Sir, How many amps can be drawn in each core of a 1.1KV 3.5 c x 185 Sq.mm Al XPLE cable when it is laid out in air , because cable chart showing current carrying capacity for 1 core 185 Sq.mm and 3.5 c 185 Sq.mm is same
The chart shows the current carrying capacity only. The actual capacity shall be find out using derating factors in this case grouping, ambient temperature, and laying condition. Apart from this the length of cable shall also be considered for voltage drop(max allowable 5%)
Electrical Simplified thanks . Since the cable termination has one side at Acdb aluminium busbar and one side copper busbar TERMINAL inside inverter , the aluminium pin type lugs have burned twice , 1) can I use copper lugs at this al cable at TERMINAL (inside inverter side ) instead of aluminium lugs ? 2) or do I have to put bimetallic lugs here 3) or do I have to make separate a busbar box before termination at terminal and use 35sq mm CU cable btw terminating at terminal (inside inverter ) and newly created busbar box 📦 and other side existing AL cable can be terminated at new busbar (which acts as intermediate ) ,
Please read the reply. 1. Using cu lug in aluminum cable is not advisable. 2. Bimetallic washer can be used and advisable. Cable terminations shall be properly tighten with connections bolts. 3. Intermediate JB's can be used. In many cases it is useful where the terminals are not suitable for larger size cable terminations. Thanks
@@electricalsimplified4382 sar thoda kanfusen ho raha he cable ko pachane me aap pliz ak video banao PVC xlpe sqyar mm ground duct air ka kya matlab he
Very informative video...good job
Ek dam Badiyaa jankari Di hy sirji...
loved this video. Very simple language used and detailed explanation is made. I have noted everything in my book. Thankyou. Keep up the good work and keep posting more videos.
Thanks for your comments.
East and west
Electrical engineering always best
Very informative. Nice job. Keep it up👍🙏
Thanks sir
superb , Sir please do video cable design its my request
Nice information. Keep it up.
I like that nice job... cabile joint ke bareime video banaie...
Nice video
Bahut hi behtreen video bnaya hai aapne aur sabse achhi baat hai ki aapka samjhnae ka andaaz bahut hi accha hai...Mujhe cable ke bare me aur bhi details maloom karna tha like Single core cable, Difference between HT and HV cable,Multipair cable etc...
Aaapse kaise contact karun?
Very nice sir. upload more electrical videos plzz
Sure will upload shortly
Which certification is used in cable industries.
IS7098 is for XLPE cables.
WHICH CABLE IS USE FOR 7.5HP MOTOR
3cX 6 copper cable. Or 3cx16 al cable
Aapane Jo bataya Lal ka video kahan per milega
Nice topic sir
Thanks mumtaj.. you can demand on your topic also. I will try to provide.
nice video sir
Thankyou Alam ji
Sir, How many amps can be drawn in each core of a 1.1KV 3.5 c x 185 Sq.mm Al XPLE cable when it is laid out in air , because cable chart showing current carrying capacity for 1 core 185 Sq.mm and 3.5 c 185 Sq.mm is same
The chart shows the current carrying capacity only. The actual capacity shall be find out using derating factors in this case grouping, ambient temperature, and laying condition.
Apart from this the length of cable shall also be considered for voltage drop(max allowable 5%)
Electrical Simplified for a length of 120mtrs aluminium cable 3.5C 50sq for max 100A current , is 50sq ok or do in have to put 95sq ????
Hi A streak,
For current 100A, and length 120 M
3.5C×100 is ok. But i suggest one size higher 3.5CX70 Sqmm.
Electrical Simplified thanks .
Since the cable termination has one side at Acdb aluminium busbar and one side copper busbar TERMINAL inside inverter , the aluminium pin type lugs have burned twice ,
1) can I use copper lugs at this al cable at TERMINAL (inside inverter side ) instead of aluminium lugs ?
2) or do I have to put bimetallic lugs here
3) or do I have to make separate a busbar box before termination at terminal and use 35sq mm CU cable btw terminating at terminal (inside inverter ) and newly created busbar box 📦 and other side existing AL cable can be terminated at new busbar (which acts as intermediate ) ,
Please read the reply.
1. Using cu lug in aluminum cable is not advisable.
2. Bimetallic washer can be used and advisable. Cable terminations shall be properly tighten with connections bolts.
3. Intermediate JB's can be used. In many cases it is useful where the terminals are not suitable for larger size cable terminations.
Thanks
Nice topic
You can suggest also for better topic
hello sir how we can measure derating factors i.e ambient, grouping, spacing
please share simple formulas of these factors
Share your mail id.
zeeshanhyder688@gmail.com thanks in advance sir
Cable me ground ducts air ka kya matlab he
HT LT cable ke size ke bare mein bataiyel ke bare mein bataiye
هذا كابل الومنيوم 00 3جهدkv 6/10 سمك العزل 3،2
Electric software mangta hai tum bole to nahin hai kahan per milega
4 wire what use
Four wire is for 3 phase neutral applications like power and lighting requirements.
Control cable kise kahte hai sir
Cable me mm condekter ka aata he ya puri cable ka
Only conductors ka.
@@electricalsimplified4382 sar thoda kanfusen ho raha he cable ko pachane me aap pliz ak video banao PVC xlpe sqyar mm ground duct air ka kya matlab he
Insulation screen ka use and usko earth kaise Krte hain ?? Pls reply