Hi... All ISI cables have standard quality features. then check price in store near your place. Only thing you have to take care while buying, buy from authorized dealer only because there are duplicates of good company cable available in marker.. Thanks... keep supporting... Stay subscribed with bell button and like and share this video to friends and family.
Nice explanation 👍 Oru group of motor feeders inu vendiyulla panel inte main incomer breaker, athinu vendiyulla cable sizing ine kurichu oru video cheyyamo? Ithinte oru explanation NEC (nfpa70) il und, but ithinu corresponding oru code iec/is (specifically 60947) il ninnu infer cheyyan saadhichilla.
Hi For single phase/Three Phase I planned to fix switch gear following pattern Isolater 63A + DP MCB 40 Changaeover kseb / Generator ( Emergency)+ RCBO AC /DC Pulsating type I need your help, possible Explain
give 2 isolator for each kseb and generator supply, then change over MCB. if you are giving change over MCB, then no need of RCBO. you can use RCCB. if you are using changeover isolator without tripping ... you can use RCBO.... RCBO is RCCB and Overload...MCB will provide Overload
Good answer... keep watching for complete answer in detail. Thanks... keep supporting... Stay subscribed with bell button and like and share this video to friends and family.
Good answer... keep watching for complete answer in detail. Thanks... keep supporting... Stay subscribed with bell button and like and share this video to friends and family.
എന്റെ വീട്ടിൽ സിംഗിൾ ഫേസ് ആണ്. Elcb യും mcb യും ഉണ്ട്. Elcb ഇടയ്ക് ഇടയ്ക് ട്രിപ്പവുന്നു. പഴയത് മാറി പുതിയത് വെച്ചിട്ടും അൽപ സമയത്തിനകം elcb ട്രിപ്പ് ആവുന്നു. ഇത് എന്ത് കൊണ്ടാണെന്നു വിശ്ദീകരിക്കാമോ
എല്ലാ എം സി ബി യും ഓഫാക്കി ഓരോന്നായി ഓണാക്കി നോക്കുക ഫെയിസും എർത്തുമാണെങ്കിൽ ഏതെങ്കിലും ഏതെങ്കിലും ഒന്നു ഓണക്കുമ്പോൾ ഇ എൽ സി ബി ട്രിപ്പ്പാകും ആയില്ലെങ്കിൽ ഓരോ ന്യൂട്രൽ ആയി ചെക്ക് ചെയ്യുക അപ്പോൾ അറിയാൻ പറ്റും
എന്റെ വീട്ടിൽ മെയിൻ സ്വിച്ചിന്റെ ലിവറിലെ ഇൻസുലേഷൻ കരിഞ്ഞു ബോഡിയുമായി ഷോർട്ട് ആയി.വീട്ടിൽ പല സ്ഥലത്തും ചെറിയ ഷോക്ക് ഉണ്ടായിരുന്നു.എന്നാൽ മൂന്നാം ദിവസമാണ് തകരാൻ കണ്ടെത്തിയത്, അപ്പോഴേക്കും 157 യൂണിറ്റ് പോയിരുന്നു.ഇപ്പോൾ ഐസൊലേറ്റർ ആണ് വെച്ചിരിക്കുന്നത്.Kitkat fuse വേറെയും വെച്ചിട്ടുണ്ട്.ഇനിയെന്തെങ്കിലും ചെയ്യാൻ ഉണ്ടോ?
Earth clear ആണോ എന്നു നോക്കുക, isolator il Earth connection illa, വേറെ Earth അടിച്ചിട്ടുണ്ടോ എന്ന് നോക്കുക..kitkat fuse മാറ്റി MCB വയ്ക്കുക..അതാണ് better.
ഒരു സോളാർ ഇൻവെർട്ടർ വയ്ക്കുമ്പോൾ ഇടിമിന്നലിൽ നിന്നും MPPT ,ഇൻവെർട്ടർ എന്നിവയെ സംരക്ഷിക്കുവാൻ വേണ്ട ബ്രേക്കർ ഏതാണ് .... പാനലിൽ നിന്നും വരുന്ന D.C വോൾട്ടിനെ MPPT ക്ക് മുൻപായി ഒരു ബ്രേക്കർ വയ്ക്കണം ....അതുപോലെ ഇൻവെർട്ടർ INPUT . A.C വോൾട്ടിനും ഒരു ബ്രേക്കർ വയ്ക്കണം ....MCB പോലുള്ള ബ്രേക്കർ ആണോ നല്ലത് ....(പാനൽ 24V ,450W , ഇൻവെർട്ടർ 1350VA ) ബ്രേക്കറിന്റെ AMP ,ഉദ്ദേശ്യം വില എന്നിവ അറിയുവാൻ താല്പര്യം ഉണ്ട് ....
എന്റൈ വീടിന്റെ കോൺക്രീറ്റ് കഴിഞ്ഞു ഇനി വയറിങ് നു പൈപ്പ് ഇടണം. ഒരു വയറിങ് drawing ഇല്ല. അതു ഉണ്ടാക്കിയിട്ടു മാത്രം chyunatale നല്ലതു . ഇതിന് ആരെ സമീപിക്കണമ് ഏകദേശമ 1100sqft ഉണ്ട്.
You can Contact any electrical consultant near your home. If you are interested and have proper as-build plan for your house, you also call our office +918606472279
Nice explanation 👍 👍 👍
ഞാനും നിങ്ങളുടെ വീഡിയോകൾ കാണാറുണ്ട് നല്ല അവതരണം ആണ് വളരെ ഉപകാരപ്രദമാണ് കൂടാതെ ഒരു ചെറിയ ഇലക്ട്രീഷ്യനും ആണ് നമ്മുടെ വീഡിയോകളും കണ്ട് സപ്പോർട്ട് ചെയ്യുക
ok.. sure.. all the best
നല്ല അവതരണം മനസിലാകാൻ എളുപ്പം
താങ്കൾ ഒരു ആധ്യാപകൻ ആകുകയാണെങ്കിൽ ആ വിദ്യാർത്ഥികളുടെ ഭാഗ്യം....
Rccb main swich aeeuse cheyyamo
Nice explanation
Very useful video. Kudos
Spd ye kurich oru vivaranam pratheekshikkunnu
Pleas suggested good house wiring cable
Hi... All ISI cables have standard quality features. then check price in store near your place.
Only thing you have to take care while buying, buy from authorized dealer only because there are duplicates of good company cable available in marker..
Thanks... keep supporting...
Stay subscribed with bell button and like and share this video to friends and family.
കിടിലൻ വീഡിയോ 🥰🥰
😜😜
X😊😊
,,😊
X
, 😊😊😊😊😊😊😊😊😊😊😊😊😊😊😊😊😊😊😊😊😊😊😊😊😊😊😊😊😊😊😊😊😊😊😊😊😊😊😊😊😊😊😊😊😊😊😊😊😊😊😊😊😊😊😊😊😊😊😊😊😊😊😊😊😊😊😊😊
Oru sadarana vitil Rccb munb vekunna mcb yethra 40a ano atho 32a ano vekkandath
So informative
Oru mcbyi l etra lod kollum, motor hp enninanan hp kudiya motor upayogikkunnand, ac one ten, edoke ulkollichoru video cheyyumo
Earth leakagum short current um ekadesham onnano
Thanks
Welcome... keep supporting...
Stay subscribed with bell button and like and share this video to friends and family.
Thanks.........
Ee mixi use cheyyumbo bulb ittinenkil bulb cheruthayi minni kathunnu ath enth konda?
It may be due small induced voltage in phase or small residual voltage in common neutral point
@@shishiram ഇതു പൂർണമായിട്ടു മാറ്റാൻ സാധിക്കുമോ
Whether old type CutOut Fuse is a must for obtaining KSEB 3PHASE CONNECTION.
മെയിൻ സ്വിച്ചന് പകരം എംസിബി ഉപയോഗിക്കാമോ
Great info.
Sir njangalude വീട്ടിലെ fanukalum light kalum pettannu കേടാകുന്നു എന്തുകൊണ്ടായിരിക്കും അത് സംഭവിക്കുന്നത്. ഒന്ന് പറഞ്ഞ് തരുമോ
9 ampire output തരുന്ന 375w സോളാർ പാനലിന് എത്ര ampire Dc mcb ഉപയോഗിക്കാം.....
Nice explanation 👍
Oru group of motor feeders inu vendiyulla panel inte main incomer breaker, athinu vendiyulla cable sizing ine kurichu oru video cheyyamo?
Ithinte oru explanation NEC (nfpa70) il und, but ithinu corresponding oru code iec/is (specifically 60947) il ninnu infer cheyyan saadhichilla.
ലിവർ ബാറിന്റെ ഇൻസുലേഷൻ മെൽറ്റ് ആയാൽ
Meter fuse matti mcb vekammo
സർ മൈൻസുച്ചിലെ ട്രമിനൽ ഹിറ്റാകുമ്പോൾ കരിജൂപോകുമ്പോൾ എർത്തേയ്ക്കുട്ടിയിലാക് ഇറങുമ്പോൾ
ന്യൂട്രലും എർത്തും ഷോർട്ട് ചെയ്താൽ ELCB ട്രിപ് ആ കുമൊ?
ആകാതിരുന്നാൽ ELCB കംപ്ലെയിന്റാണോ?
Yes
Hi
For single phase/Three Phase
I planned to fix switch gear following pattern
Isolater 63A + DP MCB 40 Changaeover kseb / Generator ( Emergency)+ RCBO AC /DC Pulsating type
I need your help, possible Explain
give 2 isolator for each kseb and generator supply, then change over MCB. if you are giving change over MCB, then no need of RCBO. you can use RCCB. if you are using changeover isolator without tripping ... you can use RCBO....
RCBO is RCCB and Overload...MCB will provide Overload
@@shishiram
I Thank you
👍👍👍
Thanks... keep supporting...
Stay subscribed with bell button and like and share this video to friends and family.
Mcb ethra A aaam fuse aayi use cheyendath
Athum eth type mcb aaan use cheyyendath
B or C
Meter boxil fusin pakar mcb vekkaan patto
ഒരു വീട്ടിൽ 3 ഫേസ് വയറിംഗ് ചെയ്യുമ്പോൾ എന്തൊക്കെ materials വേണം etc mcb, rccb with rating
All depends on Load connected...
@@shishiram housing wire recommend ചെയ്യാമോ
Main switchnu പകരം elcb വെക്കുന്നത് നല്ലത്
സ്വിച് ലിവർ ബാറിന്റെ ഇൻസുലേഷൻ മേൽറ്റായാൽ
Good answer... keep watching for complete answer in detail.
Thanks... keep supporting...
Stay subscribed with bell button and like and share this video to friends and family.
അങ്ങനെ എംസിബി വെക്കുകയാണെങ്കിൽ അത് എത്ര യുടെ തായിരിക്കും അനുയോജ്യം ആയിട്ടുള്ളത്
Fuse carriers complaints& insulation leakage
Good answer... keep watching for complete answer in detail.
Thanks... keep supporting...
Stay subscribed with bell button and like and share this video to friends and family.
planning to Replace Old Fuse units with MCB. DP MCB is required along with other single MCB units ?
Meter Box ൽ വച്ചിരിക്കുന്ന ഫ്യൂസ് ന് പകരം MCB വെക്കാൻ KSEB അനുവദിക്കുമോ
Pattum Facebook update undu
@@shajuvk6096 ലിങ്ക് അയച്ചു തരാമോ please
💞
Thanks keep watching and supporting our channel by like, share and comments..
Hi sir
Hello.... Keep supporting our channel by like and share to friends and family..
How to fix spd, where we can fix, spd earthing can connect normal house wiring earthing
👍
Thanks... keep supporting...
Stay subscribed with bell button and like and share this video to friends and family.
@@shishiram already subscribed 👍
ഒരു സംശയം earth connect ചെയ്യാത്ത ഒരു iron boxil നിന്നും ഒരാൾക്ക് ഷോക്ക് ഏൽക്കുകയാണെങ്കിൽ അവിടെ RCCB ( 30 mA)
Trip ആവില്ലേ...!
I mean earth leakage...
എന്റെ വീട്ടിൽ സിംഗിൾ ഫേസ് ആണ്. Elcb യും mcb യും ഉണ്ട്. Elcb ഇടയ്ക് ഇടയ്ക് ട്രിപ്പവുന്നു. പഴയത് മാറി പുതിയത് വെച്ചിട്ടും അൽപ സമയത്തിനകം elcb ട്രിപ്പ് ആവുന്നു. ഇത് എന്ത് കൊണ്ടാണെന്നു വിശ്ദീകരിക്കാമോ
എല്ലാ എം സി ബി യും ഓഫാക്കി ഓരോന്നായി ഓണാക്കി നോക്കുക ഫെയിസും എർത്തുമാണെങ്കിൽ ഏതെങ്കിലും ഏതെങ്കിലും ഒന്നു ഓണക്കുമ്പോൾ ഇ എൽ സി ബി ട്രിപ്പ്പാകും ആയില്ലെങ്കിൽ ഓരോ ന്യൂട്രൽ ആയി ചെക്ക് ചെയ്യുക അപ്പോൾ അറിയാൻ പറ്റും
എന്റെ വീട്ടിൽ മെയിൻ സ്വിച്ചിന്റെ ലിവറിലെ ഇൻസുലേഷൻ കരിഞ്ഞു ബോഡിയുമായി ഷോർട്ട് ആയി.വീട്ടിൽ പല സ്ഥലത്തും ചെറിയ ഷോക്ക് ഉണ്ടായിരുന്നു.എന്നാൽ മൂന്നാം ദിവസമാണ് തകരാൻ കണ്ടെത്തിയത്, അപ്പോഴേക്കും 157 യൂണിറ്റ് പോയിരുന്നു.ഇപ്പോൾ ഐസൊലേറ്റർ ആണ് വെച്ചിരിക്കുന്നത്.Kitkat fuse വേറെയും വെച്ചിട്ടുണ്ട്.ഇനിയെന്തെങ്കിലും ചെയ്യാൻ ഉണ്ടോ?
Earth clear ആണോ എന്നു നോക്കുക, isolator il Earth connection illa, വേറെ Earth അടിച്ചിട്ടുണ്ടോ എന്ന് നോക്കുക..kitkat fuse മാറ്റി MCB വയ്ക്കുക..അതാണ് better.
ഒരു സോളാർ ഇൻവെർട്ടർ വയ്ക്കുമ്പോൾ ഇടിമിന്നലിൽ നിന്നും MPPT ,ഇൻവെർട്ടർ എന്നിവയെ സംരക്ഷിക്കുവാൻ വേണ്ട ബ്രേക്കർ ഏതാണ് .... പാനലിൽ നിന്നും വരുന്ന D.C വോൾട്ടിനെ MPPT ക്ക് മുൻപായി ഒരു ബ്രേക്കർ വയ്ക്കണം ....അതുപോലെ ഇൻവെർട്ടർ INPUT . A.C വോൾട്ടിനും ഒരു ബ്രേക്കർ വയ്ക്കണം ....MCB പോലുള്ള ബ്രേക്കർ ആണോ നല്ലത് ....(പാനൽ 24V ,450W , ഇൻവെർട്ടർ 1350VA ) ബ്രേക്കറിന്റെ AMP ,ഉദ്ദേശ്യം വില എന്നിവ അറിയുവാൻ താല്പര്യം ഉണ്ട് ....
Due to insulation break
For detailed full answer
Stay subscribed with bell button pressed to all..
Also like and share this video to friends and family..
Cut out ഫ്യൂസിന് പകരം mcb vechu kode
ഇപ്പോൾ RCCBO. ഉണ്ടല്ലോ
Yes but normally in India it isolator, RCCB and MCB in DBs
Moving contact rod
Ac polarity agana marunnu
ബ്രെക്ക് ആവുന്നതും അവത്തതും സിംപിൾ നോക്കി എങ്ങനെ മനസ്സിലാക്കും ഐ സൊലേറ്ററും ബ്രെകേറും എങ്ങനെ മനസ്സിലാവും
്് മൊടോറിൻറ,കോയിൽ, ചൂട് ആയാൽ,ഡിപപി,സുച്,ടൃപ്പ്, അടിക്കുന്ന എങ്ങനെ
മൈക്ക insulator കത്തിപ്പോയി മെയിൻ സ്വിച്ച് ന്റെ ബോഡിയിൽ വൈദ്യുതി പ്രവഹിക്കുന്നു
10 mlഅംബിയറും വരുന്നു സിംഗിൾ ഫേസ് അതായത് ജാഖൂസിക്ക് വക്കുന്നത്
ലൂസ് കണക്ഷൻ വഴി മെയിൻ സ്വിച്ചിൻ്റെ ലിങ്ക് ചൂടായി ഇൻസുലേഷൻ കരിഞ്ഞു പോയി ബോഡിയിൽ ലീക്കാവുന്നു .
എന്റൈ വീടിന്റെ കോൺക്രീറ്റ് കഴിഞ്ഞു ഇനി വയറിങ് നു പൈപ്പ് ഇടണം. ഒരു വയറിങ് drawing ഇല്ല. അതു ഉണ്ടാക്കിയിട്ടു മാത്രം chyunatale നല്ലതു . ഇതിന് ആരെ സമീപിക്കണമ് ഏകദേശമ 1100sqft ഉണ്ട്.
concreate നു മുൻപ് ആയിരുന്നെങ്കിൽ ചുവരിലൂടെയുള്ള pipeing കുറയ്ക്കമായിരുന്നു
You can Contact any electrical consultant near your home.
If you are interested and have proper as-build plan for your house, you also call our office +918606472279
Yes planning is always better to do in initial phase, but better late than never...
MCB earth leakage detect cheyyumo
No. Mcb is a normal overload tripper. Only ELCB or RCCB detects earth leakage