RSLogix & Studio 5000 Produced and Consumed Tags | PLC Data Concentrator SCADA, Messaging, EtherNet

Поділитися
Вставка
  • Опубліковано 8 вер 2024

КОМЕНТАРІ • 19

  • @chrishill8612
    @chrishill8612 3 роки тому +1

    Thanks for this, your fault finding saved me. I had exactly the same problem and needed to set Electronic Keying to Disabled on the 1756-EN2TR as you did in your video at 22:09.

  • @biz3kid
    @biz3kid 5 років тому +1

    Your videos are awesome! You fit a lot of good information succinctly and without skipping any steps. I learn something new and useful every time I watch your videos. Thank you!

  • @heraindesai257
    @heraindesai257 3 роки тому

    Such a good explanation about it. Really like the way you explain it and looking forward to see many more.🙌🙌🙌
    Thank you for your effort.🙏🏻✌🏻

  • @KhalilNajjar
    @KhalilNajjar 3 роки тому

    GREAT CONTENT. Thank you!

  • @LOKESH-nq2zu
    @LOKESH-nq2zu 3 роки тому

    THANKS

  • @mohamedel-shamy1945
    @mohamedel-shamy1945 Рік тому

    please sir, we want u to reference some resource thru which we can read into the topic to get a bit deeper understanding

  • @shaishavshah5114
    @shaishavshah5114 4 роки тому

    Hey. Good stuff bro.
    Only thing i wanted to ask you if you could make a video of how to transfer more then 500 bytes of an array from one to other cpu.
    I know that one scheduled connection can only transfer uptp 500 dint. So if you could make a video on this please.
    Thank you very much and god bless you for the good teaching skills

    • @SolisPLC
      @SolisPLC  4 роки тому

      That's an interesting question. I have never had to transfer more than 500 bytes from a single PLC. Let me test what that will entail.

    • @dipakpateel1
      @dipakpateel1 2 роки тому

      @@SolisPLC The size of the produced and consumed standard tag is limited to less
      than or equal to 500 bytes.
      The size of the produced and consumed safety tags are limited to 128
      bytes.

  • @controlsmike2433
    @controlsmike2433 3 роки тому

    Hello! I am adding 11 groups (6 tags in a group) of produced tags to a PLC. They are in the program and ready and I'm about to enable the consuming PLC. My concern is the producing PLC is running at 94% I/O utilization and I am concerned I am going to overload it with this addition. Thoughts?

  • @mrtrader4628
    @mrtrader4628 4 роки тому +1

    Okay very good once again thanks, still a bit to fast..and can you show this use emulator 5000?
    Darren TX

    • @SolisPLC
      @SolisPLC  4 роки тому

      Sorry about the speed. We're working on it. We don't have access to a license of RSLogix 5000 Emulate at this time.

    • @mrtrader4628
      @mrtrader4628 4 роки тому

      Okay thanks for your timely reply. Also I don't know if you guys have this out there already to go with this, but I also need some training or Info about the various type of
      switch that you are using to connect between PLC's
      Thanks.

  • @jagatheeshmani6959
    @jagatheeshmani6959 Рік тому

    I’m using L43 in Rs-logix 5000 v17 and L72 in Studio 5000 v24. In studio 5000 I can find both cpu as shown in your video but logix 5000 L72 is not available so I used L65 and tried to establish communication but no use. What can I do in this situation. Please suggest

  • @yasaali7475
    @yasaali7475 3 роки тому

    Hello .. how speed of the kind studio 5000 ( typical freq )

    • @SolisPLC
      @SolisPLC  3 роки тому

      I don't understand what you're asking; what do you mean by speed? "of the kind studio 5000"?