Finding Target Superheat to Check the Charge of an R-410A AC Unit!

Поділитися
Вставка
  • Опубліковано 28 сер 2024

КОМЕНТАРІ • 85

  • @acservicetechchannel
    @acservicetechchannel  4 роки тому +4

    -Join our updates list for an email strictly from us for new videos, articles, products and website features! www.acservicetech.com
    -Our Website has FREE Videos, Calculators, Podcasts, Articles, Tips, Quizzes, Q/A: www.acservicetech.com
    -Facebook Tips: facebook.com/acservicetech
    -Tools we use, Our Book, Workbook, and Quick Cards: www.amazon.com/shop/acservicetech
    -Our E-book, Paperback, Workbook, Quick Cards, Powerpoint, www.acservicetech.com/ac-book
    -Our E-book: play.google.com/store and search "ac service tech"
    -Spanish Book & E-book: www.acservicetech.com
    /store

  • @bluffjumper2832
    @bluffjumper2832 3 роки тому +14

    Awesome! Finally, someone that can talk you through the whole system and procedure flawlessly and they're easy to follow! Kudos on making a great teaching video where each word is understandable!

  • @fastlife866
    @fastlife866 4 роки тому +7

    Had a System today. 0 superheat 30 subcooling. Had to take out 1lb of refrigerant to get the superheat on point. I always use your chart.

  • @Matthew-jr1xr
    @Matthew-jr1xr Рік тому +3

    Why go to school when you can just watch this guy's videos? Awesome work sir.

  • @tecniman356
    @tecniman356 Рік тому +3

    Finally i understand the super heat

  • @oscarmiranda-ui1ej
    @oscarmiranda-ui1ej Рік тому +1

    Thank you. After being on the field and shadowing this makes so much more sense !

  • @hvacdoc2338
    @hvacdoc2338 4 роки тому +5

    Great video and explanation as usual !!

  • @altrality
    @altrality 2 роки тому +1

    Thank you for explaining the info. It really did help a lot. Keep at it man. You're the best

  • @APHVAC0913
    @APHVAC0913 4 роки тому +2

    So basically you need those fancy tool's 😁 Great video 👍✌️

    • @MaMa-qh4dy
      @MaMa-qh4dy 4 роки тому +3

      No. You can use the compound manifold gauge set (analog dial pressure gauges) and less expensive psychrometer to read the temps. No need for digital instruments.

  • @dustinmarkmendoza2313
    @dustinmarkmendoza2313 4 роки тому +1

    new subscriber, your video really helps me. better than SJ*C school

  • @brahimabdelsadek9534
    @brahimabdelsadek9534 3 роки тому

    Thanks for the effort you're making.learning with you makes me proud.i find it hard to understand all.wanna get rid of the French language.have a nice day.

  • @jimbola77
    @jimbola77 4 роки тому +2

    Excellent vid!!!! thanks, Craig.

  • @betocruz2589
    @betocruz2589 Рік тому

    You guys are the best😊

  • @cristobalsanchez2030
    @cristobalsanchez2030 Рік тому

    Hey Craig, can you do a video on how to check sub cooling and super heat on packaged units please

  • @mikev.1034
    @mikev.1034 4 роки тому +2

    Great video. 👍👍

  • @ludwig6332
    @ludwig6332 2 місяці тому

    I am trying to wrap my mind around what is happening to the gas if the SH is way low, I.e. you said "if low to 5 or so, we want to make sure we're not sucking liquid back too the compressor". So that would be overcharged robbing volume? causing a lack of space for expansion to take place?

  • @JesusZendejas-nz5ni
    @JesusZendejas-nz5ni Рік тому +1

    Is the indoor wet bulb temperature just a reading of the temperature inside the return ? Or is a special tool required to calculate it ?

  • @corruptedbrain6
    @corruptedbrain6 Рік тому

    i just ordered some of those charts !

  • @mystory1162
    @mystory1162 2 роки тому +1

    Craig, I wish you explained in this video better to its listeners WHY you are checking the WBT in the return at the air handler and not the DBT. So let me explain the missing info. You only check the WBT if the relative humidity is above 70% or below 20%. Anything in between you are to check the DBT at the return.

  • @paullenton2076
    @paullenton2076 4 роки тому +3

    Great channel Craig, I am a mature student after many years as a plumber and a move from the UK to Australia I have moved onto HVAC, my question. Do you have any plans to do a metric version of the book ?

  • @AnimateInstinct
    @AnimateInstinct 3 роки тому +1

    Great video! Thank you 👍

  • @nikosgood4774
    @nikosgood4774 4 роки тому +1

    This is awesome 👌 thank you!

  • @aamirdilshad4122
    @aamirdilshad4122 2 роки тому

    Very useful information thanks dear

  • @leonechevarria359
    @leonechevarria359 4 роки тому +1

    I have replaced a heat pump compressor(2ton) that had r-22 and i filled it with mo-99... replaced filter dryer, did a nitrogen pressure , pulled a good vacuum... the evaporator is a fur down unit (pancake) i checked both piston... blowers are ok
    ..the problem I have is that the compressor making a hissing noise, Low side 115 psi , 15 sh , vsat 71.4 , slt 86.3....hi side 168, -OL sc (no subcooling), 85 LSAT , 86.6LLT....had a a/c company called in and said was the valves 🤔 went ahead a replaced it with another compressor same problem no enough super heat/no cooling properly...
    Did replaced filter from the beginning...coils inside evaporator and condenser clean.
    I KNOW THERE'S A PROBLEM BECAUSE NO COOLING PROPERLY/HAVE USED DIGITAL AND ANALOG GAUGES BUT DON'T HAVE PROPER READING...I HAVE OVER CHARGE AND UNDER CHARGE IT ON PURPOSE TO SEE BUT CAN'T FIGURE IT OUT....

  • @zekenzy6486
    @zekenzy6486 4 роки тому +1

    Great Video. Have a nice weekend . Thank you for sharing ^_^

  • @KamalSingh-dd4ou
    @KamalSingh-dd4ou 4 роки тому

    GREAT VIDEOS OF YOUR THANK YOU SIR
    can you do video or share info about which refrigerant is best replacememt for R22 and what needs to be done when replacing refrigerant

    • @Pibs2525
      @Pibs2525 24 дні тому

      407c has similar pressures, I’d change the filter drier and install a 407c txv

  • @dwightvelez8357
    @dwightvelez8357 4 роки тому +1

    Super great!!

  • @jimbola77
    @jimbola77 4 роки тому +1

    are those digitals accurate! do u need to calibrate them? thanks.

  • @Funboyy123
    @Funboyy123 3 роки тому +4

    Why were the digital and analog readings so different? Super heat on Analog was 14 and Digital it was 7.5. Why is that?

    • @guillermotejeda692
      @guillermotejeda692 Рік тому +1

      That's exactly what I thought, lol which would be more accurate?
      Maybe look at the overall picture to determine?

    • @hvacmania8323
      @hvacmania8323 Рік тому

      Because it fluctuates depending on indoor / outdoor temps . Maybe after removing analog gauges and attaching digital ones outdoor indoor temps weren’t exactly the same etc

    • @bobward7489
      @bobward7489 Місяць тому

      The I door wet bulb changed, shifting the readings

  • @ArqualityShuttersCom
    @ArqualityShuttersCom Рік тому

    Exactly where does the psycrometer needs to be place on the evaporator coil to find the temperature can it be place just outside the box

  • @milanlipovic7349
    @milanlipovic7349 4 роки тому

    I’m fresh out of HVAC school so this might be a stupid question but I believe I heard that if your suction line temp is 65 or above that it’s bad for the compressor or maybe it’s just Copeland compressors?

    • @JohnQPublic345
      @JohnQPublic345 3 роки тому

      If refrigerant is low, oil that's supposed to lubricate compressor will get pumped out and into lineset

  • @BallisticBilly3
    @BallisticBilly3 Рік тому

    Would you get the same wet bulb temp reading at the return air vent and in the duct-work??

  • @mikeblackpoetry5248
    @mikeblackpoetry5248 5 місяців тому

    What tool are you using for temps?

  • @JohnQPublic345
    @JohnQPublic345 Рік тому

    Can you take the IDWB temp at the main return?

  • @nbctcp3450
    @nbctcp3450 8 місяців тому

    1. how to find target superheat for single split aircond R32 in Celcius
    2. do u hv chart for it

  • @666miguel99
    @666miguel99 Рік тому

    I got a question, why are all my wet-bulb temperatures below 49 degrees Fahrenheit. I'm taking my temperature right at my condenser return. Is that not what I'm supposed to take it from ?

  • @matt_in_maine
    @matt_in_maine 4 роки тому

    Does the digital manifold connect with the job link prob compared to the dual in duct psychrometer?

  • @michaeldreves5072
    @michaeldreves5072 4 роки тому +1

    I have a question if you have a 410a system with a txv and you have good temperatures like say 42 degree evap coil temperature and 11 degree SH and 8 degree SC but have low suction pressure of 95 psi and a head pressure of 305 psi is this a system that has issues like air flow or other problems

    • @hvacdoc2338
      @hvacdoc2338 4 роки тому +3

      Michael Dreves
      Take your readings again. Something seems off. If you have a 95psi your coil would freeze. 95psi is a 28° evaporator temperature.

  • @foodtravelxp24
    @foodtravelxp24 2 роки тому

    Can you tell me that r134a and r404 gas target superheat chart. -temperature and +temperature are both gas.

  • @bayouflats5054
    @bayouflats5054 3 роки тому +1

    Thanks. What happens when a fellow employee insists on charging by sub-cool method on systems with pistons ?

    • @Sesamestreet9080
      @Sesamestreet9080 Рік тому +1

      We’ll sub cooling can tell you something also if you reading a piston system . Too high of a sub cooling can tell you it’s over charged so your next move would be to reduce sub cooling,

    • @bayouflats5054
      @bayouflats5054 Рік тому +1

      @@Sesamestreet9080 appreciate reply, but sub-cool method is for TXV system and superheat is for piston/ fixed orifice. And “I” find these scroll compressors to be very finicky and don’t last if not pretty much dead on. Oh well, he’s the sup, so it’s on his head, but man, in Deep South, summers are murder on units already, if a person is there working/ charging it…., why not simply do it correctly? 😖🤷‍♂️

    • @Sesamestreet9080
      @Sesamestreet9080 Рік тому +1

      @@bayouflats5054 definitely charge by superheat with piston, but knowing both will let you know what’s going on with the system , sub 6 on superheat means you’re flooding the compressor

  • @Samlol23_drrich
    @Samlol23_drrich 2 роки тому

    On my old r22 system with a piston, is it true that if the vapor line temperature at the condenser is 41 degrees, (83 dry bulb for what it’s worth) the MOST my superheat can be is 9 degrees or so if my system is working properly? (Since the evaporator coil isn’t freezing, I took 41 and subtracted 32 to get 9).
    I have two 33 year old Armstrong air units and both work well. Clean coils, good air flow etc. I do not want to hook any gauges to them, there is just no reason. The downside of creating a schrader valve leak outweighs any knowledge I would get, since they are working very well. Delta T indoors is about 19 degrees which is just fine for me. I find this stuff very interesting. Thanks in advance.

    • @JohnQPublic345
      @JohnQPublic345 Рік тому

      41 degrees makes sense. Yes . Depends on the other variables

  • @IsaacHernandez-ow3sn
    @IsaacHernandez-ow3sn 11 місяців тому

    Do yall have an app

  • @hbo7799
    @hbo7799 2 роки тому

    Can these two parameters also be used in the AC car service?

    • @hbo7799
      @hbo7799 2 роки тому

      for r134a?

  • @mnew213
    @mnew213 4 роки тому

    Hi Craig, I have a R410a unit - model # YCJD36S41S1, the unit pressure is 175 PSI when the unit turned off, do you know if this pressure is correct? Thanks

    • @JohnQPublic345
      @JohnQPublic345 3 роки тому

      Depends on outdoor temp. It will change pressure in an off unit

  • @acrepairnearme
    @acrepairnearme 4 роки тому

    Good beard! But! Craig, you are still young. Without it, you will look even better.

  • @hvacplayer3238
    @hvacplayer3238 4 роки тому

    I wonder if I could get your opinion on this
    r410a refrigerant
    My sub cooling is high, unit calls for 10-12 but it’s 18 (it’s a TXV system)
    super heat is .8-1.2
    Temp split is 18-20
    Suction line temp is 38-40 (118 psi)
    Liquid line temp is 75 (288 psi)
    Outdoor temp is 77
    Indoor temp is 77
    Blower is set to 400 cfm, 3 ton
    Filter, blower, evaporator, ductwork is all clean, all new units installed a few months ago

  • @irham9856
    @irham9856 10 місяців тому

    👍👍👍

  • @abdulfataw2119
    @abdulfataw2119 4 роки тому +1

    Sir pls do u have a book

    • @acservicetechchannel
      @acservicetechchannel  4 роки тому +1

      Good Morning, We have a Paperback - Refrigerant Charging and Service Procedures for Air Conditioning on our website! www.acservicetech.com/store

  •  4 роки тому

    The cards they sent me have a smudge mark across the 80 degree mark it looks like green paint. I tried to scratch it of but it made it worse

    • @acservicetechchannel
      @acservicetechchannel  4 роки тому

      Please email us with a pic of the card to info@acservicetech.com and if you ordered it on amazon or our website and we can send you out a new one, thanks!

    •  4 роки тому

      My address is 2408 Windridge Ct, Apt#1, Rockford Illinois 61108

  • @suwajmarek
    @suwajmarek Рік тому

    👌

  • @aaronhickey4879
    @aaronhickey4879 Рік тому

    Flip hot and neutral, please. The fan is blowing in the wrong direction.

  •  4 роки тому

    That card your holding.

  • @guntheraveusa8772
    @guntheraveusa8772 Рік тому

    Gz... HOW LOW IS THE VAPOR LINE TEMP GOING TO GO 😆😂