How Trane Screw Chillers Loaders Work

Поділитися
Вставка
  • Опубліковано 7 жов 2024
  • Walking through the sequence for Trane screw compressors CHH loading and unloading function.
    Houston Hermetics
    jake@houstonhermetics.com
    Get 8% off at TruTech Tools with promo HVACTIME
    www.trutechtoo...
    Get tech support, training, and the Tech Blog at hvactimetx.com
    You can contact me at Hvactimetx@gmail.com
    Support my COFFEE problem through,
    venmo.com/code...

КОМЕНТАРІ • 43

  • @dfwhvac
    @dfwhvac Рік тому +8

    Great Video and explanation. You’re my UA-cam chiller icon lol😂

  • @edwardcrane7520
    @edwardcrane7520 19 днів тому

    Excellent job 👍👍👍

  • @tommycollett9584
    @tommycollett9584 Рік тому +3

    Great video your a legend learning more and more every time you post thank you 🙌🏻

  • @robertmason4334
    @robertmason4334 3 дні тому

    Thx for this video!

  • @hvacguy11
    @hvacguy11 Рік тому +1

    You’re an Hvac legend

  • @JUANM896
    @JUANM896 Рік тому

    Thanks bro
    Really thank you for sharing your knowledge.

  • @robertrichardson5026
    @robertrichardson5026 Рік тому

    Learned something new, great video.

  • @DerbyDogz
    @DerbyDogz Рік тому

    We deal with American Hermetics pretty often out of Tennessee. Agreed they are awesome to deal with.

    • @HVACTIME
      @HVACTIME  Рік тому +1

      Good people

    • @AhmedAli-po5xi
      @AhmedAli-po5xi Рік тому

      @@HVACTIME Dear hvac expert from long time i am watching your following to you.I am from pakistan.i am facing one problem in my yciv chiller.this chiller have to to systems.chiller was running normal but i recive complaints chiller trip both system same time trip due to low suction alarms.We changes steppers controller and new mother board.water flow also also ok in cooler suction tranduser also replaced.Share your advice.thanks for repling.

  • @REFEREEMOUSE
    @REFEREEMOUSE Рік тому

    Love the explanation!

  • @greglawson740
    @greglawson740 3 місяці тому

    I know this is an older video but i need help. You have the most comprehensive videos on the Trane Chillers. Could you please put out a video or even a "short" on how to switch between pumps for like doing PM's

    • @HVACTIME
      @HVACTIME  3 місяці тому

      You can get direct support in the chiller community when enrolled at chilleracademy.com.

  • @zekenzy6486
    @zekenzy6486 Рік тому

    Great Video. Thank you for sharing

  • @sh6323
    @sh6323 7 місяців тому

    awesome video brother

  • @ulisessalas4731
    @ulisessalas4731 11 місяців тому

    Excelente.... saludos desde Venezuela

  • @vickygalanis4965
    @vickygalanis4965 Рік тому

    THANK YOU🎉

  • @thesilentonevictor
    @thesilentonevictor Рік тому

    Great video

  • @jonnymac31
    @jonnymac31 Рік тому

    Sweet, man.

  • @Patrick-hq7sq
    @Patrick-hq7sq Рік тому

    I like to use my amp clamp on solenoids to check .

  • @Md.TausikHasan
    @Md.TausikHasan Рік тому

    Please need your all video with English subtitles.

  • @kehindefatai3830
    @kehindefatai3830 6 місяців тому

    Trane chiller showing no data communication after resetting the system come up but only one compressor runs while the second refuse to run and keep showing high pressure cut out and the system goes down after 10min showing no data communication what can be the problem

  • @fkdeazevedo
    @fkdeazevedo Рік тому

    During unloading or on startup what should the oil pressure be on a rtaa and rtud? And during normal operation while it's maintaining what should the oil pressures be.

    • @MelonBopper
      @MelonBopper 2 місяці тому

      Most R series chillers run at 35psid on the oil system for proper oil flow. Trip point at 50psid

  • @Covercash1982
    @Covercash1982 9 місяців тому

    So i have a bad compressor on one of these chillers. I have no room for a fork lift and have no clue how to get the old one out and new one in.You got any ideas?

    • @HVACTIME
      @HVACTIME  9 місяців тому

      I've always used skid plates and rigging equipment with a gantry

  • @HVACRTECH-83
    @HVACRTECH-83 Рік тому

    We are getting 2 new trane chillers with screws next summer, long waiting list, going to be a hot summer at this school this year. But my question is, is there any classes you know of I can attend to learn up on these screw compressors? I've never worked on one and would really love to become more familiar. I doubt trane offers anything, they don't want us to learn their equipment, main reason why I hate trane, there's other reasons though of course

  • @Practicing_HVACR
    @Practicing_HVACR Рік тому

    At 3:20 you said that during shut down the female unloader is deenergized. Is that correct? Or is the female unloader energized?

    • @Practicing_HVACR
      @Practicing_HVACR Рік тому

      Noticed that you repeated it at 3:42 and 3:51 but at the start you said the unloader was energized. Seems like you mixed up the words?

    • @Practicing_HVACR
      @Practicing_HVACR Рік тому

      Was reading through the RTAA IOM to study this further and noticed it says. “The female unloader valve is the first stage of loading after the compressor starts and the last stage of unloading before the compressor shuts down.”
      Appreciate your videos, I don’t know about any other channels that make quality large tonnage HVAC videos like yours. I mostly work on under 100 tons so I’ll dabble with this equipment occasionally. It’s good to be able to see the equipment to supplement the studying I’m doing in manuals and other resources.

    • @Practicing_HVACR
      @Practicing_HVACR Рік тому

      Looks like I found the other answer in the manual. Kind of odd that energizing the unloader valves loads the compressor and vice versa. You would think it should be called a female loader valve.
      “The female unloader valve solenoid receives a constant signal from the UCM, based on system cooling requirements. To load the compressor, the female unloader valve solenoid is energized and discharge pressure is passed through the normally-closed port and into the cylinder. This pushes the female unloader valve closed.
      To unload the compressor, the female unloader valve solenoid is de-energized and the discharge pressure is relieved to the suction of the compressor. The female unloader valve retracts into the cylinder and the compressor is unloaded.”

    • @HVACTIME
      @HVACTIME  Рік тому +2

      Yes the female unloader gets denergize as a final step before shutdown. So when loading starts it gets energized and stays energized until shutdown.

  • @mikelazzari503
    @mikelazzari503 Рік тому

    Do you work for Trane? Just wondering how you would plug into there newer chillers without the proprietary software?

    • @HVACTIME
      @HVACTIME  Рік тому

      I have the software license. I don't work for Trane though.

    • @Eighty8Fitter
      @Eighty8Fitter 5 місяців тому

      You don’t need proprietary software for Trane nor a license

    • @MelonBopper
      @MelonBopper 2 місяці тому

      You cannot plug into a trane system without the software. Tech View for any Dynaview systems and Tracer TU for any UC or Symbio systems. But the licenses need to be purchased for the software.

  • @Cloudstrafie
    @Cloudstrafie Рік тому

    Tried the app says it's for older android :/

    • @HVACTIME
      @HVACTIME  Рік тому

      Thats weird, there should be a current version

  • @SoutheastHVAC
    @SoutheastHVAC Рік тому +3

    So many words in 6 minutes

  • @calex9398
    @calex9398 Рік тому +1

    🤯lol 👍😅

    • @AhmedAli-po5xi
      @AhmedAli-po5xi Рік тому

      In my job location i have facing on problem with chiller of yciv 2 system model.chiller was in normal operations but now a day's chiller going low suction trip same time both system going low suction trip.i changed stepper controller and motherboard also with new one but same issue.after start both systems of chiller goes low suction trip.need help to rectify