No cooling call on a Saturday - HVAC
Вставка
- Опубліковано 11 жов 2024
- I had a no cooling call on a hot Saturday.
There was high voltage power at the outdoor unit.
The unit was just not receiving a low voltage call at the contactor.
I followed the low voltage 24v all the way from the air handler to the outdoor unit and noticed that I was not getting 24v after the high pressure switch.
I tested this by bypassing the high pressure switch and saw that the contactor coil pulled in.
I was able to add a new high pressure switch at the liquid line and wire but it in where the old pressure switch went.
Tested pressures and finished the service call.
Thanks for watching!
Like and subscribe for more
Good job buddy
Cool channel bro. I have a question maybe u can answer. im a cannabis grower and i have a 10x10 room. how many btu's for a window unit is enough to make the room reach 60 degrees with no problem. Thanks
I would go with a 5000 btu size windows unit for a 100 square foot room. And it would be difficult to get any room to 60 degrees.. especially with a window unit.
WRONG WRONG WRONG WHY DUDE YOU JUST MADE IT A LOT MORE TROUBLE TO SERVICE THIS UNIT