Hi sir your way of explanation is too good, i just want to know that when we inject the voltage through IR test set i noticed that i had select the volate 2.5 kv DC but the display always show extra volatge like 2850v can you explain it what's phenomina behind this
Thanks for the vedio .. you r doing very great Job 👍👍 thanks once again 🙏 We have seen that till 7-8 Minute IR increases but in few of cases after 7-8 mintus IR start decreasing...why it start decreasing? What is the reason behind this ? Pls suggest...
Sir , this is Priya Ranjan Mallick who had asked you about AVR & Capability Curve . Anyways , why have you told that Live terminal wire has gained negative polarity ? I couldn't understand it Sir . Will you please clarify ?
Nice question. Overload is one kind of overcurrent. But the difference is in operating time and magnitude. Overcurrent - Very high current as compared to rated current (For short period of time) Overcurrent - Slightly high current as compared to rated current (For long time)
Hi sir your way of explanation is too good, i just want to know that when we inject the voltage through IR test set i noticed that i had select the volate 2.5 kv DC but the display always show extra volatge like 2850v can you explain it what's phenomina behind this
Being a field engineer I must say,This is the MOST Perfect neet and clean explanation....good job to my IIT friend.
Thanks
Video i was trying to find in UA-cam..thank you very much♥️
Welcome!
I never ever seen this type of explanation thank you so much sir
You are most welcome 😊
great explanation.
Glad you think so!
Excellent bro 👍🏻👍🏻
Very intresting video, thanks
Nice 👍 explain bro
Thanks 🙂
Very very usefull sir.
Nice video sir
So nice of you
Good. Thanks 🙏
Good job my bay
Nice
Pls sir guide me DD and DAR test kyo karate hai(Motor,Generator, Transformer etc) ek video banakar explain kar de
Hi sir your way of explanation is too good, i just want to know that when we inject the voltage through IR test set i noticed that i had select the volate 2.5 kv DC but the display always show extra volatge like 2850v can you explain it what's phenomina behind this
If HT motor ( 11 kv ) pi value is less than 1 then what action to be taken for to increase pi value
Thanks for the vedio .. you r doing very great Job 👍👍 thanks once again 🙏
We have seen that till 7-8 Minute IR increases but in few of cases after 7-8 mintus IR start decreasing...why it start decreasing? What is the reason behind this ?
Pls suggest...
Sir what is the unit of polarization index test
Sir , this is Priya Ranjan Mallick who had asked you about AVR & Capability Curve . Anyways , why have you told that Live terminal wire has gained negative polarity ? I couldn't understand it Sir . Will you please clarify ?
Sir , Is it really due to Electric Field is the negative of potential gradient ?
Requesting you for making a vedio regarding CT Excitation test & Generator Droop setting.
Best
Sir what is different over current. And overload in electrical !
Nice question. Overload is one kind of overcurrent.
But the difference is in operating time and magnitude.
Overcurrent - Very high current as compared to rated current (For short period of time)
Overcurrent - Slightly high current as compared to rated current (For long time)
Please sir Kisi bhi motor ka IR value range kitna hona chahiye different rated motor or equipment.
Ok. your question will be answered.
sir power point me esp ka presentation banao na
Hi sir your way of explanation is too good, i just want to know that when we inject the voltage through IR test set i noticed that i had select the volate 2.5 kv DC but the display always show extra volatge like 2850v can you explain it what's phenomina behind this