Ji ye colling tower ki vidio hamne cleaning ke time banai thi jis vajah se tank me paani kam tha ... Tank me pani cooling tower ki capacity ke hisab se hota hai ... Aor 👉 jo apne dekha is tank me bhi atound 5 hajar liter tak pani aata hai .. aor ye jaldi khatam nahi hota qki ek taraf se water out hota hai to doosri taraf se inlet bhi hota rahta hai .. jis vajah se pani tank me bana rahta hai .. bas apko har 2 ghante me ek baar check karna rahta gai hai
Ye ek tarah ka panal hota hai jise ham DDC panal kahte hai iska full form (direct digital control panal) hota hai ye jaha pe BMS system rahta hai ye wahi par use hota hai। Qki BMS ki poori cable DDC se connect rahti hai aor poori tarah se DC volt pe chalta hai mtlb 12V ya 24v sukriya
Sir colling tower m pani h he kaha ap to dekhai pani tank k jaisa ka ha h wo to sef jo pipe aaya h neche se opar os m he pani h srf baki said m dono trf jali laga hua h or opar fine waha pr to pani nhi reh sakta h to pani aakhir h kaha nhi smhaj aaya 100000 ltr water to jama tnk k trha nhi dekha sir
Thermostat ek actuter ki tarah hi work karta hai 👉jaise ham split ac me room temp.24 digri celcies set karte hai aor jab room ka temp.24 aa jata hai to thermostate compresser ko off kar deta hai ...aor ye evaporater se pahle ya evaporater me hi side me fit kiya jata hai lekin iska sensor jaha pe hame cooling supply deni usi tarf kar dete hai taki wo us area ka temp sens kar sake ....sukriya
Bol dena wet compretion ko resolve kiya hai ye problem tab aati hai jab gas evaporater me vaper nahi ban pati aor wo liqvid form me hi compresser me chali jaati hai jiski vajah se compresser noise karne lagta hai ..ya phit trip bhi ho jayega
Primery pump Ahu ke out let and chiller ka inlet ke beech me lagaya jata hai ....aor secondry pump chiller ke outlet and ahu ke inlet ke beech me lagaya jata hai sukriya
No. 1 answer 👉Apka chiller centryfugal typ hai to surge ayega Check step by step 1. CHECK chiller load (FLA) 2. cooling tower tank water level 3. Cooling tower fan condition 4. Condenser Approch level 5. Chiller plant ke ander ka abient temp And apka CH flow loss alarm tab ayega chahe apka condeser me ho ya phir evaporater me Agar condenser me CH loss aaya to check kare step by step 1. Condenser pump running status 2. Cooling tower water level 3. Condenser water presser 4. Flow switch check kare aap 5. Check inlet and outlet valve open condition 6. release air from condeser line Aor agar evaporater me CH flow loss ayega to 1. Check primery pump running status 2. Primery pump pressure 3. Release air from top AHU
Aap aise samjh lijiye 👉Surge alarm tabhi ayega jab apki gas theek se condensation nahi hogi mtlb vaper se liqvid nahi banegi ....koi doubt ho to jarur batana
sir app bahut Achha se samjate hai 👍👍
Ji bahoot sukriya apka 👍
app kaha se ho..
Nice explained thank u sir
You're most welcome
Bohot acca video banta hai bhai appka carry on....
Bahoot sukriya apka 💐
Thank you ji
Thanks
🌹🌹❤️❤️❤️🌹🌹
Sir BMS work details me ek video bnaye please
Sir ak video vgd and prv and vsd ke upar banaiye please sir🙏
Sir watercooled chiller condenser me gas leak k upper vidio banao
Ji jarur ..hamne ek chiller cycle vidio upload ki hui hai usme bataya hai kaise leak hota hai aor kaise resolved hoga ....sukriya
Nice sir 💯💯💯👌👌👌
Very nice bhai
Bahoot sukriya
Centrifugal chiller me jo lube oil use hota he..
Uska name kiya he?
Polyester short name ( POE )
Water spray Nozzle nahi dikhya apne, wo bhi dikha dain please.
Next time jarur dikhayenge dost aor ache se uske baare me batayenge bhi ।।।👍
Plz thoda smjha dijeay mujhe lgta tha k jaise bada sa tnk hoga opar fan laga hua h water os tnk m jama rehta hoga lekin ye to srf water ki runing h
Ji ye colling tower ki vidio hamne cleaning ke time banai thi jis vajah se tank me paani kam tha ...
Tank me pani cooling tower ki capacity ke hisab se hota hai ... Aor 👉 jo apne dekha is tank me bhi atound 5 hajar liter tak pani aata hai .. aor ye jaldi khatam nahi hota qki ek taraf se water out hota hai to doosri taraf se inlet bhi hota rahta hai .. jis vajah se pani tank me bana rahta hai .. bas apko har 2 ghante me ek baar check karna rahta gai hai
Sir,
App bohut ache ache video banate ho..
2 week ke bad video bana raheho..
Bahot late video banaya sir😢
Sorry but jyada hi busy ho gaya tah
Okay sir..
Sir HVAC chiller plant ki achi achi videos banaya please
Sir ddc kya hota hai kaise kaam karta hai. Full details bataiye na.
Ye ek tarah ka panal hota hai jise ham DDC panal kahte hai iska full form (direct digital control panal) hota hai ye jaha pe BMS system rahta hai ye wahi par use hota hai।
Qki BMS ki poori cable DDC se connect rahti hai aor poori tarah se DC volt pe chalta hai mtlb 12V ya 24v sukriya
Bhaiya ji chiller keya keya par trip mrta Hai or kon sa alarm ata Hai or MTLB keya hota alarm ka uspe video banaiye na Plz Sir ji 🙏
Ji hamne apke topic par vidio already upload ki hui hai ...aap link pe dekh sakte hai ...konsa alram kaise resolved kare sab kuch hai ...sukriya
Actuvater working bataye our types
Ji hamne actueter ki alag se vidio upload ki hui aap link pe dekh sakte hai sukriya
Chillar 3way valved us
Sir colling tower m pani h he kaha ap to dekhai pani tank k jaisa ka ha h wo to sef jo pipe aaya h neche se opar os m he pani h srf baki said m dono trf jali laga hua h or opar fine waha pr to pani nhi reh sakta h to pani aakhir h kaha nhi smhaj aaya 100000 ltr water to jama tnk k trha nhi dekha sir
Pani tank me hi hota hai .. baki kahi nahi
Sir.. cooling tower ki ... safety kya kya hoti hai .. please reply????
1 . water parameters
2. proper air flow
3. fan condition
@@c4chiller9984 Thank you sir♥️
Sir chiller ka Delta T jayada ho rha hai tb hame kya krna padega
Check chiller load
Bhai Kaha ho koi video nai uploaded kr rahi ap muji
Ji jarur upload karenge
But thoda busy jyada ho gaye the
Please explain what is thermostat. And where it is located in refrigeration cycle diagram. And why it is fixed at that location only
Thermostat ek actuter ki tarah hi work karta hai 👉jaise ham split ac me room temp.24 digri celcies set karte hai aor jab room ka temp.24 aa jata hai to thermostate compresser ko off kar deta hai ...aor ye evaporater se pahle ya evaporater me hi side me fit kiya jata hai
lekin iska sensor jaha pe hame cooling supply deni usi tarf kar dete hai taki wo us area ka temp sens kar sake ....sukriya
Sir,
App bahot din video keu nehi bana raheho😢
Thoda kaam jyada ho gaya tha ji abhi jaldi ayegi vidio
Sir hvac mein major problem kya aati hai ?
Interview mein yeh sawal pucha tha ke hvac mein aap ne kaunsa major problem solve kiya hai ?
Bol dena wet compretion ko resolve kiya hai ye problem tab aati hai jab gas evaporater me vaper nahi ban pati aor wo liqvid form me hi compresser me chali jaati hai jiski vajah se compresser noise karne lagta hai ..ya phit trip bhi ho jayega
So nice sir
( 1 ) Oil Level Switch
( Alarm ) Plz sir Solution
🙏
Ji next vidio will coming in you topic 👍
Sir cooling tower ki capacity kitne ton ki hoti hai agar hamara chiller 60 ton ka hai
20% extra hogi chiller se jaise ki apka chiller 60 tr ka hai to cooling tower 72 se 80 tr ke beech me lagega 👍
@@c4chiller9984 thanks sir
@@c4chiller9984 60tr ke chiller me GPM kitna hoga tower ka
60×3 = 180 GPM
@@c4chiller9984 thanku so much
Mai Job Dhundh Raha Hu aapke Pass Ya Or Kahi PR Vacancy Ho To Bataiye Sir.
Mai Bahut Paresan hu.
Abhi Mai Mumbai Me Hu
Nokri .com pe cv upload kr dijiye vacancy mil jayegi ji
I need job in Dubai?
Mil jayegi sir
Naukari, Apna, indeed,Hirect Sare PR Search Kar Raha Hu Sir Kahi Se Call Nahi AA Raha Hai
HVAV Me Kahi Batao Sir
Primary pump kaha hota hai between cooling tower outlet to condensor inlet?
Primery pump ahu and chiller ke beech me lagaya jata hai
Primery pump Ahu ke out let and chiller ka inlet ke beech me lagaya jata hai ....aor secondry pump chiller ke outlet and ahu ke inlet ke beech me lagaya jata hai sukriya
Cooling tower aur condensor k beach me jo pump hota hai usko Condensor water pump kehty hai?
Love you sir...
You better clear this question..
Ji ha bilkul 👍
condenser pump kahte hai use
( 1 ) surge high section superheet_ running
( 2 ) CW Flow Loss
CW Flow Loss alram baar Baar ata hai Plz Sir helf
No. 1 answer 👉Apka chiller centryfugal typ hai to surge ayega
Check step by step
1. CHECK chiller load (FLA)
2. cooling tower tank water level
3. Cooling tower fan condition
4. Condenser Approch level
5. Chiller plant ke ander ka abient temp
And apka CH flow loss alarm tab ayega chahe apka condeser me ho ya phir evaporater me
Agar condenser me CH loss aaya to check kare step by step
1. Condenser pump running status
2. Cooling tower water level
3. Condenser water presser
4. Flow switch check kare aap
5. Check inlet and outlet valve open condition
6. release air from condeser line
Aor agar evaporater me CH flow loss ayega to
1. Check primery pump running status
2. Primery pump pressure
3. Release air from top AHU
Aap aise samjh lijiye 👉Surge alarm tabhi ayega jab apki gas theek se condensation nahi hogi mtlb vaper se liqvid nahi banegi ....koi doubt ho to jarur batana
@@c4chiller9984 nice explain sir❤️
CW flow ka full form kiya he sir?
@@sintudas1828 bahoot sukriya apka 🙏