Is it just me or is Trane symbio turning on the wrong compressor? simple fix on this one.

Поділитися
Вставка
  • Опубліковано 6 вер 2024
  • settings were to have a discharge temp sensor disabled that function and jumped y1 and y2 to get both compressors running at the same time...

КОМЕНТАРІ • 20

  • @Millertime1717
    @Millertime1717 16 днів тому

    I agree it's not what we're use too but y1 energizes compressor 2. It's gonna take some getting use too.

  • @joshuaricks7730
    @joshuaricks7730 10 днів тому

    Cool 1 is NOT the same as compressor 1. Compressor 2 is the smaller of the two compressors. That will always be the first on last off. This is stated in the manual a couple times. The contactor failure faults you are having is because you have Y1 and Y2 jumped out. If the aux switch makes without a call it thinks the contactor is welded.

  • @alessichris07
    @alessichris07 23 дні тому

    Circuit 2 is stage 1 cooling, the smaller compressor.
    I've seen the proving error, caused by discharge temp sensor.

  • @lccerrillo
    @lccerrillo 2 місяці тому +1

    Just investigate one with that proving lockout alarm with tandem circuit, it was overcharged

  • @hotcoolheatingcooling3850
    @hotcoolheatingcooling3850 23 дні тому

    Same problem I have compressor number 2 start first

  • @scottsnider3511
    @scottsnider3511 3 місяці тому +3

    I have the same issue on a 7.5ton proving switch 1st stage issue, and tech supports no help. I replaced the contactor and aux without resolution. Did you find a solution?

    • @hvactoolporn188
      @hvactoolporn188  3 місяці тому

      We replaced contactor and micro switch and 2 days later ordered a Dainkin unit. We are experimenting with gutting controller on a few units but have not made a final decision to what methods we will use in the future....

    • @Kdavis8377
      @Kdavis8377 2 місяці тому +2

      Bottom contractor is actually circuit #1. Schematic is labeled wrong. Small compressor is 1st stage. Don’t ask me how I know. Had this exact issue and scratched my head for awhile. Check incoming voltage. Trane taps all their transformers for 240v. Had to tap the transformers for 208v. Haven’t had a single trip since. My control voltage went from 23.2v to 27v. Tranes are super sensitive to anything below 24v

    • @hvactoolporn188
      @hvactoolporn188  2 місяці тому

      Yeah we replaced the switch and have not been back..

    • @kylewhite291
      @kylewhite291 Місяць тому

      Anybody having issues with these units not dehumidifying in 1st stage cooling? 33% cooling capacity and 66% fan speed. 50+ degree saturated suction temperature not below RAT dew point. I’ve lowered the “max fan speed” as a temporary fix but then when unit runs 100% cooling capacity it like 230cfm/ton.

  • @marvinsellers4457
    @marvinsellers4457 3 місяці тому +1

    Buddy I’ve have the same problems gut it rewire as long as your warranty is not in place they do some really dumb things

  • @hvac402
    @hvac402 Місяць тому +1

    Can you just move the 24 V wires from one contactor to the other

    • @hvactoolporn188
      @hvactoolporn188  Місяць тому

      No, the board will fault out. First thing I tried.

    • @joshuaricks7730
      @joshuaricks7730 10 днів тому

      Cool 1 is NOT the same as compressor 1. Compressor 2 is the smaller of the two compressors. That will always be the first on last off. This is stated in the manual a couple times. The contactor failure faults you are having is because you have Y1 and Y2 jumped out. If the aux switch makes without a call it thinks the contactor is welded.

  • @nevermind3965
    @nevermind3965 21 день тому

    symbio controls are garbage.If you can get it to start anything, just go with it.

  • @benahmedahmed831
    @benahmedahmed831 Місяць тому

    Perblam E2 model SERVICE FIRST Trance Rooftop SENO 1577 ‏termstat