EICR dead short...

Поділитися
Вставка
  • Опубліковано 20 тра 2020
  • Whilst carrying out an EICR that the installation was only 10 years old, we came across a neutral to earth fat whilst carrying out an insulation resistance test.
    Watch the video to discover what I found...

КОМЕНТАРІ • 7

  • @mrt864
    @mrt864 4 роки тому +1

    Well done on finding that fault!

    • @repsyltd
      @repsyltd  4 роки тому +1

      Total luck to be fair... could of been anywhere. It was relatively close to the loft hatch as well.

  • @RWATraineeElectrician
    @RWATraineeElectrician 4 роки тому +1

    Great video, so I assume you cut out the piece with the nail in it and then the white flex joined the two wago boxes together?

    • @repsyltd
      @repsyltd  4 роки тому +1

      The white flex was actually twin and earth.. all we had.. was a nightmare where it was..

  • @johnwaby4321
    @johnwaby4321 3 роки тому

    Don't forget to carry out an insulation resistance test with the circuit earth connected in the main earth bar and put one your test leads on the main earth bar ..

  • @SJM689
    @SJM689 3 роки тому

    Did you cable tie the box's and secure them to a joist?

    • @repsyltd
      @repsyltd  3 роки тому

      Extremely awkward access restricted us from fixing anything, the cable was deep in the eves. We were lucky we could even carry out the repair.