What is a LIGHTER Pot

Поділитися
Вставка
  • Опубліковано 23 лип 2024
  • In this video we talk about what the terms LIGHT and POWER mean in regards to a delta bank. We also talk about the proper procedure for energizing a delta bank and why it is important to do so.
    *************************************************************************
    Email: hilineacademy05@gmail.com
    FOLLOW ME ON INSTAGRAM
    hilineacademy?i...
    FOLLOW ME ON FACEBOOK
    profile.php?...
    UA-cam Video Legal Liability Disclaimer Notice
    The content of this video is presented as information only, and Hiline Academy LLC makes no claims, promises, or guarantees about the accuracy, completeness, or adequacy of the procedures and instructions contained therein.
    Hiline Academy LLC expressly disclaims liability for errors and omissions that any viewers of this video might declare to exist in the information as presented.
    No liability exists or can be ascribed to this content created and presented by Hiline Academy LLC in the event of any accident or injury that might occur as a result of improper application or understanding of the procedures and information contained in this video.
    ------------------------------------------------------------------------------------------------
    DISCLAIMER
    Under no circumstances will Hiline Academy LLC be responsible or liable in any way for any content, including but not limited to, any errors or omissions in the content, or for any loss or damage of any kind incurred as a result of any content communicated in this video, whether by Hiline Academy LLC or a third party. In no event shall Hiline Academy LLC be liable for any special, indirect or consequential damages or any damages whatsoever resulting from the performance of any information communicated in this video.
    Hiline Academy LLC assumes no liability for property damage or injury incurred as a result of any of the information contained in this video. Use this information at your own risk. Hiline Academy LLC recommends safe practices when performing any do it yourself repairs and or with tools seen or implied in this video. Due to factors beyond the control of Hiline Academy LLC, no information in this video shall create any expressed or implied warranty or guarantee of any particular result. Any injury, damage or loss that may result from improper use of these tools, equipment, or from the Hiline Academy LLC.

КОМЕНТАРІ • 13

  • @daveg.4862
    @daveg.4862 Рік тому +1

    EE here Cody. First thank you for making these Great Videos. They fill in sooo many blanks for us industrial sparkys. Open Delta services can cause problems on SCR/IGBT controls because they deform the sine wave (making the peak higher) an tripping the drives on high bus faults. RMS voltage stays ok, so you can only see it on a Scope. You are a great Teacher! keep up the good work. Closing the Delta fix's it. (but thats more work for you guys)

  • @bordersoldier
    @bordersoldier Рік тому +1

    Another great lesson !!!

  • @jeffreykornspan9053
    @jeffreykornspan9053 Рік тому +1

    Nice demonstration

  • @StoneStraiff
    @StoneStraiff Рік тому +1

    Thankyou so much for this

  • @zackberghoefer5174
    @zackberghoefer5174 3 місяці тому

    Question, on the board in the shop you had A feeding the power pot and B feeding the lighting pot? Wouldn’t that give you counterclockwise rotation?

  • @tedlahm5740
    @tedlahm5740 Рік тому +1

    The lighter designated transformer would typically be LARGER in size
    (more current) than power pot? Open Delta two transformer system?
    Excellent explanation.

    • @hilineacademy8482
      @hilineacademy8482  Рік тому +1

      Yes sir. The lighter pot is carrying all of the single phase load and two phases of the three phase load therefor it needs to be a larger K a pot. 👍

  • @dandisen2643
    @dandisen2643 8 місяців тому +1

    Is it true to say that the Lighter Pot/Power Pot is the same as Open Delta bank? Comparing this video vs the Open Delta Bank video that you made, it appears that both are same connections. Am I understanding this correctly?

    • @hilineacademy8482
      @hilineacademy8482  7 місяців тому +1

      Yes sir. When building a transformer bank that has a 4 wire delta connection on the secondary side (meaning three phases and a neutral) you will have both phase to neutral load, and phase to phase load. The phase to neutral load is referred to as “lighting load”, and the phase to phase load is referred to as “Power load”. The transformer that is supplying the neutral is called to lighter because it is the only transformer supplying the phase to neutral load. That’s why we call it the “Lighter. “ It does not mean that it is lighter in weight. The other transformer / transformers are only supplying the power load, or the phase to phase load. Please let me know if this answered your question.
      Stay safe 👍