тому +14

    Best 1 hour and 10 minutes of my day

  • @impsh500
    @impsh500 Рік тому +37

    @nics-systems-electric: As a fellow fire alarm tech, for future reference with EST / Kidde fire alarm panels when a module/detector, etc. goes into alarm / trouble condition the panel should also show the module's serial number (this same number would match the serial number sticker on the module itself). Granted, that is dependent on if the original installer/programmer kept the module's serial number in programming. On that type of panel, try the status button to see if additional info shows the active module's serial number. That serial number can make it easier to troubleshoot and narrow down the possibilities of what is causing the fault / issue.

    • @nics-systems-electric
      @nics-systems-electric  Рік тому +13

      That's a good call. Thanks for the tip. I admit I got complete tunnel vision looking at the labelling trying to find it that way which is obviously something to avoid while troubleshooting. and look at the whole picture. But I should've known better. I even did use the status light to check for any helpful information, I should've considered that. Thanks again for the tip

    • @wolphin732
      @wolphin732 Рік тому +2

      @@nics-systems-electric Skipping steps in troubleshooting... especially when on call-in was something I worked to stop doing.
      Gather information (Symptoms, Errors, what has happened, what steps have already been done), Question contact/user (to confirm details -- say it back to confirm it is heard/understood correctly, and as much details), Identify symptoms (as may be some not noticed), Determine if any changes have been done, if so when/what, duplicate (confirm the symptoms and errors are still there... and it hasn't just resolved itself), most important... resolve one issue at a time. At points you seemed to start, then jumped to doing something else, but with the security system and fire alarms interconnected... that would be harder to do.

    • @impsh500
      @impsh500 Рік тому

      @@nics-systems-electric Been there, done that w/ the "Tunnel Vision" happening. :) I recently had a Kidde VS system that would randomly pop the dreaded "System Ground Fault" message that would last for a few seconds on the signaling line circuit (SLC). Tore the SLC apart several times trying to isolate / segment down to locate the cause, and banged my head against the wall. Turned out to be a faulty switch on a sprinkler tamper valve that was causing the ground fault condition. I forget what I had done, but I had managed to get the panel to say what SLC device had the fault on it and once that happened figuring out the exact cause was super simple. It's all good in the end. :)

    • @russellhltn1396
      @russellhltn1396 Рік тому

      @@nics-systems-electric Part of it is you were too trusting in the labeling. Incorrect documentation is a fact of life. Don't be too quick to judge, but consider it when things don't add up.

    • @JoanneStealey-dz6qm
      @JoanneStealey-dz6qm Місяць тому

      Who's idea was it to put a security system keypad in a bathroom?

  • @jeffjohnsisland5551
    @jeffjohnsisland5551 Рік тому +8

    This is first vid of yours I have watched. I am the one at work that handles fire alarm problems. Not certified, just onsite guy with knowledge.
    I felt your pain as you were trying to figure out the problem. I was telling you to bypass the SLC when you were disconnecting the zone circuit and then you did. 😁 yea!
    I keep some emergency rations in my work vehicle. My choice is a couple of cans of pull tab top chili (I can eat it cold if I have to), a couple plastic spoons and some bottles of water. It’s hard to think straight when you are hungry or thirsty. Sometimes you have to stop and fuel up so you can figure out the problem. Sometimes fueling up also helps get your patience back.
    Like your tool bag with pockets for everything. I think I will get one like it.
    I think you have the brains to work through problems like that panel. Sometimes it’s easy to get stuck on the idea that the problem is “A” and you have to remember to stop and reevaluate, is there a “B”!
    I have nine months before I retire, you have a bit more😝. Make it a goal to work a tiny bit smarter every day!
    Best wishes,
    Jeff

    • @nics-systems-electric
      @nics-systems-electric  Рік тому +3

      Hey thanks, I'm glad you enjoyed the video and for sure can't think well when you're hungry lol

  • @mewing-gawd
    @mewing-gawd Рік тому +14

    my old school had an EST system in which we would have “fire drills” every few days.

    • @nics-systems-electric
      @nics-systems-electric  Рік тому +8

      Special EST feature some of the best surprise drills out there

    • @lukep4339
      @lukep4339 Рік тому +5

      ​@@nics-systems-electric My district *only* uses EST, we had a few "surprise" drills

    • @mewing-gawd
      @mewing-gawd Рік тому +2

      @@nics-systems-electric fr

    • @ABCEasyas--
      @ABCEasyas-- Рік тому

      Yep, one year in college I lived in a dorm/apartment that had EST alarms and panel. Fire alarms went off (whether it was a prank, burnt food, or system failure) almost every week!

    • @parker02311
      @parker02311 Рік тому +1

      @@nics-systems-electric My school uses EST, get surprise drills every once and a while. However I think this is more because of the large amount of pull stations in opened and unattended classrooms, could also be both. EST is popular around where I live

  • @fatboyfat_uk
    @fatboyfat_uk Рік тому +2

    Interesting stuff. The fact that you drive from the portables to the main school and back so many times instead of just walking is the most American thing ever though! 😂

    • @nics-systems-electric
      @nics-systems-electric  Рік тому +1

      I'm in Canada and when you've got 40 pounds of tools it's easier to drive lol

  • @GaryBeltz
    @GaryBeltz Рік тому +13

    I think Mr. Quickstart needs to be replaced with a nice Notifier NFS

    • @nics-systems-electric
      @nics-systems-electric  Рік тому +6

      Yeah couple weeks after this we did a walk-through of the building with our notifier guys to get a quote for replacement

    • @jacobflanigan6343
      @jacobflanigan6343 Рік тому +4

      If the quick start gets replaced with an nfs, will there be fire suppression

    • @GaryBeltz
      @GaryBeltz Рік тому +1

      @@jacobflanigan6343 not unless the school has servers that they need to protect usually suppression systems are only for pressurized server rooms

    • @EASsirenVids01
      @EASsirenVids01 Рік тому +1

      @@nics-systems-electric will there be a video on replacing that system?

    • @nics-systems-electric
      @nics-systems-electric  Рік тому

      @@EASsirenVids01 yes I will most likely make a video if I'm part of this replacement project which I likely will be and as for the other comment about suppression system no suppression system has nothing to do with a fire alarm upgrade and they are only put in place in specialty areas which this building does not have any that would require such system

  • @s0584333
    @s0584333 Рік тому +55

    Accurate labeling is important. When the system is installed every point needs to be tested and verified for accuracy before it is signed off by the intaller, fire department and owner. annual testing should also verify accuracy. Failures of many parties led to this issue being this difficult to troubleshoot. Hopefully lessons were learned during this and this will help in future trouble shooting.

    • @russellhltn1396
      @russellhltn1396 Рік тому +3

      It appears that it was accurate between the sensor and the front panel, but the modules themselves were not properly labeled. Apparently that's not checked as part of the annual. Nor would it really need to be as it's not safety critical. It's just for the tech's convenience.

    • @johnrauner2515
      @johnrauner2515 Рік тому +3

      This was just terrible troubleshooting. He lept to a rash conclusion without any supporting evidence and then went about handling the situation as though his idea it was software was correct. This was so drawn out because his approach was miopic. First rule in a situation like this is DO NOT FIXATE. All he had to do was keep an open mind. He closed his mind and convinced himself the first thing he thought of was the answer and that decision tied him up in knots.
      Instead of grabbing the first thing he thought of as correct and thus not even thinking about others, he should have said software could be causing this but it might be something else entirely. And kept looking to see what else could also be the cause. He didn't keep looking because he was convinced he was already right.

    • @nics-systems-electric
      @nics-systems-electric  Рік тому +3

      @@johnrauner2515 that's not true I never once said this is the problem for sure if I didn't have an open mind the problem wouldn't have been solved

    • @russellhltn1396
      @russellhltn1396 Рік тому

      ​@@johnrauner2515 I agree it's a poor example, but it's not like I've never gone down the wrong rabbit hole. Let he who is without sin cast the first stone. He looks to be pretty young. Hopefully he learns from it.

    • @jerrykorman7770
      @jerrykorman7770 Рік тому

      My favourite is building P&ID or other diagrams, that have “TO BE FIELD VERIFIED”

  • @johndeerefan725
    @johndeerefan725 Рік тому +5

    Obviously it's a QuickStart and I see why EST discontinued the QuickStart and I've never saw one in person. I see EST3s and EST iO panels and those I think do slightly better than QuickStarts.

  • @amahlaka
    @amahlaka Рік тому +9

    Great video, and really relatable, in the sense of rabbithole-troubleshooting, been guilty of that many-many times in my industry as well.
    While the time spent diagnosing the control unit/brains of the machine could be considered “wasted time” by some, it actually provided a great learning opportunity to you (and us).
    Confirmation-bias is super common when doing complex troubleshooting for extended periods of time😅
    Thanks for the captions that explain the problem early on, as otherwise i would have had no idea what was going on.
    It is sad-funny(or ironic?) that the module that was causing the alarms was right next to the one you were looking at.

  • @marshallwalker8000
    @marshallwalker8000 Рік тому +1

    When I realized that is ALSO my old middle school!! small world!!

  • @ObamnaSoda513
    @ObamnaSoda513 Рік тому +8

    will you guys replace it this summer???

    • @nics-systems-electric
      @nics-systems-electric  Рік тому

      No at the time of making this video there was no plans for replacement however a couple weeks after we did a walk-through with our notifier guys and got a quote for replacement but we have too many other things going on this summer that this will probably be sometime in the 2023/2024 school year

    • @ObamnaSoda513
      @ObamnaSoda513 Рік тому

      @@nics-systems-electric
      K that makes sense thanks

  • @iffyspeak
    @iffyspeak Рік тому +1

    i dont know why youtube recommended this to me, but i am glad it did

  • @Fire_Alarm_Duude
    @Fire_Alarm_Duude Рік тому +4

    Well it’s a Quickstart. you know they are most of the time there trash

    • @GaryBeltz
      @GaryBeltz Рік тому +2

      Simlex is worse according to NIC I asked which one he would call the lesser evil and he said EST

    • @nics-systems-electric
      @nics-systems-electric  Рік тому +3

      EST may have problems however we were able to get a technician in on Monday that's the difference between EST and Simplex both can be problematic but Simplex would be a month till you got them in and then they rip you off once they were there

  • @Peekofwar
    @Peekofwar Рік тому +6

    Would be useful if the red lights stayed illuminated on the module when it alarms... At least for a few seconds so that you can more easily spot it.

  • @stevendamavandi3482
    @stevendamavandi3482 Рік тому +2

    I was watching this last night and i fell asleep and when i went to check my tablet ib the morning it was at 2% and it was on a linus tech tips video

  • @lawrence_Cuzo1029
    @lawrence_Cuzo1029 Рік тому +12

    It’s cool how you can help with the fire alarms in systems are you a part of the district? How are you able to do these type of jobs? Love your videos❤

  • @MisterBroadnax
    @MisterBroadnax Рік тому +1

    32:05
    EST: Goes Back into Alarm
    Nic: “God Da******”

  • @Granth_Man
    @Granth_Man Рік тому +5

    This is so cool. I love electric videos(battery’s, ups) and troubleshooting

  • @bm652Z
    @bm652Z 9 місяців тому +2

    54:22 i didnt know those panels had christmas tree mode

  • @hypnotic8285
    @hypnotic8285 Рік тому

    man a long time has came for this channel, i remember when this was called pickle700 or something like that but keep up the content

  • @kuramagb
    @kuramagb Рік тому +2

    biggest Lesson is never presume anything even in your own team/company there always going to be that one thing which slips even in years of checking verify verify verify

  • @afiliaassela
    @afiliaassela Рік тому +3

    7:19 man a lot of fire going on there, couldnt even see anything.

  • @Spl1ntMan
    @Spl1ntMan Рік тому

    thumbs up for the security mind of your video editing.... blurring the video so the keys cant be copied... 10/10

    • @nics-systems-electric
      @nics-systems-electric  Рік тому

      Hey thanks for recognizing that! that actually means a lot most just talk crap about it.

  • @Ron2600_
    @Ron2600_ Рік тому +2

    When he took off the module that you thought was an alarm and a portable other than 1 when it's in trouble you should have known right away that the labels were messed up.

  • @UpcraftConsulting
    @UpcraftConsulting Рік тому +3

    At 1:01:47 is the exact moment I think you may have "fixed" the glitch. Wire just fell off was what was said. And it was not one of the 2 wires removed for testing from what I could see.

    • @nics-systems-electric
      @nics-systems-electric  Рік тому

      I believe it was a different zone altogether even if it was the right zone it was still solid contact until it broke as the wire didn't fall off it broke off from fatigue if it had been loose even still fire alarms are a normally open system so loose contact only will cause trouble not full alarm

  • @stphinkle
    @stphinkle 28 днів тому

    What annoying it is for fire alarms to keep going off. I remember back in the 1990s at my high school (brand new school), the fire alarms kept false alarming with alarms in the ventilation sensors kept activating. The school ended up having to replace the system a couple of years later. How did they pick the install contractor back then? LOW BID!

  • @suzylarry1
    @suzylarry1 Рік тому +2

    the fact that they are registered / labeled wrong really really suck ! You trust on test when it was installed would have been caught ! all in a day of headaches.

  • @wolphin732
    @wolphin732 Рік тому +5

    When playing with it the first time and tripping a different zone... me as a computer tech goes... wait... that was a different area... As I have seen many times items are mislabelled. I prefer to confirm the device is correct device as part of my early troubleshooting, especially when playing with what should have been the device tripped something which shouldn't have been related. Figuring out which device it was at that point would have saved a lot of back and forth, especially when jumping it out didn't resolve the issue.
    Also... as soon as I was on-site, would have made sure whoever was responsible had notified everyone monitoring (911, security, etc) that you were working on the system before I even opened a panel or touched a button.

    • @nics-systems-electric
      @nics-systems-electric  Рік тому +1

      Yes for sure you can never trust the labelling too much and that got reinforced into my mind that day and yes definitely notify the monitoring company before going hands on which in that case I was OK to start touching stuff as the system was already in alarm and had already called out so it couldn't call out again until reset

    • @johnrauner2515
      @johnrauner2515 Рік тому +1

      I don't think this guy has the skills to be touching a system like this. He wasted most of the day running around in circles because he decided the first thing he thought of was the answer - the firmware upgrade was the problem. From there he fixated on this to the point of being myopic.
      This was just terrible troubleshooting. He reached a rash conclusion with no supporting evidence to justify it and then did nothing to confirm it as the cause. Eventually hours later he isolated the data channel into the panel to see if the fault went away which it did. That confirmed firmware wasn't the problem. But he should have done that test the moment he decided the firmware was the problem to confirm his conclusion or exclude it. That's just basic troubleshooting. If you think something is the cause then figure out how to confirm it and do that. Instead he spent the day running back and forth between opposite sides of the school even to the point where the two of them actually wondered around the school checking all the smokies. That right there tells you these guys shouldn't be touching this system.
      The moment I saw all those remote modules on that wall I knew wrong labeling was something to watch for. Especially once he'd isolated the suspect module and the fault remained. I would have then isolated the last half of those modules and seen if the fault went away. If it did then the fault was in that last set of modules (about 4 in total). If the fault remained I'd have isolated the first half as well and seen if the fault went away. Either way, isolating one half of them (and if need be the other half) would cut in half the number that then had to be isolated one by one. to find the faulty one. This should have taken them less than an hour.
      I also notice in one of his comments here he's wanting to replace the whole system with a new one thinking somehow that's going to make things better. When in reality this system works perfectly fine, there's nothing wrong with it apart from the occasional defect which all systems of this size have from time to time.
      Guys like this can cost organizations a fortune. Not only in the man hours spent on this due to how he went about it, but also in the money he's encouraging the school to waste putting in a new system to replace one that doesn't need replacing.
      Again, myopia. Just jumping from one rash unsupported conclusion to another. He's blaming the system for the massive amount of time spent finding this fault and hasn't learned a thing. It wasn't the system that caused this massive amount of time to be wasted. It was him.

    • @nics-systems-electric
      @nics-systems-electric  Рік тому

      @@johnrauner2515 I did not jump to any conclusions not once did I say this is the problem for sure part of troubleshooting is you have to look at all possibilities

    • @nics-systems-electric
      @nics-systems-electric  Рік тому

      Checking all of the smoke detectors was not my decision and with something I was asked to do

    • @nics-systems-electric
      @nics-systems-electric  Рік тому

      Also not my decision to replace the system and it does not work fine at all you don't know the history

  • @Lazy2332
    @Lazy2332 3 місяці тому

    4:08 if it’s connected to the network, yes. You would be able to view it on APC SmartConnect on that model. I don’t believe that one allows any other types of monitoring (self monitoring/free).

  • @jayhollowayii2
    @jayhollowayii2 Рік тому +2

    Also nice radio music choice lol 😊

  • @flower3444
    @flower3444 9 місяців тому +1

    Replace the not sounding 439D in the 1964 middle school

  • @hotsoup1001
    @hotsoup1001 Рік тому +1

    @1:30 You can take the boy out of middle school, but not the middle school out of the boy. 🤣

  • @SOU6900
    @SOU6900 Рік тому +2

    Seems about as complicated as a modern diesel pickup 😆

  • @Maelael
    @Maelael Рік тому +1

    A malfunctioning fire alarm is a right pain in the drain. That can cause a panic that can lead to injuries.

  • @Icee-On-YT
    @Icee-On-YT Рік тому +4

    Nice video nick

  • @sharkey086
    @sharkey086 Рік тому +2

    Reminds me of dealing with all the quarks of the fire system at a large museum I worked for. That thing was so temperamental (FCI) and only myself and 2 others knew how to troubleshoot it. Made for some long days and nights.

  • @matthewantonucci6751
    @matthewantonucci6751 Рік тому +1

    Hey Nic, I Would Just Upgrade The Whole System To A Napco Gemini Commercial Combo Burglar/Fire Security System!

    • @nics-systems-electric
      @nics-systems-electric  Рік тому +1

      We do have a quote to replace the system with a real fire alarm system we will be installing a notifier system likely a 320

    • @NyxKemo
      @NyxKemo Рік тому

      Combo panels are illegal in Canada and they’re crap anyway

    • @nics-systems-electric
      @nics-systems-electric  Рік тому

      @@NyxKemo someone finally said it I do agree. They are OK for residential but for commercial get a real System

  • @JoeCdaYT
    @JoeCdaYT Рік тому +1

    As someone who messes with electricity, sensors and a temperamental dodge truck with dash gauges acting up. That one loose wire that popped out as the other guy was messing with it could have caused all the problems you were seeing. Wire is loose and causing a poor connection to the module. When you tightened the screw back down on it, it took the resistance away. That is all it takes to throw those system out of whack. I had been called out on a problem with the system saying there was a trigger at the fryer fire suppression but it did not. All wires had good connections and resistor was in place. All I could suspect was there was a joint in the wire else where and I was not going to hunt it down since I was there to diagnose the Ansul box with the switch inside it. It was the other guys who were the techs of the monitors company that had all the tools needed to locate that problem. Hope this info helps you out in other jobs with fire alarm systems.

  • @tomcoward16
    @tomcoward16 Рік тому +1

    I once was at a boarding school and the alarm went off in the middle of the night. my teacher joked it could be a caterpillar... it turned out to be a caterpillar! walking inside a part of the alarm system. LOL

  • @jayhollowayii2
    @jayhollowayii2 Рік тому

    Hey mate good video love the technology things

  • @davidperry4013
    @davidperry4013 13 днів тому

    EST is junk. If I’m getting a fire alarm system installed in my own property, Simplex-Grinnell or Notifier and System Sensor.

  • @michellebertrand7702
    @michellebertrand7702 6 місяців тому +1

    This is not surprising for EST.

  • @Corvette1658
    @Corvette1658 Рік тому +2

    Well it sounds like they definitely need a new system.

  • @Railfan-Travis7043
    @Railfan-Travis7043 Рік тому +2

    looks like you where very busy

  • @MatthijsvanDuin
    @MatthijsvanDuin Рік тому +1

    12:00 I was a bit confused here how you'd be able to measure the loop resistance while it's in an active measurement circuit... but then you measured 0 Ω and tripped an alarm so I guess that answers that ;-)

  • @YourLocalFireAlarmTech
    @YourLocalFireAlarmTech Рік тому +2

    one little gripe about EST; in alarm or activation, the LEDS should be solid Red like notifier modules instead of blinking. Their smokes do the same thing. That might have helped a bit identifying which module is acting up. Really sucks the labeling was wrong lmao. It's either that or someone put the wrong description??

    • @nics-systems-electric
      @nics-systems-electric  Рік тому +4

      That's what was kind of throwing me off to as I am looking for solid red however we had blinking red for whatever reason I'm not a expert on EST so I'm not sure and yeah the labelling was completely goofed up

    • @YourLocalFireAlarmTech
      @YourLocalFireAlarmTech Рік тому +1

      @@nics-systems-electric Yeah I get ya bro, I'd be looking for solid red as well because I'm so used to Notifier with my company, and Simplex as my hobby systems. I would have been thrown off with y'all lmao. I'm not used to EST either but I'm trying to get into them. I hope they fix that damn labeling

    • @nics-systems-electric
      @nics-systems-electric  Рік тому +3

      @@YourLocalFireAlarmTech yeah the labelling was corrected on Monday when I worked with the EST tech

  • @Emmisullivan14
    @Emmisullivan14 Рік тому +2

    You had to deal with Every Single Trouble plus a dead security system 💀

    • @jrepairman
      @jrepairman Рік тому +1

      lol !!!! Been in the industry 35 years and this is the first time I heard of these. Good one !!! Do you happen to have any other good ones for other brands ?

    • @Emmisullivan14
      @Emmisullivan14 Рік тому

      @@jrepairman mmmmm. Simplex isn't all that simple

  • @TheSimplex4903
    @TheSimplex4903 Рік тому +2

    Get this man his breakfast!

  • @julerobb1
    @julerobb1 Рік тому +5

    Have you tried completely restarting every panel ? As in disconnect power and battery, wait 10 seconds or so and then plug it all back in? Sometimes system reset might not work in my experience

  • @sircampbell1249
    @sircampbell1249 Рік тому +1

    Been in Alarm buzz started in 1979 this was painful 😫 to watch...

  • @Pbell
    @Pbell Рік тому +1

    Yeah man, did commercial fire alarms for many years not doing it anymore but. I want to see some ground fault videos. I was the guy you sent to find the ground fault and I was damn good at finding and repairing them.

  • @stevecraft00
    @stevecraft00 Рік тому +1

    The 3 bells pattern. Is that pretty standard in the usa? I live in the uk and we fit fire angel smoke alarms in houses, they have the same pattern, 3 beeps - most brands just have continuous short beeps. In commercial fire alarms here bells arent normally used - we have sirens or vsrious types - some are a constant sound, some are a "repeating climb" noise. But the rules are the same type must be fitted throughout a building.
    Amazed to see those portable classrooms have sprinklers in them! My school had some portable units but i think the rules for them in the uk are far less strict - sprinklers are required in far less places here.

    • @nics-systems-electric
      @nics-systems-electric  Рік тому +1

      This is Canada depending on the municipality sprinklers are required portables not all of them require it mine does

  • @RobloxTrainspotting
    @RobloxTrainspotting 11 місяців тому +1

    Lol i liked it when you said la la la la la to the man 😂

  • @Twentythree33
    @Twentythree33 6 місяців тому

    Ed Wards Quick Start Fi Re Ala Rm Cont Rol Pan El

  • @dutchwolf2675
    @dutchwolf2675 Рік тому +4

    Great video! How come you said this pullstation doesn’t work? And how did the security system go off and how does the battery drain and the panel shut off when the sirens go off? Keep up the great work.

    • @nics-systems-electric
      @nics-systems-electric  Рік тому +6

      There is a pull station that doesn't work in one of the portables. The security system was set off by the door that is shown a couple times in the girl washroom where the door contact is too far away from the magnet so we had to make an adjustment on Monday. Security system power supplies are tiny and don't put out much power so unlike a fire alarm system when they go into alarm they take power from the battery as well as the normal power supply to get more power for the sirens so if it's going off for hours eventually it will drain the battery

    • @dutchwolf2675
      @dutchwolf2675 Рік тому +1

      @@nics-systems-electricwould you have replaced it?

    • @nics-systems-electric
      @nics-systems-electric  Рік тому +1

      @@dutchwolf2675 can't remember it's been a while since we looked at it

    • @adamcrane1436
      @adamcrane1436 Рік тому +1

      Hello ​@@nics-systems-electric

    • @jrepairman
      @jrepairman Рік тому

      @@nics-systems-electric It should not go on forever as the default bell time out for a DSC system is 4 minute, and if the alarm triggered on the same zone again, the system should ignore the the circuit after swinger shut down.

  • @spectacularhurricanecat
    @spectacularhurricanecat Рік тому +1

    I LOVE this kind of problem solving in IT

  • @Casonplayz
    @Casonplayz Рік тому +1

    Nice video

  • @jennywatts7054
    @jennywatts7054 Рік тому +2

    Hi

  • @EoRdE6
    @EoRdE6 Рік тому

    They really brought out the B team to fix this one lmao 😅

  • @ihasarax
    @ihasarax 4 місяці тому

    who tf was playing kid cudi by playboi carti 😂😂😂 15:43

  • @akshonclip
    @akshonclip Рік тому +1

    The firmware update probably scrambled the module addresses. The bad module is a separate issue.

  • @Sssnipercat1
    @Sssnipercat1 Рік тому +1

    This just shows never trust the labeling, never trust the guy before you

    • @Sssnipercat1
      @Sssnipercat1 Рік тому +2

      Even if the guy before you was you

  • @Rileygee0224
    @Rileygee0224 Рік тому +1

    My 11th or 12th grade year. Our high school alarm system had a bug and for almost an hour ever 2 to 3 minutes after being turned off, the alarm would sound again so the entire system was shut down for the rest of the day.

    • @nics-systems-electric
      @nics-systems-electric  Рік тому +1

      Then they would've had to have someone or multiple people on firewatch until system was back

    • @Rileygee0224
      @Rileygee0224 Рік тому

      @nics-systems-electric there was, but it took nearly a day to figure out the issue. Being a student, they didn't tell me/anyone anything, of course. just a glitch in the system, I guess.

  • @transportfan08
    @transportfan08 Рік тому +1

    Why on earth would they put the intruder alarm keypad in a portable bathroom of all places? Is this normal in America?

  • @dylanreynolds8264
    @dylanreynolds8264 Рік тому +1

    is this the same middle school that had the false alarm back in November of 2022

  • @ChrisTopher284765490
    @ChrisTopher284765490 Рік тому +1

    Hope that low air wasn’t the dry pipe. Hopefully there’s a Pre Action System there also

    • @nics-systems-electric
      @nics-systems-electric  Рік тому +1

      No pre-action system just a wet system in the main building and dry system in the portables as well as the band hall building is a partial dry system the low air trouble is not actually there the panel just comes up with random stuff when it's resetting or has been messed with at all

  • @cbart1987
    @cbart1987 Рік тому +1

    Hey SB head office we found cause of the alarm looks like someone broke in and went Lizzie Borden on the fire PNL

  • @Murphys2ndLaw
    @Murphys2ndLaw Рік тому

    23 years in IT/AV engineering… never, ever assume anything. If you didn’t install and test it yourself. You’ve gotta step back. Get a different perspective and come at it from another angle. Don’t dismiss another colleagues suggestions. Even if you think you’ve ruled it out. Also, we all wanna go home when you get called in off hours. But, you’ve got a job to do. Man up and solve it!

    • @nics-systems-electric
      @nics-systems-electric  Рік тому +1

      Definitely can't assume anything. I would've done less complaining if I was getting paid lol. I thought it would be a quick little call out and a quick fix that I was curious so I thought I would go to it

  • @Jackmawer
    @Jackmawer Рік тому +1

    thanks this was super interesting, i hope the breakfast ended up being worth it 😂

  • @adamcrane6306
    @adamcrane6306 Рік тому +1

    Hello
    NIC’S - SYSTEMS & ELECTRIC

  • @gedeonclavet2946
    @gedeonclavet2946 Місяць тому

    The heck??😂😂 17:01 the background sound

  • @mircomamsecosirensnalarms
    @mircomamsecosirensnalarms Рік тому +1

    hello

  • @Parascuba
    @Parascuba Рік тому +1

    Simple, building is haunted!

  • @ElevatorWasher5000
    @ElevatorWasher5000 4 місяці тому

    Quick Starts have so many faults

  • @brandonkonicki2177
    @brandonkonicki2177 Рік тому +1

    The system should get upgraded to a Fire-Lite ES200X Fire Alarm Addressable Control Panel

    • @nics-systems-electric
      @nics-systems-electric  Рік тому +1

      It would be notifier not firelite we don't have any companies that sell Firelite they are also not very Canadian compatible

    • @Ron2600_
      @Ron2600_ Рік тому

      Put a IO and keep all the Edward's devices.

    • @nics-systems-electric
      @nics-systems-electric  Рік тому

      @@Ron2600_ it will be notifier

  • @TheTechPianoPlayerKid
    @TheTechPianoPlayerKid 8 місяців тому

    The security system sounds like one of those keypads used in a DSC security system.

  • @IanGSully
    @IanGSully Рік тому +3

    My god, that system is a piece of shit! Thank god they decided to replace that awful thing! I hope you do a durability test on it if you take it home! That would be so funny to see that system you hate so much get set on fire and smashed into pieces!!! 😂😂😂

    • @nics-systems-electric
      @nics-systems-electric  Рік тому +1

      It's not replaced yet all we've got is a quote but it will be replaced at some point when we have time so not this summer lol

    • @IanGSully
      @IanGSully Рік тому +1

      @@nics-systems-electric Well, I know you got 2 other systems that are getting replaced this summer, that and the fact that your school district has decided to put old systems over reliably, which is bullshit because this system is anything but reliable, and the 2 systems that you are replacing this summer we’re working perfectly fine no problem!

    • @nics-systems-electric
      @nics-systems-electric  Рік тому +4

      @@IanGSully well yeah one of them working perfectly fine the other one has a permanent ground fault

    • @IanGSully
      @IanGSully Рік тому +1

      @@nics-systems-electric Oh okay.

  • @shanespringate7386
    @shanespringate7386 3 місяці тому

    So exactly what happened at that school

  • @gregbouchard414
    @gregbouchard414 Рік тому

    Hi how are u ok today u do a rally good job on here keep up there good work on here I hop we can be friends at we'll be good too do at let me know

  • @achannelwithnopurpose1977
    @achannelwithnopurpose1977 Рік тому +1

    And that’s why you don’t buy Edwards EST products

    • @johndeerefan725
      @johndeerefan725 Рік тому

      My high school has a EST3 from 2008, and every time I see it, it is always in a normal state with no troubles. And a golf course nearby where I went had a Simplex system that later got replaced by EST

  • @sterlinggarcia9859
    @sterlinggarcia9859 5 місяців тому

    you had this meme sound play in your head when u accidently set off the system. meme sound plays: "OH SH**, NOT GOOD" 🤣. When Jamie said you set off the bells, and the split second u where like....... OOPS MY BAD

  • @TechOne7671
    @TechOne7671 3 місяці тому

    Well done lad, you got there in the end. As an electrician/ security tech for 30 years I have seen it all until tomorrow when a new fault will have to be solved. Some tips for you, when first arriving on-site assess the complete situation, then a plan of action. Do your own detective work, it’s easy to get lost listening to peoples opinion of the issue. When trying to identify a circuit or zone, put a short or fault on it and check panel shows same, this would have identified your mislabelling issue. Although they are probably not mislabelled, some fool has had the lids off and put them on wrong. From the UK, I have not seen that panel but I am sure I could wire and work it no problem😂. Addressable system devices with no dip switches are no good for heat of the moment fault finding. Still, it was a good video and I am glad to see it’s not just me that gets stuff like that. All the best to you.

  • @thethirdrail8397
    @thethirdrail8397 Рік тому

    @ 1:06The flip side to the Sun records 45 of the Gentrys Song "Cinnamon Girl" is " I Just Got The News" My copy is th emono Mix, but There was a stereo if I am not wrong Canadian Mix later released.
    I know 99% of every 45 and Lp in my collection. over 10k 45 rpm records and a few thousand Lps!

  • @nickcliff
    @nickcliff Рік тому +2

    About to eat breakfast and then the fire alarm is going off that’s bad timing

    • @nics-systems-electric
      @nics-systems-electric  Рік тому +1

      That's how it always goes lol

    • @An_Official_Scratcher
      @An_Official_Scratcher Рік тому

      Lol that's nothing like what i had, i had a fire drill right before recess XD

    • @nics-systems-electric
      @nics-systems-electric  Рік тому +2

      @@An_Official_Scratcher that's a drill when you're at school not a big deal but this was a call out from my house on a Saturday that's why I was complaining

  • @Wire_Tech22
    @Wire_Tech22 Рік тому

    Nice video!

  • @gregbouchard414
    @gregbouchard414 Рік тому

    U got a rally good car u do hove a good car u do hove a good car u hove how are u ok today keep up there good work on here

  • @Julianacan
    @Julianacan Рік тому

    I wish i could get paid for this stuff, I would be rich... too bad im a lowly sysadmin

  • @ErnieGamezOfficial
    @ErnieGamezOfficial 3 місяці тому

    24:05 HOTEL CALIFORNIA!

  • @Willamafton104
    @Willamafton104 Рік тому

    Im a chan and i will be one a day 6 so the ,lalalala, made me cringe 😂 so sometimes its loud to me and im 6 years old and i like your vids

  • @Buyer_Pro
    @Buyer_Pro 4 місяці тому

    At my school, one time after a fire grill we went in and then it started going off again. We had to evacuate but they couldn't turn it off. So we get extra time to play We could not get in. We could only stay outside.

  • @Nirujan-f5c
    @Nirujan-f5c 7 місяців тому

    My Friend, In Edwards if you didnt enable in the program disable event to restore to normal, you cant disable input alarm devices while they are in active, short cut way is note down device address and panel and card address and then disconnect SLC wire from panel i mean power down field device and then press reset on the panel now alarm will restore and now disable and then reconnect your SLC back to the panel. now you are good.

  • @elijahisanog5776
    @elijahisanog5776 11 місяців тому +2

    32:24

  • @firealarm421
    @firealarm421 Рік тому

    Was the dialer bypassed as you working on the system

    • @nics-systems-electric
      @nics-systems-electric  Рік тому

      No the procedures here are to call in and put the system on test/disregard

  • @Casonplayz
    @Casonplayz Рік тому +1

    Crazy