System Test 5 | Simplex and Smoke!

Поділитися
Вставка
  • Опубліковано 3 гру 2024

КОМЕНТАРІ • 76

  • @SystemFire20lifesafety
    @SystemFire20lifesafety 5 років тому +3

    Hey there’s one of my old TrueAlerts (BTW, it’s not a quick alert. The quick alerts had a different grill design, that’s just an early true alert.) ! Actually really cool that you ended up with it. I actually got that 4903 from One of Western Michigan universities academic buildings. They were doing construction and they gave me 5. I ended up giving one to Zach from BSS, and that’s how you got it. I still have 3 left of my own, and I did a short review video on it.

  • @jessicahowe1838
    @jessicahowe1838 5 років тому +2

    Great system test! Love the activation with the sparkler

  • @micahbreland
    @micahbreland 5 років тому +1

    Great Video!
    This is my favorite series you do!

  • @firesignz2804
    @firesignz2804 5 років тому +3

    Awesome! You should try using those sparklers more often haha. Really enjoyed this one!

    • @ExitSign250
      @ExitSign250  5 років тому +1

      I’m glad you liked it! I’ll try to use those sparklers often.

  • @ncalarms6022
    @ncalarms6022 5 років тому +2

    Gotta love FWR. I’d recommend trying to look for a NAC power supply (FCPS). Usually, they aren’t too expensive.

    • @ExitSign250
      @ExitSign250  5 років тому +1

      I would, but there is no room for it on the demo boards.

  • @firealarmdiscovery
    @firealarmdiscovery 5 років тому +1

    I just love this channel

  • @nm4fsv684
    @nm4fsv684 5 років тому +1

    Cool man! Love the boards!

  • @ElectronicsHikingandJesusTalk
    @ElectronicsHikingandJesusTalk 5 років тому +1

    Cool! Now we know why Sparklers are to stay outside!

  • @WheeloveFireAlarms
    @WheeloveFireAlarms 5 років тому +1

    Awesome! This was a fun video!

  • @TheDeadman4093
    @TheDeadman4093 Рік тому

    I kinda figured that the simplex alarm on the right would sound like the one ser safety has, but it kinda sounds like an alarm clock

  • @frankspliff7037
    @frankspliff7037 3 роки тому

    Very interesting setup 👍

  • @Critical311
    @Critical311 5 років тому

    Great video! What model truealert is that?

  • @ElCalamardo69
    @ElCalamardo69 5 років тому

    Very neat! Keep up the great vids 👍

  • @Venturafirefanatic
    @Venturafirefanatic 5 років тому +2

    Nice video! I subbed and liked

  • @fst1775
    @fst1775 5 років тому

    cannot wait for u to upload another vid! your channel is awesome!! :D

  • @FireAlarm33
    @FireAlarm33 4 роки тому

    You can use a True Alert on a 5ud?

  • @EVGSTORE
    @EVGSTORE 5 років тому +2

    can you do a upside down system?, where everything (pull stations and fire alarms) are upside down, and swap the pull stations with the smoke detectors?!?!? that would be amazing!!

    • @ExitSign250
      @ExitSign250  5 років тому

      Maybe one day, as like a joke video.

  • @WilmingtonOHProductions
    @WilmingtonOHProductions 5 років тому

    Awesome and I have 2 older Simplex devices a 2901-9838 and a 4251-20 that needs a new button

  • @Fireandsecuritykid
    @Fireandsecuritykid Рік тому

    You should’ve done that for New Year’s😂

  • @fst1775
    @fst1775 5 років тому +1

    really neat system, can you make a video on how you wire the pull stations, panels and alarms all together? :)

    • @ExitSign250
      @ExitSign250  5 років тому

      Thanks! Like how to basically wire fire alarm systems?

  • @evanbart4109
    @evanbart4109 5 років тому +1

    Great video 😀👍👍
    I couldn’t tell whether it was the Simplex Alarms on FWR, my headphones, and/or something audio related on your end, but the alarms sounded really scratchy. Keep up the great work and thank you!😉

    • @ExitSign250
      @ExitSign250  5 років тому +1

      Thanks! I appreciate it! I think was a mix of FWR and my volume. I’m in the process of getting a relatively stable audio system for filming.

    • @evanbart4109
      @evanbart4109 5 років тому +1

      ExitSign250 Okie Dokie! Thank You

  • @BousaiGuy
    @BousaiGuy 5 років тому +1

    Great system test! =]

  • @djifirealarms
    @djifirealarms 5 років тому

    Cool! I might get a t bar soon.

  • @electricalsmokealarmsandmo1564
    @electricalsmokealarmsandmo1564 5 років тому

    Can you do a video on how to wire a addressible fire alarm system.

  • @Gavinsgamer
    @Gavinsgamer Рік тому

    I have the same white Simplex alarm but I have the TrueAlert

  • @kenifedy
    @kenifedy 5 років тому

    Awesome video

  • @vintagefirealarmguy5285
    @vintagefirealarmguy5285 5 років тому

    Awesome video 😊👍👍

  • @FireRescue80
    @FireRescue80 5 років тому +1

    Nice system. New subscriber btw.

  • @FireAlarmDude5967
    @FireAlarmDude5967 5 років тому

    Love it!

  • @blairshears1121
    @blairshears1121 3 роки тому

    how did you wire the simplex smoke alarm to a addressable fire lite panel i have the same one but it does not work with my fire lite es-50

    • @ExitSign250
      @ExitSign250  3 роки тому

      To wire conventional initiating devices to addressable panels, you must use a monitor module. My monitor modules are above the MS-9200UDLS panel. They look like square plates with a blinking light on it. Some other brands may have different looking ones but they all have the same general function.

    • @blairshears1121
      @blairshears1121 3 роки тому

      @@ExitSign250 oh I understand i have a simplex 4098 9754 and it does not work with my panel

  • @pvh_facp4001yt
    @pvh_facp4001yt 5 років тому

    Very cool!

  • @calebmorand4604
    @calebmorand4604 5 років тому

    Is the simplex smoke detector wired to a monitor module? Thanks

    • @ExitSign250
      @ExitSign250  5 років тому

      It is. That’s the only way conventional devices work with addressable systems.

    • @calebmorand4604
      @calebmorand4604 5 років тому

      @@ExitSign250 how you wired it was wiring resettable power to the resettable power terminals of the module, the smoke detector to the zone on of the module, and the SLC to the slc terminals? Thanks

  • @TheKappaDOS
    @TheKappaDOS 8 місяців тому

    Why is it so scratchy?

  • @ntekniklaus3710
    @ntekniklaus3710 5 років тому +1

    I really hope you’re not directly wiring those to the panels and using FWR

    • @ExitSign250
      @ExitSign250  5 років тому +1

      Yep, they are directly wired to the panel’s NACs. (FWR) I don’t personally believe in the whole “don’t run Simplex devices on FWR” stuff because I’ve done it for years and nothing has ever happened.

    • @ntekniklaus3710
      @ntekniklaus3710 5 років тому +1

      ExitSign250 just be careful with the quick/truealerts please. it would suck if those broke

    • @ExitSign250
      @ExitSign250  5 років тому +1

      The devices aren’t effected by the FWR, and it certainly won’t break them.

  • @pentiumman3338
    @pentiumman3338 Рік тому

    What is that cover on the vent for?

    • @ExitSign250
      @ExitSign250  Рік тому

      It directs the air away from the smoke/heat detectors. The air from the vent can make it difficult to test the detectors so the vent cover redirects it away from them.

    • @pentiumman3338
      @pentiumman3338 Рік тому

      @ExitSign250 very cool!

  • @Thunderbolt1003
    @Thunderbolt1003 5 років тому

    Sweet!

  • @Extremely_crazy_toaster_light
    @Extremely_crazy_toaster_light 2 роки тому

    The quickalert sounds like a sheep doing code 3

  • @mrexitsign2024
    @mrexitsign2024 Рік тому

    One of my olds schools had a quick alert and same horn delay

  • @FireTech7
    @FireTech7 5 років тому +1

    That truealert omg that thing is loudddd

  • @EVGSTORE
    @EVGSTORE 5 років тому

    nice video

  • @dale4231
    @dale4231 5 років тому

    Your microphone seems to be having trouble with the sound of those alarms.

    • @Aaronproductions
      @Aaronproductions 5 років тому

      The iPhone/iPad or whatever that he’s using that is connected to his microphone can only handle a very low level line input, so it’s probably that the level is too high and the internals on the device start to clip. I use a TRS to TRRS converter to use the mic input to play music via a 3.5mm cable while I’m streaming and if the volume on the other phone playing the music is over half then the mic input will start clipping and causing the audio to have the same effect. I think it has to do more with the levels and that his microphone is completely fine.

    • @dale4231
      @dale4231 5 років тому

      Aaron Productions ok thanks for the explanation!

    • @ExitSign250
      @ExitSign250  5 років тому

      Actually, the issue with the sound is due to I face my shotgun microphone away from the devices and facing me. If I were to face it towards the alarms, you wouldn’t be able to hear me much. I’m in the process of getting a mic to attach to me, then have the shotgun mic faced towards the alarms. That way audio from both ways is equal.

    • @Aaronproductions
      @Aaronproductions 5 років тому

      ExitSign250 make sure you get a powered lav

    • @QuikCall4623
      @QuikCall4623 5 років тому

      Dale Nuss Because these Alarms are using FWR (Unfiltered DC) which makes the alarms sound raspy.

  • @Ilikefirealarm-yl2lm
    @Ilikefirealarm-yl2lm Рік тому

    My school has simplex fire alarm

  • @alfaalcala2766
    @alfaalcala2766 10 місяців тому

    Finland 🇫🇮

  • @Liam-and-Kitties
    @Liam-and-Kitties 2 роки тому

    Reset😅

  • @WilmingtonOHProductions
    @WilmingtonOHProductions 5 років тому

    Sounds bad on FWR

  • @safetyzone2962
    @safetyzone2962 5 років тому

    1st

  • @electricalsmokealarmsandmo1564
    @electricalsmokealarmsandmo1564 5 років тому

    Can you do a video on how to wire the switch.

  • @petuniaskunk2316
    @petuniaskunk2316 5 років тому

    1st