Great video!, I have a vista 15P with the 6150, the 2 exit doors when open say 05.There is no exit/entry delay on either or anything else. I need help programing the delays on the 6150.I only have 1 good working hand so I am a little slow at the keypadThanks for all your help!!
Just installed second 61/64 keypad on same bus as 1st keypad. 1st keypad address was 16 .... should the new 2nd keypad be addressed the same or 17 or something- FYI it’s not working
I've currently got 7 wireless sensors on my Vista 15P system and want to add 6 more. Are there enough open wireless slots to do that? How do I check to see what zones have been allocated to my existing sensors, so that I don't assign a new sensor to a zone that is already occupied?
Dear Friend.I have vista 120 and the house is separate in 5 partition.When arming the partitions separately 1 or 2 etc , the exit delay beeps do not always make sound even if the system starts to arm.Why is that? Why sometimes is arming in silent? All partitions should make exit beeps always and not sometimes.....What do you think??
my system has issued 3 false fire alerts today, more than minutes apart. each alert has a LOUD voice message "FIRE" and beeping that lasts less than 10 seconds. obviously, there is no fire. what is the procedure to diagnose which sensor(s) is a fault and how to correct? also, is there a way to control the alarm volume- its way too loud?
Thanks for the video. But it's not going anywhere for me. I pressed 1 & 3, then inputted 1 & 6, pressed * and the display goes blank after that and I can't proceed to the next step of putting in the installer code. So now what do I do?
Good Morning just install my Vista 20P, followed the manual info for programming. the system is not reporting open, close or alarm restoral reports, can you determined where did I went wrong?
Hi, my HONEYWELL VISTA 20P alarm panel is reading "FC 100". I want to use my door chime but I am not using any monitoring system. Is there anyway to clear the FC100 error and use the alarm as a door chime only? Thank you.
My question is, could a bad main vista 20 p alarm panel that is connected to a 4219 zone expander give me an open circuit on the keypad? The wire between the expanded and main panel is good.
It's possible, but most times when we see the Open CKT being displayed on the keypad it is because of a bad wire or wire that has snapped inside the wiring sheath or simply that the wires are not hooked to the proper terminals. I would replace the wire between your keypad and the 4219
good video. would you know of a product that I can install foe 2 way voice. I have installed the evl-4 communicator. I also have voip from an obi-110. do I have any options where I can listen in when alarm or emergency or distress alarm occurs.
I configured Zone3 for a motion sensor, Zn ZT P RC HW: RT: 03 04 1 10 NC 1 But the panel shows Fautl in this zone, I have a resistor on the sensor, I was told it was needed. Is it really necesary?? What can I do??
Is it possible to add a time delay to every zone, not just delay entry, I want to monitor five or six doors, when they are opened I want it to be delayed for X amount of time before the vista sees it, is this possible?
It is possible to add a delay to the doors like you mentioned. The Vista system has an entery delay 1 and entry delay 2. The reason for this is that you can set a different duration for each delay. You could just make all doors like you were telling about entry delay 1. And if you set entry delay 1 to be 30 seconds in programming then all of those five or six doors would have a 30 second delay when they were opened
You could add the following device to the system and get that capabilty. It's called the Envisalink 4 and it's made by a company called Eyez-On - www.alarmsystemstore.com/products/envisalink-4-ip-communicator-security-interface-module
Can you please help me I'm trying to reprogram my system because my roommates sister and her boyfriend messed it up while they stayed here at my apartment they did it without asking me first
We do have a great tech guide for a Honeywell Vista system that makes programming very easy. Is that the system you're working with? You can find the Vista guide here - www.alarmsystemstore.com/pages/honeywell-vista-series-15p-20p-and-21ip-quickstart-guide
Hi john my name is John I usto do alarms and took some equipment out of my apartment can i talk to you about it it is all honneywell equipment and a telguard comm
Well, there's a few ways to program those keys. What exactly do you want them to do? They can be used as all panic keys or you can assign one button arming to a few of them. Unfortunately you cannot do both at the same time
that means they are like 2 different systems but all on 1 system it also means you can for example have a partition on your basement that means you can arm your basement from your main system but still have the main one disarmed or both
the installer code is rong. if you want to program the system you have to pouer cycle the panel. when the panel boots up run to the nearest keypad before 50 seconds expires when you give power to the panel. press star and pound to get into programing.
10 years later and you're still educating people like me - great video, super clear explanations. Thanks!
Just installed a vista 20P over the weekend and started programming. Excellent video to start. this is my second one to do, a good refresher for me.
Great video!, I have a vista 15P with the 6150, the 2
exit doors when open say 05.There is no exit/entry delay on either or anything else. I
need help programing the delays on the 6150.I only have 1 good working hand so I am a little slow at
the keypadThanks for all your help!!
thank you for you support
Just installed second 61/64 keypad on same bus as 1st keypad.
1st keypad address was 16 .... should the new 2nd keypad be addressed the same or 17 or something- FYI it’s not working
I've currently got 7 wireless sensors on my Vista 15P system and want to add 6 more. Are there enough open wireless slots to do that? How do I check to see what zones have been allocated to my existing sensors, so that I don't assign a new sensor to a zone that is already occupied?
Dear Friend.I have vista 120 and the house is separate in 5 partition.When arming the partitions separately 1 or 2 etc , the exit delay beeps do not always make sound even if the system starts to arm.Why is that? Why sometimes is arming in silent? All partitions should make exit beeps always and not sometimes.....What do you think??
my system has issued 3 false fire alerts today, more than minutes apart. each alert has a LOUD voice message "FIRE" and beeping that lasts less than 10 seconds. obviously, there is no fire. what is the procedure to diagnose which sensor(s) is a fault and how to correct? also, is there a way to control the alarm volume- its way too loud?
hi,can you make a video how to enrol a 5834-4 key fob?thank you
Thanks for the video. But it's not going anywhere for me. I pressed 1 & 3, then inputted 1 & 6, pressed * and the display goes blank after that and I can't proceed to the next step of putting in the installer code. So now what do I do?
Good Morning just install my Vista 20P, followed the manual info for programming. the system is not reporting open, close or alarm restoral reports, can you determined where did I went wrong?
Hi, my HONEYWELL VISTA 20P alarm panel is reading "FC 100". I want to use my door chime but I am not using any monitoring system. Is there anyway to clear the FC100 error and use the alarm as a door chime only? Thank you.
Can you do a video on how to wire and program a Honeywell vista 50p.
My question is, could a bad main vista 20 p alarm panel that is connected to a 4219 zone expander give me an open circuit on the keypad? The wire between the expanded and main panel is good.
It's possible, but most times when we see the Open CKT being displayed on the keypad it is because of a bad wire or wire that has snapped inside the wiring sheath or simply that the wires are not hooked to the proper terminals. I would replace the wire between your keypad and the 4219
good video. would you know of a product that I can install foe 2 way voice. I have installed the evl-4 communicator. I also have voip from an obi-110. do I have any options where I can listen in when alarm or emergency or distress alarm occurs.
I configured Zone3 for a motion sensor,
Zn ZT P RC HW: RT:
03 04 1 10 NC 1
But the panel shows Fautl in this zone, I have a resistor on the sensor, I was told it was needed. Is it really necesary??
What can I do??
Is it possible to add a time delay to every zone, not just delay entry, I want to monitor five or six doors, when they are opened I want it to be delayed for X amount of time before the vista sees it, is this possible?
It is possible to add a delay to the doors like you mentioned. The Vista system has an entery delay 1 and entry delay 2. The reason for this is that you can set a different duration for each delay. You could just make all doors like you were telling about entry delay 1. And if you set entry delay 1 to be 30 seconds in programming then all of those five or six doors would have a 30 second delay when they were opened
How do i program my key fob to the system.
Also can you reset the alarm from a remote location over the internet?
You could add the following device to the system and get that capabilty. It's called the Envisalink 4 and it's made by a company called Eyez-On - www.alarmsystemstore.com/products/envisalink-4-ip-communicator-security-interface-module
how can i set up the moshen sensor to chime.
my printer can print out report, but when arm/disarm and bypass there's no report. why uh?
Can you please help me I'm trying to reprogram my system because my roommates sister and her boyfriend messed it up while they stayed here at my apartment they did it without asking me first
We do have a great tech guide for a Honeywell Vista system that makes programming very easy. Is that the system you're working with? You can find the Vista guide here - www.alarmsystemstore.com/pages/honeywell-vista-series-15p-20p-and-21ip-quickstart-guide
How do you program function A key location for duress on a 6160? The flow chart on the manual is hard to follow.
access level 3 is duress
Hi john my name is John I usto do alarms and took some equipment out of my apartment can i talk to you about it it is all honneywell equipment and a telguard comm
Need a updated video
How do you program function keys? (*57)
Well, there's a few ways to program those keys. What exactly do you want them to do? They can be used as all panic keys or you can assign one button arming to a few of them. Unfortunately you cannot do both at the same time
Never mind. I found it in the programming manual.
Good deal! Glad you found it :) Thanks for watching
My alarm system is showing open zones and there's none.
Great work
Thanks! We're always trying to do better to put out quality videos. Always nice to hear feedback :)
what do you mean by partition 2 vs. partition 1
that means they are like 2 different systems but all on 1 system it also means you can for example have a partition on your basement that means you can arm your basement from your main system but still have the main one disarmed or both
Nice one
I'm pressing 4112 800 but it isn't registering the last 0. Suggestions?
Probably a wrong installer code
Ok got that sorted. But now my other 2 keypads have blank screens. I addressed them 1 and 2. Suggestions?
Nevermind. Figured it out. Thx!
installer code + 800 = long beep.... what does that mean
the installer code is rong.
if you want to program the system you have to pouer cycle the panel.
when the panel boots up run to the nearest keypad before 50 seconds expires when you give power to the panel.
press star and pound to get into programing.
This never worked on my vista
i need one how can i gate
shahain kamal Amazon. Honeywell Keypad 6160