i am installed 2 LSG 1 for active power and 1 for reactive power but when check the sequencing screen reactive power lsg is showing LSG and active power LSG have stop sing
wich generator is controling that easygen? I mean does proportional values at the voltage and frequency controls are way to high. I have worked with easygen almost 10 year with all kind of engines (gas, diesel and crude oil) and I havent seen those values, but if it is working it must be ok
zeusbreaker this was a strange job where we were syncing only through a 2301D and the 2301D was doing the load sharing. This was on a 550KW Waukesha Natural Gas genset.
i am installed 2 LSG 1 for active power and 1 for reactive power
but when check the sequencing screen reactive power lsg is showing LSG and active power LSG have stop sing
hi dear can you tell me how to config the load share gatway (LSG) with easygeb2500
wich generator is controling that easygen? I mean does proportional values at the voltage and frequency controls are way to high. I have worked with easygen almost 10 year with all kind of engines (gas, diesel and crude oil) and I havent seen those values, but if it is working it must be ok
zeusbreaker this was a strange job where we were syncing only through a 2301D and the 2301D was doing the load sharing. This was on a 550KW Waukesha Natural Gas genset.
I was thinking about that possibility. some configuration are strange and it depends how it was concieved at the engineering design
You need a 2301D to control a mechanical governor. Also it was a retrofit and the 2301D was already on site.
Engine working pairamitar