    A pressure-balanced trim uses the process pressure to balance the static pressure acting on it, while unbalanced trim takes the full force of the process fluid.
    Unbalanced trim: There is no balance hole on the plug, the medium pressure differential acts on the effective area of the plug to generate a force equal to the product of the differential pressure across the plug and the plug’s area (F = PA). However, balanced plugs do not generate this same force because they equalize the pressure on both sides of the plug.
    Unbalanced trim control valves are suitable for applications where the pressure difference is not large.
    Balanced trim control valves are suitable for applications with large pressure differences.
    You can learn more about these in the below technical paper by Valtek
    pro-quip.com/i...
    Unbalanced trim design generally requires that the direction of flow should assist the motion of failure, for example, flow-over for fail-closed and flow-under for fail open.
    Pressure-balanced trim design generally requires that the direction of flow be opposite to standard (unbalanced) trim to oppose the motion of failure for example, flow-over for fail-open and flow-under for fail-closed

КОМЕНТАРІ • 26

  • @AsadPassionateEngineer
    @AsadPassionateEngineer  Рік тому

    🔴Link to Instrumentation Crash Course for Professionals (FREE course)
    1500+ Students have already taken this course.
    👉asad-shaikh-instrumentation.ck.page/06e66ac455
    Students have said to make the course course PAID ( Because of the value they received from the course)
    Let me know your feedback

  • @balajiarni
    @balajiarni 2 роки тому +2

    Good Content. Had a feel of spent valuable time by watching this video. Video Sound are clear

    • @AsadPassionateEngineer
      @AsadPassionateEngineer  2 роки тому +1

      Thank you so much Balaji, your comments really motivate me to work 10 fold more to produce such videos
      I really appreciate you taking out the time to watch these videos !! 😊
      Please also let me know i there are some specific topics you would love to see videos on. I will specially work on those !!

  • @divyeshjain56
    @divyeshjain56 Рік тому +4

    Also in slurry application you must avoid a balanced trim design as it might get choked and also possible to dislocation of valve stem

  • @mohanramgunasundaram1568
    @mohanramgunasundaram1568 2 роки тому +2

    It’s it good we are getting videos on non Saturdays 🎉

    • @AsadPassionateEngineer
      @AsadPassionateEngineer  2 роки тому +1

      Most welcome, so glad to know you are finding these efforts valuable!!! 😊

  • @swaminnathan1
    @swaminnathan1 2 роки тому +1

    Excellent refresher....

  • @ankurbhatnagar3241
    @ankurbhatnagar3241 2 роки тому +2

    Nice one Asad

  • @manumani903
    @manumani903 Рік тому

    My vendor used a blanced trim for a dp actuator sizing in 10bar and dp at max flow is 0.7 .is this is correct? Or to use unbalanced trim

  • @prafuldethe3489
    @prafuldethe3489 Рік тому

    Is there chances of leakage in stem side in case of balanced trim as pressure will also be acting upwards.

  • @milindketkar9059
    @milindketkar9059 Рік тому +2

    Normally we used pressure balanced trim when DP actuator was very high. Quite often very low pressure drop and large flow of say steam makes it difficult for an actuator to shut fully tight. Solution is pressure balanced trim or else use of electrical or hydraulic actuator instead of pneumatic actuator. Typical application are turbine bypass PRDS and spray water control valve with very low DP but very high inlet line water pressure.

    • @AsadPassionateEngineer
      @AsadPassionateEngineer  Рік тому +1

      Thanks for such an insightful comment ..... and sharing your knowledge Milind !! 😊

    • @cck1496
      @cck1496 Рік тому +1

      Thanks. Would you kindly elaborate "how low pressure drop and high flow steam makes it difficult for actuator to shut fully tight".... Thanks.

  • @cck1496
    @cck1496 Рік тому

    Good video. What is the purpose of "cage" in the valve?
    Thanks.

    • @AsadPassionateEngineer
      @AsadPassionateEngineer  Рік тому +1

      I am planning a separate video that cover the difference between plug guide and cage guided . I hope that would help to answer your question

    • @cck1496
      @cck1496 Рік тому

      @@AsadPassionateEngineer Thanks, eagerly waiting for that.

  • @mohammednizamuddin5613
    @mohammednizamuddin5613 10 місяців тому

    May I know the high dp range?

  • @saquibkhan1230
    @saquibkhan1230 7 місяців тому

    Please make a video control valve seat leakage calculation.

    • @AsadPassionateEngineer
      @AsadPassionateEngineer  5 місяців тому

      As requested the video is ready Saquib. Here is the Link to the Video : ua-cam.com/video/j7Ew0JYoMpo/v-deo.html

  • @instrumentwave5720
    @instrumentwave5720 2 роки тому

    Excellent.

  • @balajiarni
    @balajiarni 2 роки тому +1

    Again Saturday video, is that we can say DIWALI DAMAKA

  • @anand9152
    @anand9152 Рік тому