Thank you po sir napalinaw po ng pag kaka-discuss nyo sir from BFP po Electrical Engineer by Profession. Sa permitting din po ako application sa FSEC may nilabas pong DILG memorandum circular no. 2016-23 na Naka Address po sa mga governor, mayor at lahat po ng concern sa issuance ng permit saken palang po nirerequire ko na sila ng Electrical Design Analysis, short ckt and voltage drop calculation
Thank you sir for sharing your knowledge to us.. malaking tulong po itu sa tulad nming electrical practitioners I will rewatch this if my nakaligtaan ako Godbless po.
Yes, we can issue webinar certificates. The fee is Php300 per certificate, Pls remit via our GCash, 0998 311 6838 or thru our bank account. A scanned copy of the cert can be sent via email. Shipping/delivery fee is Php150, if you wish it delivered to your address in the Phils. If acceptable, please send your complete name and your address. Thank you and regards. Engr. Juan 0943 0616 215, 0998 311 6838
Hi sir, sobrang salamat po sa video simple at madali maintindihan naging guide ko po siya para sa paggawa ko ng design analysis sa trabaho. More videos po para ma share nyo pa po knowledge niyo sa amin. God bless!
Sir tanong ko lang po, may nagpagawa po kase sa akin ng design analysis nung chineck ko po ung plano overdesign po siya. Ok lang po bang iba ang computation at mga size ko sa ko ng wire at breaker dun sa design analysis kumapara sa plano?
@@danv.600 Dapat, kung anu ang lumabas sa design analysis, yun ang magiging sizes sa final design or sa load schedules/ riser diagrams, layout plans. Kaya nga ginagawan ng design analysis para makonfirm ang correct sizes ng feeders at corresponding circuit protections
Salamat po sa pag sagot sir, madalas po kase naka blueprint na ung plano pag pinapa check sakin ayaw naman pong mag print ng bago kung may kelangan baguhin
@@danv.600 ok nga eh, Kasi dapat pag gumawa Ng design, gawin na din dapat itong SC at VD Calcs para maadjust agad ang load schedule at mga call outs sa risers
Thank you for the informative and technical-specific lecture engr. Will. Tanong ko po sana regarding the voltage drop calculation, if pwede na gamitin 230V as reference as Voltage Supply?
Thank You Po dito sir... Stay safe and God Bless you.. Sir sana, bago pumirma Si PEE sa Electrical Plan, sana hanap sana kng ang nag de design sa plan is PEE,REE or RME. for residential ,small commercial building .. salamat po. more power sayo.
Napaka ganda po sir marami ako natutunan. sir ask ko lang about short ckt calc, what if po hindi na ka connect sa utility, using its own generator? Thank you po.
tanong ko po sana kung paano nyo malalaman kung anong size po ng SERVICE DROP ung gagamitin sa isang residential/commercial building? salamat po sa sasagot
On your sample design, why we need to use one circuit for 10 outlets.. Should we separate this into two convenience outlet circuit to give a better design on voltage drop and such as maintenance purposes. Thanks for advance reply sir
Hi po sir. Ask ko lang po, as tenant po ba kailangan namin ipakita sa design analysis (short circuit calculation) kung anong transformer po kami naka connect? pero naka tap pa lang po kami sa metro ng admin bldg.
Hi Sir Will, bago lang po ako nakapanood ng presentation nyo at maraming salamat po sa pagshare nyo ng knowledge nyo. Tanong ko lang po kung pwede makahingi ng soft copy ng slides presentation po ninyo.
Good afternoon sir, Do I need to do voltage drop analysis for every circuit or... just the voltage drop of the farthest circuits and use those as the basis for the other circuits?
We usually do VD analysis of the farthest branch circuit and the branch circuit which has the biggest load. If these circuits have VDs not exceeding the required maximum value/s, then the shorter circuits or the branch circuits with lesser ampere loads are obviously less than the maximum allowable VD. However in industrial plants, it is recommended to compute the voltage drop of each of the motor circuits, sub-feeders and main feeders, especially if the circuit runs are long.
@@willjac1tv73 When computing load schedules sir, d I need to include the emergency lights? they only consume 40W at most while charging and 5W standby
@@Thedeadsaluteyou their watts load as you say is only 40watts, but you have to use the maximum charging current after its use. This charging load is usually higher than 40watts. Anyway, the alloted design load for an outlet which is 180watts is already enough to cover load of the standard emergency light.
Paano engr. Will kong yong service entrance ko copper hanggang sa poste ko tapos yong utility distribution alluminum # 8 hanggang sa poste ng electric nandoon din yon meter base tapos yong secondary line # 4 paano i calculate yong KAIC yong mga CB.
Sir, tanong ko lang, regarding 24VA per sq.m sa General Lightings and Convenience Outlet, kasi kadalasan sa schedule of loads, 100 VA ung isang lighting fixture and 180 VA yung convenience outlet, So ibig sabihin ba nun pwede ka makalagay ng ilaw na tig 100VA at C.O na 180VA basta wag lang lalagpas sa 1348.32VA n nang galing sa 56.18sq.m X 24 VA?Salamat po
Good day po Sir Wil! Ask kolang po if pwede po kaya makagawa ng free Webinar Workshop Topic in How to Design and Plan a Residential? Thank you so much for your Webinars Sir! More power!
230v is used because the location of the faults in the SC studies is at the main panelboard where the voltage should be 230v. This is to differentiate from the voltage at the secondary of the DT which is 240v and the utilization voltage which is 220v at the terminals of motors or other loads.
Good day po sir. meron lang po ako sanang itatanong regarding induction motor. 1. meron po bang table para malaman ko po ang sub transient reactance for induction motor gamit ang nameplate rating ng motor? Kung sakaling meron po table for it pwede po ba ako makahingi ng copy? 2. can i determine the percent impedance or reactance using the locked rotor current/ampere (LRC/LRA) and its X/R ratio? Sana masagot nyo po ang aking katanungan. Thank you and more powers po.
Yes, we can issue webinar certificates. The fee is Php300 per certificate, Pls remit via our GCash, 0998 311 6838 or thru our bank account. A scanned copy of the cert can be sent via email. Shipping/delivery fee is Php150, if you wish it delivered to your address in the Phils. If acceptable, please send your complete name and your address. Thank you and regards. Engr. Juan 0943 0616 215, 0998 311 6838
Ang concern ko sir is about this ground wire. Ang electric supply natin lalo na sa residential ay dalawa lang wire at walang ground wire. Bakit maglalagay ng ground wire sa mgq motor load
57:07 Voltage Drop Analysis discussion
1:37:43 Short Circuit Analysis discussion
Thank you po sir napalinaw po ng pag kaka-discuss nyo sir from BFP po Electrical Engineer by Profession. Sa permitting din po ako application sa FSEC may nilabas pong DILG memorandum circular no. 2016-23 na Naka Address po sa mga governor, mayor at lahat po ng concern sa issuance ng permit saken palang po nirerequire ko na sila ng Electrical Design Analysis, short ckt and voltage drop calculation
Thank you Sir Will very informative, may natutunan din ako sa mga abogado......
Ganda ng turo nyo sir specially saming mga aspiring electrical designer. Thankyou sa pag she-share sir!
Please share to others
thank you po sir ...very informative...sinusubaybayan ko po mga videos mo...salamat po nang marami.
Pls share to others
Tnaks sir. Wag k po mgsawa mggwa ng mga ganitong video. Malaking tulong po ito sir
Welcome
marami akong natutunan sir! iba talaga mag lecture ang mga veterans sa industry!...thanks
You are welcome!
Salamat sir Will sa presentation mo sana marami pa matoto galing sa yo.
God bless po sir.
You are welcome.. God bless likewise..
Thank you sir, Mabuhay po kayo!
Thank you sir for sharing your knowledge to us.. malaking tulong po itu sa tulad nming electrical practitioners
I will rewatch this if my nakaligtaan ako
Godbless po.
It is my pleasure..
Sir salamat Po sa PAG share ng knowledge mo Po.
God bless you sir ❤️
If you have watch the video, we will appreciate your comments. Thank you.
sir ty po sa inyo, your making our life happier. keepup po the good work, mabuhay kayo.
Salamat
Salamat sir Will sa malaking tulong mo sa kapwa tao mo sana marami pa ang matutulongan mo.
As Gabay ng Dios
Thank you so much for informative lecture sir. I have been searching para maka kuha ng information kasi wala akong matanungan.
This is a great lecture sir. Thank you so much for being a good leader and PEE for all aspirants in the electrical field. This is really a great help.
It is my pleasure..
very informative ,naipaliwanag step by step ,more blessing to you sir
Maraming salamat sir sa presentation nyo napaka informative. More power!
you are welcome!
thank you sir for sharing your knowledge, napakaganda ng presentation nyo, God Bless and more power!
God bless
maraming salamat po for sharing ...mabuhay po kayo and God bless you more
Sir wil gud evning. Thank you so much for a well explained computation of voltage drop and short circuit fault analysis. God bless you more.
Will watch this again, the short circuit analysis is very informative.
Okay, take your time
Thank you for sharing engr. Watching from djibouti africa salamat sir..
You are welcome Ms/ Engineer Geneva..
Keep going and God will always blessed you.
Congrats po sir will ,maraming salamat po marami matutulungan po nito
Thanks Ernie!
Thank you very much sir. Very impormative. Marami ako natutunan sa mga lecture s nyo sir. Galing nyo po mag turo.
Yes, we can issue webinar certificates.
The fee is Php300 per certificate,
Pls remit via our GCash, 0998 311 6838 or thru our bank account.
A scanned copy of the cert can be sent via email.
Shipping/delivery fee is Php150, if you wish it delivered to your address in the Phils.
If acceptable, please send your complete name and your address.
Thank you and regards.
Engr. Juan
0943 0616 215,
0998 311 6838
Thank you po sa presentation. God bless!
Likewise Godbless
Very informative.
Hi sir, sobrang salamat po sa video simple at madali maintindihan naging guide ko po siya para sa paggawa ko ng design analysis sa trabaho. More videos po para ma share nyo pa po knowledge niyo sa amin. God bless!
Likewise God bless...
Sir tanong ko lang po, may nagpagawa po kase sa akin ng design analysis nung chineck ko po ung plano overdesign po siya. Ok lang po bang iba ang computation at mga size ko sa ko ng wire at breaker dun sa design analysis kumapara sa plano?
@@danv.600 Dapat, kung anu ang lumabas sa design analysis, yun ang magiging sizes sa final design or sa load schedules/ riser diagrams, layout plans. Kaya nga ginagawan ng design analysis para makonfirm ang correct sizes ng feeders at corresponding circuit protections
Salamat po sa pag sagot sir, madalas po kase naka blueprint na ung plano pag pinapa check sakin ayaw naman pong mag print ng bago kung may kelangan baguhin
@@danv.600 ok nga eh, Kasi dapat pag gumawa Ng design, gawin na din dapat itong SC at VD Calcs para maadjust agad ang load schedule at mga call outs sa risers
Very Informative. Highly recommended. Very accessible.
thanks
Sir, ano fbpage niyo?
Salamat po
Para din sana makapagpaCertificate Sir. Salamat pong marami.
@@kervyolivo8827 William Jacinto Juan
@@kervyolivo8827 pls send request to wiljjuan.engr@gmail.com
Very informative ..salamat po sir...pang thesis nato sa PEE..
Salamat
I appreciate everything you did. thank you very much,
My pleasure..
salamat dito sir...from north cotabato
galing niyong magpaliwag sir naiintindihan ng husto..
salamat Richard
Thank you for resfreshing us sir Will.. Godbless
God bless
Thank you po Sir sa walang sawang pagshare nyo po ng knowledge :)
Take care always. God bless
Thank you soo much. God bless you
God bless, too
Magaling to c sir wiliam Lodi ko to.. Hindi na ako makapunta sa office mo sir due to covid. Ingat kayo sir.
Okay Naman. Dito na Lang Tayo SA UA-cam
Very informative presentation Sir. More Power. Godbless...
Thank you
Very informative topics sir William, thank you sir! Godbless
You are welcome
Thank you for this very informative lecture sir. More webinars to come, Godbless
Sir salamat po nadagdagan po kaalaman ko GOD BLESS PO
Likewise, God bless..
MARAMING SALAMAT SIR MADAMI AKO NATUTUNAN :)
Thank you sir for sharing the knowledge
You are welcome.
THANK YOU SO MUCH SIR. UPLOAD PA PO KAYO NG MGA VIDEO. LAKING TULONG PO TALAGA SA AKIN TOH. ❤️😊😊
You are welcome!
GOD BLESS YOU ALWAYS SIR.....HEALTHY LONG LIFE SIR
Thank you God bless you too
nice video sir, hingi po sana ako ng presentation nyo,
IF may nalito, copper sa slide is 12.9 and (aluminum = 21.2) :)
Thank you very much sir ...
Hi sir! Thank you for this wonderful presentation :))))))
You are welcome!
gud evening sir. This very informative lecture. Thanks po
You are welcome..
Thank you for the informative and technical-specific lecture engr. Will. Tanong ko po sana regarding the voltage drop calculation, if pwede na gamitin 230V as reference as Voltage Supply?
Sir, thanks po talaga sa presentation
You are welcome!
Very nice topic Sir! Thanks po
Thank You Po dito sir... Stay safe and God Bless you.. Sir sana, bago pumirma Si PEE sa Electrical Plan, sana hanap sana kng ang nag de design sa plan is PEE,REE or RME. for residential ,small commercial building .. salamat po. more power sayo.
ganda at ang linaw po sir..thank you for sharing
Please share to others
Salamat po, Sir Will
Welcome!
SIR SALAMAT NG MARAMI!!! DITO KO LNG PO TALAGA NA INTINDIHAN KUN PANO KUMUHA NG VALUE KAIC SALAMAT SIRRRRRR
You are welcome!
Please share to others.
thank you very much for this video Sir! :)
You are welcome!
thank you...
@@adrianangelobaing9680
Welcome
Good evening po, Thanks for sharing your knowledge.
You are welcome!
Thank you for this informative lecture sir. More power and God Bess :)
Thank you sa magandang topic mo sir will
You are welcome
Please share to your friends
Salamat sir sa webinars niyo
Still watching po sir. Nakapalaking tulong po.
Pls share to others
puede po ba ako Sir Wil mag exam ng master plumber, pero ngayon master electrician po ako. Salamat Sir Wil.God Bless.
@@18pher
We will evaluate, please send your resume via my email, wiljjuan.engr@gmail.com
When we add impedances, we need to break them into R and X..then apply phytagorean theorem sa Rt and Xt to get Zt or total impedance, tama po ba?
Salamat po sir❤
Thank you Sir William
Thank You Very much for this Sir!!
very very informative, thank you sir
Napaka ganda po sir marami ako natutunan. sir ask ko lang about short ckt calc, what if po hindi na ka connect sa utility, using its own generator? Thank you po.
Mababa lang ang short circuit current available pag ang supply ay Galing lang SA MGA generator set
Ah ok2 sir thanks
tanong ko po sana kung paano nyo malalaman kung anong size po ng SERVICE DROP ung gagamitin sa isang residential/commercial building? salamat po sa sasagot
thank po sir webinar
Welcome
Good day sir may i ask at around 2:08:18 when you added the Z values the Zu and Zt are in PU while Zdl and Zse are in Ohms?
Thanks for info.
My pleasure..
On your sample design, why we need to use one circuit for 10 outlets.. Should we separate this into two convenience outlet circuit to give a better design on voltage drop and such as maintenance purposes. Thanks for advance reply sir
The voltage drop is so minimal. But Yes, that is also okay.
Thank You Sir Godbless Ryane Ross Ramos ,REE from Batac Ilocos Norte This presentation is very useful 😊💪 sana ma meet ko po kau personally
Sapay koma.. God bless
May facebook po ba kau sir?
@@rossryaneramos8347 merun, heto, Wjjuanpeermp Mepfs Tte
Sir pa email naman po pdf files for tables and references 😊
Hi po sir. Ask ko lang po, as tenant po ba kailangan namin ipakita sa design analysis (short circuit calculation) kung anong transformer po kami naka connect? pero naka tap pa lang po kami sa metro ng admin bldg.
Hi Sir Will, bago lang po ako nakapanood ng presentation nyo at maraming salamat po sa pagshare nyo ng knowledge nyo. Tanong ko lang po kung pwede makahingi ng soft copy ng slides presentation po ninyo.
Please send your request to wiljjuan.engr@gmail.com
Thank you Sir for this webinar. 👌
Sir, Yung po bang waste water treatment kailangan pa Ng design analysis?
yes
Hello.
In 38 minutes when you have been calculating current, should you consider 3 phase system?
Ask ko lang sir, what if yung subtotal ko hindi lumampas ng 3000, san po ako kukuha ng first 3,000 or 10,000 VA? salamat po sa pagtugon :)
Good afternoon sir, Do I need to do voltage drop analysis for every circuit or... just the voltage drop of the farthest circuits and use those as the basis for the other circuits?
We usually do VD analysis of the farthest branch circuit and the branch circuit which has the biggest load. If these circuits have VDs not exceeding the required maximum value/s, then the shorter circuits or the branch circuits with lesser ampere loads are obviously less than the maximum allowable VD.
However in industrial plants, it is recommended to compute the voltage drop of each of the motor circuits, sub-feeders and main feeders, especially if the circuit runs are long.
@@willjac1tv73 Thank you sir
@@willjac1tv73 When computing load schedules sir, d I need to include the emergency lights? they only consume 40W at most while charging and 5W standby
@@Thedeadsaluteyou their watts load as you say is only 40watts, but you have to use the maximum charging current after its use. This charging load is usually higher than 40watts. Anyway, the alloted design load for an outlet which is 180watts is already enough to cover load of the standard emergency light.
You are welcome
Paano engr. Will kong yong service entrance ko copper hanggang sa poste ko tapos yong utility distribution alluminum # 8 hanggang sa poste ng electric nandoon din yon meter base tapos yong secondary line # 4 paano i calculate yong KAIC yong mga CB.
Kunin mu yung corresponding reactance and resistance ng components sa table, yun ang gamitin mu
Sir, tanong ko lang, regarding 24VA per sq.m sa General Lightings and Convenience Outlet, kasi kadalasan sa schedule of loads, 100 VA ung isang lighting fixture and 180 VA yung convenience outlet, So ibig sabihin ba nun pwede ka makalagay ng ilaw na tig 100VA at C.O na 180VA basta wag lang lalagpas sa 1348.32VA n nang galing sa 56.18sq.m X 24 VA?Salamat po
Paliwanag mo bakit THHN @ 90 C ang br. ckt. conductors in relation to temp rating of protective device, pwede? Ano default temp ng OCPD mo ?
Kasama po ba ang mga maliit n bahay, gaya po ng bahay kubo yang mga requirements n nsabi? Salamat po. From Doha Qatar
Good day po Sir Wil! Ask kolang po if pwede po kaya makagawa ng free Webinar Workshop Topic in How to Design and Plan a Residential? Thank you so much for your Webinars Sir! More power!
Please watch this..
ua-cam.com/video/1vGzzGSgmBg/v-deo.html&feature=share
Thanks po sir
You are welcome!
galing nyo Sir😊
Salamat
Salamat po sir
You are welcome..
Tanong ko lang , Sir. Bakit yung computation ang gamit namin ay 230 volts all thru out.Thanks
230v is used because the location of the faults in the SC studies is at the main panelboard where the voltage should be 230v. This is to differentiate from the voltage at the secondary of the DT which is 240v and the utilization voltage which is 220v at the terminals of motors or other loads.
Salamat po
GALING MO IDOL!!! LONG LIVE!!!
Good day po sir. meron lang po ako sanang itatanong regarding induction motor.
1. meron po bang table para malaman ko po ang sub transient reactance for induction motor gamit ang nameplate rating ng motor? Kung sakaling meron po table for it pwede po ba ako makahingi ng copy?
2. can i determine the percent impedance or reactance using the locked rotor current/ampere (LRC/LRA) and its X/R ratio?
Sana masagot nyo po ang aking katanungan.
Thank you and more powers po.
Thank you sir for very informative video, how we can avail certificate sir?
Yes, we can issue webinar certificates.
The fee is Php300 per certificate,
Pls remit via our GCash, 0998 311 6838 or thru our bank account.
A scanned copy of the cert can be sent via email.
Shipping/delivery fee is Php150, if you wish it delivered to your address in the Phils.
If acceptable, please send your complete name and your address.
Thank you and regards.
Engr. Juan
0943 0616 215,
0998 311 6838
sir, saan mo po nakuha yung 100% sa first 10 kVa load plus 40% of the remainder? sa PEC kasi 100% sa first 3 kVA plus 35% of the remainder
Pwede din yang First 3kw plus 35% of the remainder
Ang concern ko sir is about this ground wire. Ang electric supply natin lalo na sa residential ay dalawa lang wire at walang ground wire. Bakit maglalagay ng ground wire sa mgq motor load
The ground wire is for safety. It keeps the potential of the casing or metallic parts as low as possible.