No cooling call on a Saturday - HVAC

Поділитися
Вставка
  • Опубліковано 11 жов 2024
  • I had a no cooling call on a hot Saturday.
    There was high voltage power at the outdoor unit.
    The unit was just not receiving a low voltage call at the contactor.
    I followed the low voltage 24v all the way from the air handler to the outdoor unit and noticed that I was not getting 24v after the high pressure switch.
    I tested this by bypassing the high pressure switch and saw that the contactor coil pulled in.
    I was able to add a new high pressure switch at the liquid line and wire but it in where the old pressure switch went.
    Tested pressures and finished the service call.
    Thanks for watching!