Primary Secondary Chilled Water System Working | BMS Training 2021

Поділитися
Вставка
  • Опубліковано 1 жов 2024
  • Limited Time Offer: If you find my videos useful, please check out my BMS fundamentals course on Udemy. Get it for discounted price of only 12.99$ using the below link:
    www.udemy.com/...
    . . . . . . .
    . Primary Secondary Chilled Water System consists of Primary Loop and Secondary loop. The Primary Loop consist of constant speed primary chilled Water Pumps while the Secondary Loop consists of variable speed secondary chilled water pumps. Primary and Secondary loops in a primary-secondary chilled water system are separated by a decoupler or bypass line.
    A differential pressure transmitter is used to control the speed of the secondary chilled water system.
    We discussed in detailed the working/sequence of operation of the primary-secondary chilled water system. We also discussed the causes and effects of low delta T Syndrome.
    -------------------------------LINKS--------------------------------------
    Constant Primary Flow Chilled Water System Video:
    • Chilled Water System W...
    Selection of Valves and Actuators Video:
    • Control Valve Selectio...
    -----------------------------------------------------------------------------------
    Primary Secondary Chilled Water System
    Primary Secondary Chilled Water System Working
    Primary Secondary Chilled Water System SOP
    Primary Secondary Chilled Water System Sequence of Operation
    Primary Secondary Chilled Water Loop
    Primary Secondary Chilled Water System decoupler
    Primary Secondary Chilled Water Pump System
    Constant Primary Variable Secondary Chilled Water
    Primary Secondary Chiller Loop
    Primary Secondary Chiller Water Loop
    Primary Secondary Chiller
    primary secondary chiller piping diagram
    What is HVAC?
    HVAC
    HVAC Systems
    HVAC Training
    HVAC Course
    Basics of HVAC
    Constant Primary Chilled Water System
    Primary Secondary Chilled Water System
    Chiller Plant Working Animation
    Chilled Water Plant Working
    Chiller Plant SOP
    Chiller Plant Sequence of Operation
    Chilled Water System how it works
    Chiller System
    hvac system
    york chiller
    building management system for HVAC
    BMS Training
    Building Management System Training
    Basics of Building Controls
    Please subscribe to our UA-cam channel for BMS training videos.
    Follow us on Facebook at / tech-systems-106092281...
    #Chilled_Water_System #BMS #HVAC

КОМЕНТАРІ • 82

  • @TechSystems
    @TechSystems  10 місяців тому

    *Transform Your BMS Skills!* 🌟 Enjoying my videos? Dive deeper with my BMS Fundamentals course on Udemy. For a limited time, it's available for only $12.99! Don't miss out - click the link below to enroll now.
    www.udemy.com/course/bms_fundamentals/?couponCode=00C2887F1B3E637FCAB9

  • @TechSystems
    @TechSystems  3 роки тому +4

    If you find this video useful please *"Like"* this video. Also, do *"Subscribe"* to the channel and turn ON notifications to get new useful videos about BMS and HVAC.

  • @khaleelahmedshaik7857
    @khaleelahmedshaik7857 8 місяців тому +1

    Sir your videos are good and provide precise information..please can you provide the control system of the chilled water district cooling on the building side..not on the district cooling provider side

  • @libinpaulose1057
    @libinpaulose1057 2 роки тому +2

    Thanks for the detailed explanations.

  • @AKARSH696
    @AKARSH696 2 роки тому +1

    ❣️

  • @vnesmuonnam
    @vnesmuonnam 3 місяці тому +1

    Thank you. Really detail.

  • @haseebbteibet1756
    @haseebbteibet1756 7 місяців тому +2

    Great video

  • @MrSadashiva
    @MrSadashiva 3 дні тому

    Nicely explained!

  • @ddfdae
    @ddfdae Рік тому +1

    Question, does the command to start the chiller system come when a cooling/heating load is required in the building? For example, a thermostat temperature detects a higher temperature than the setpoint, this causes the actuator valves to open in the AHUs/FCU which then initiates the chiller start command?

    • @TechSystems
      @TechSystems  Рік тому

      Salam Abdulrahman,
      Chiller plant is serving a large number of AHUs/FCUs and chiller start/stop command depends on the cooling load and different strategies are used. For example in constant primary CHWS chillers are commanded to start/stop based on return water temperature from the building, in primary secondary system building cooling load is usually determined by the flow in the decoupler so chillers are controlled based on that. For further details you can watch chillers related videos on my channel.

  • @muhammadtahir8635
    @muhammadtahir8635 9 місяців тому +1

    Great explanation
    Kindly explain, how to set accurate set point for differential pressure?

    • @TechSystems
      @TechSystems  9 місяців тому

      Thanks Tahir.
      The differential pressure setpoint is provided by the TAB contractor after they perform the water balancing.

  • @ishaqkhan7061
    @ishaqkhan7061 2 роки тому

    how the temp become 10 degree in bypass line as supply temp is 6.7 and this water is coming through bypass so should it not be 6.7

  • @tmst2199
    @tmst2199 2 роки тому +1

    Why are the primary and secondary loops are connected to each other?

    • @TechSystems
      @TechSystems  2 роки тому

      Primary and secondary loops are decoupled from each other using a decoupler/bypass pipe line. Decoupler line is designed such that flow in one loop shall not affect flow in the other loop. If flow in both loops is equal, in this case the decoupler line will not have any flow.In case of unequal flow in both loops, the difference will flow through the decoupler line and we can sequence the chiller on/off based on the direction and amount of the flow in decoupler.

  • @MuhammadUmair-ll4lr
    @MuhammadUmair-ll4lr 2 роки тому +1

    sir can you tell me wich software use for this drawing

    • @tmst2199
      @tmst2199 2 роки тому

      I guess that would be "no."

  • @khaleelahmedshaik7857
    @khaleelahmedshaik7857 8 місяців тому

    Sir...can the dia of bypass line shall be equal to the header pipe dia or the chiller pipe dia..please explain

  • @tushardhamne1200
    @tushardhamne1200 2 роки тому

    Thank ypu for this video....plz make a series of such videos.....❤️

  • @whatifsenior5374
    @whatifsenior5374 2 роки тому +1

    Very informative

  • @faisalkim4739
    @faisalkim4739 2 роки тому

    Aslamaualaikum
    Brother here at my site primary loop pumps also consists VFDs.

  • @ShakilAadeez
    @ShakilAadeez 3 роки тому +2

    Great Work Brother!! your content quality and hard work can be seen in all the videos.

  • @asemakhtar9562
    @asemakhtar9562 2 роки тому

    Nice explanation brother ,,,,can you elaborate decoupler line valves and BMS connection details

  • @cad5273
    @cad5273 Рік тому

    In general , where is the ideal location for installation of DPT

  • @saeedhameed9148
    @saeedhameed9148 2 роки тому +1

    thanks for making such a great video with detailed explanation I'm new stationary engineer was looking for such a informative video I look forward to watch your more videos thanks again

    • @TechSystems
      @TechSystems  2 роки тому

      Thank you for your feedback....Glad to hear that this video hepled you.

  • @sirrom7997
    @sirrom7997 2 роки тому +1

    Sir what will happen if all actuator valves of AHUs and FCUs are closed?

    • @TechSystems
      @TechSystems  2 роки тому +2

      Very good question. Thanks for asking.. In this situation secondary pumps would be running in dead-head condition with no flow which is not desirable and can damage the pumps.. To avoid this situation either we can install 3-way Valves on some of the AHUs or FCUs or we can install a seprate bypass line with a control valve. To control this bypass valve BMS will monitor valve position of all AHUs and FCUs and once they are close, bypass valve will be opened. Hope I answered your question.

    • @sirrom7997
      @sirrom7997 2 роки тому +1

      @@TechSystems thank you for the reply sir.Appreciated.

    • @javeedhvactechnician7760
      @javeedhvactechnician7760 2 роки тому

      ua-cam.com/video/Czj7lxszrcg/v-deo.html

  • @thankwel
    @thankwel 2 роки тому

    I have a sincere question. Why are we not able to regulate the speed of individual Chiller by means of control system in a primary loop. For example, ChillerA is 1000GPM and ChillerB is 500GPM according to cooling capacity requirement of the load. Thanks for your awesome explanation.

  • @imrankhan-ns3bi
    @imrankhan-ns3bi 3 роки тому +1

    Good for knowledge 👌👌 can you make a video on how does FAS gets activated via bms

    • @TechSystems
      @TechSystems  3 роки тому +1

      Hello Imran, U
      FAS is integrated with BMS through BACnet or other protocol and BMS use FAS data to make software interlocks to shutdown HVAC equipment. Or hardwire points can also be get from smoke detector for this purpose. Will try to make video for it as requested.

    • @imrankhan-ns3bi
      @imrankhan-ns3bi 3 роки тому +1

      @@TechSystems it is very kind of you to share your knowledge!😇 also Could you tell me all the steps of FM 200 response incase of fire

    • @javeedhvactechnician7760
      @javeedhvactechnician7760 2 роки тому

      ua-cam.com/video/Czj7lxszrcg/v-deo.html

  • @fahadyaba8674
    @fahadyaba8674 Рік тому

    I have one doubt sir, if the ch actuators getting closed then Delta P will be high or low? Can u assist me.

    • @TechSystems
      @TechSystems  Рік тому

      Yes as AHUs and FCUs valves get close, delta P will increase which will be detected by the DDC controller and as a result it will reduce the speed of Secondary pumps to keep Delta P at the setpoint value. Hope i answered your question.

  • @yeechingteh1764
    @yeechingteh1764 3 роки тому +1

    very informative video. Can you share video on variable primary system too?

  • @laworder6092
    @laworder6092 3 роки тому +2

    Assalam u alaikum brother Abdulrahman
    Thank you very much for knowledge in which your are giving to the international community. I am very impressed with your teaching methodology.it would be very interesting if you add metric values and formulas to your videos like this you will gain more viewers
    Jazaka allah khair

    • @TechSystems
      @TechSystems  3 роки тому

      Waalikum Salam,
      Thank you very much for valuable feedback and suggestion. Will consider it for my future videos.

    • @laworder6092
      @laworder6092 3 роки тому

      @@TechSystems are you based here in UK?

    • @TechSystems
      @TechSystems  3 роки тому

      No I am in Saudia Arabia

    • @javeedhvactechnician7760
      @javeedhvactechnician7760 2 роки тому

      ua-cam.com/video/Czj7lxszrcg/v-deo.html

    • @royochola
      @royochola Рік тому +1

      This guy is smart, he is strengthening my BMS knowledge everyday....

  • @vinothkumarr4667
    @vinothkumarr4667 3 роки тому +1

    Really so good explanation and thanks sir 🙏

  • @vimalguna2408
    @vimalguna2408 3 роки тому +1

    sir please explain 4 chiller and 4 primary pump and 4 secondary pump and 3 DP sensor how to secondary pumps working

    • @TechSystems
      @TechSystems  3 роки тому

      Hi Vimal concept and system working will be same with 4 chiller system, I am not aware about your project situation why 3 DP sensors are installed. Usually a single DP will be used to control the pumps speed. You may consider the value of DP sensor installed on the farthest place or as mentioned in the HVAC design.

    • @vimalguna2408
      @vimalguna2408 3 роки тому

      @@TechSystems sir this system feeding 25 floor residency building chilled water feeding 3 riser

    • @javeedhvactechnician7760
      @javeedhvactechnician7760 2 роки тому

      ua-cam.com/video/Czj7lxszrcg/v-deo.html

  • @MuhammadUmair-ll4lr
    @MuhammadUmair-ll4lr 2 роки тому

    thank you so much sir

  • @غيرنفسك-ب2ن
    @غيرنفسك-ب2ن 3 роки тому +1

    Great work brother
    Keep it up
    You are amazing

  • @SikinderVatturiv
    @SikinderVatturiv 2 роки тому +1

    Awesome explanation

  • @sayyadafrid5101
    @sayyadafrid5101 3 роки тому +1

    I was waiting.😀

  • @jaganthangapandian77
    @jaganthangapandian77 3 роки тому

    what is the abbrevation of GPM?

  • @realtruth3767
    @realtruth3767 3 роки тому

    Great 👍😍

  • @sayyadafrid5101
    @sayyadafrid5101 3 роки тому

    Excellent sir.