Paralleling the Genmax 9K, Duromax 9K and Predator 9.5K

Поділитися
Вставка
  • Опубліковано 25 жов 2024

КОМЕНТАРІ • 99

  • @CubNole
    @CubNole Рік тому +1

    You are the Generator King, thanks for the videos!

  • @yvonnecates511
    @yvonnecates511 2 роки тому +1

    @Gavin's Garage. You are a wealth of knowledge. Thank you sir!

  • @felaxchow207
    @felaxchow207 2 роки тому +5

    A very good catch on the DuroMax parallel kit no neutral issue. From what I can tell at 1:15 it looks like it is really meant for 250 volt use only and there shouldn't be a neutral pin on the 30 or 50 amp connection. Standard nomenclature if it was to be utilized in split phase mode it should be 125/250. My experience working in the electrical field when your 125/250 volt 50 amp plug tester is showing open neutral is bad news from the get go and you will end up frying up some 120 volt appliances.
    You can bond the neutral and ground at the parallel box, but the ground is only meant to carry fault current back to the generator to trip the upstream breaker to clear the fault and not the unbalanced load between the phases. Also, it will cause a potential shock hazard since no one would expect any current flowing through the ground connection.
    I think DuroMax dropped ball on this one for not having a dedicated neutral for 125/250 volt split phase operation. Great work and it might've save someone's RV from a potential electrical nightmare using the parallel kit. I've went through a few old school hard knocks and learned to test and verify before plugging in. Having a Power Watchdog inline to serve as extra insurance against those costly oopsies.
    After all we are human and we're not infallible. :-P

    • @GeneratorReviews
      @GeneratorReviews  2 роки тому +1

      Thanks for sharing this Felax Chow very insightful and informative feedback. Most people don’t understand why I always have the surge protector on all my test. I’ve seen poor connection, reverse connection, open grounds, open neutral, you can’t just trust the manufacturers to deliver a fault free product.
      Thanks for watching
      I hope I earned your subscribe 👍🏾

    • @felaxchow207
      @felaxchow207 2 роки тому

      @@GeneratorReviews oh yes, I've hit that subscribe button quite awhile ago. Learned a lot and getting good ideas on projects along what pitfalls you might run against.
      I am in the process of designing my electrical system for my class B upfit. What I have on paper is 1 kW solar and 15 kWh lithium storage at nominal 52 VDC. The further into the rabbit hole I get into, I am starting to go with Victron Energy gear and I might get their isolation transformer to electrically separate the shore power connection as extra insurance.

    • @wow1022
      @wow1022 2 роки тому +1

      i think you could pluck a neutral off the 30A twist socket and run a neutral wire from each generator and parallel the neutrals into the 50A plug on the kit... not that hard of a modification and annoying you have to do that... but it's possible

  • @VidJunkie63
    @VidJunkie63 2 роки тому +1

    In your (or the readers here) opinion, is it better to go with two smaller capacity portable generators in parallel, or one large capacity portable generator to perform a whole house back up power solution?

  • @GalloPazzesco
    @GalloPazzesco 2 місяці тому

    Gavin, you are DA MAN!

    • @GeneratorReviews
      @GeneratorReviews  2 місяці тому +1

      Thanks man!

    • @GalloPazzesco
      @GalloPazzesco 2 місяці тому

      @@GeneratorReviews i'm pretty sure they still have a 50 Amp parallel kit in some of the HF stores. I'll try to get a part number for you Gavin. SKU 58374 and ouch I just now realized that I've been exceeding the recommended limits (2x5500 watts) for that kit .... ruh roh. Now I have to regroup.

  • @garden-queen2393
    @garden-queen2393 2 роки тому

    Great parallel video. Thanks 👍

  • @wingloading
    @wingloading 2 роки тому

    I'm a Duromax parallel kit user -- single generator but I added the kit as insurance against a 30amp breaker tripping while feeding my home. Most of my load side neutral current seems to return on the utility neutral, so I weighed disconnecting the kit's ground terminal. When I disconnected the ground, I have a couple of computer UPS units which did not react well by constantly cycling back and forth on battery. The batteries probably pick up something not right with the effective ground, so that leaves me with depending on the generator's bonded neutral to keep working. For standalone or separately derived, this is not an ideal solution. Also I believe if the neutral and ground were bonded on the load side, that #8 ground wire might be a bit under spec.

    • @GeneratorReviews
      @GeneratorReviews  2 роки тому +1

      Hey Jim
      There is a fix you can add a neutral wire to your parallel kit and you should be using number 6 wire.
      If you’re powering an RV or a transfer switch you want to be bonded, if you’re using an interlock kit you do not want to be bonded but you have to add a ground.
      That’s probably why your UPS are acting funny.
      Thanks for watching

  • @PRIME_ATE
    @PRIME_ATE Місяць тому +1

    Can this kit be used for the 9500 inverted Duramax generator??

  • @Caguzzi
    @Caguzzi Рік тому +1

    Which unit do you prefer out of the three? Genmax, Duromax or Predator. Trying to decide between one of these or the Duromax 1300. Thanks!

    • @GeneratorReviews
      @GeneratorReviews  Рік тому +1

      I prefer the GenMax dual fuel, 50 amp plug and it’s the only one with oil filter screening plus so many more features

  • @jmyers4006
    @jmyers4006 Місяць тому

    Thanks for all your videos. They have been super helpful. New subscriber. Is there any advantage to getting 2 4500 watt generators as opposed to one 9000. If one goes you’d still have half the power?

  • @Tom-In-Ga
    @Tom-In-Ga 2 роки тому +1

    Can't help but wonder why Duramax didn't provide the neutral connection. Could you use a bonding plug on the Duramax?

    • @GeneratorReviews
      @GeneratorReviews  2 роки тому +1

      Since there’s no actual cable going to the parallel kit The bonding club would be useless

    • @Tom-In-Ga
      @Tom-In-Ga 2 роки тому

      @@GeneratorReviews Yeah, I guess you're right. I was thinking if you plugged a bonding plug in L1 and L2 of the 120v outlets, it might work. But there's no wire to the kit so how could it? See, that's why you have a great YT channel and I just watch.😉

  • @michaelslack6891
    @michaelslack6891 Рік тому +1

    Hey Gavin! Thank you again for the great information! I have a question maybe you can help me with. I have 2 Duromax xp9000ih's and the Duromax 240 volt parallel kit that I will be using for emergency power to my main panel via 50 amp inlet box and interlock kit on the main panel. I have not tried them yet as I am still breaking them in. Do you think I will have a problem tripping my 3 GFCI circuits in the main panel because of the lack of seperate neutral wires on the generators and parallel kit? Thanks for your time and knowledge, Mike

    • @GeneratorReviews
      @GeneratorReviews  Рік тому

      I haven’t tried it yet but I think you should definitely try your setup before needing it in a real power outage. Let me know the results

    • @barryhagan9742
      @barryhagan9742 3 місяці тому

      It will work as long as you maintain the neutral bond on the generators. No respectable electrician will say this is is a good setup, but it will work. Since there is no neutral connection between the generators and the kit, your neutral is created using the ground wiring between your panel and the generators. This is completely against electric code, but it works. And it works because there are two neutral bonds. 1 in your panel and again at the generators. So what happens here? The missing neutral is effectively jumperer to the ground wiring. Unbalanced current between your 120V circuit legs in the house is going to flow on the ground wiring between your panel and the generators.

    • @michaelslack6891
      @michaelslack6891 3 місяці тому

      I ended up unbonding the generators easily and added neutral wires to the parallel kit which I plug into the 30a on the front panel. All surge protectors, afci and gfci breakers and plugs in the house run perfectly. Thanks for the videos! Mike in DFW

  • @bdkbdk8005
    @bdkbdk8005 3 місяці тому

    So does paralleling the generators give you double the power?

  • @menolose123
    @menolose123 10 місяців тому

    If you had to pick one , which one would you pick ?

    • @GeneratorReviews
      @GeneratorReviews  10 місяців тому

      My first choice I think because of the 50a plug and the fact that I don’t have to have a parallel kit would be the Genmax second choice would be Duromax.
      They both have displays, dual fuel and remote start.

  • @bandit5936
    @bandit5936 2 роки тому +1

    Is it true that the Duramax has a CO2 shut off so if I have it my barn it won't keep shutting off do you know about that thanks

    • @GeneratorReviews
      @GeneratorReviews  2 роки тому +1

      It has a CO monitor shut off if you put it in the barn it will shut off the generator

  • @egravelfl
    @egravelfl Рік тому

    Thanks for your video! I bought a DuroMax XP12000EH about 2 years ago and got to put it through its paces last Oct after hurricane Ian. It worked great though I suspect that I lost a few electronic equipment either because it caused a power surge or FPL did when they restored power to my home. I wish I had known about potential power surge issues with generators way back when I bought this. From one of your other videos, I saw that I should replace my generator with an inverter generator to condition the power's sine wave (prevent surges). I've been considering the DuroMax XP9000iH but after watching your (this) video regarding the parallel kit; I'm not sure.
    You showed that the DuroMax parallel kit does not have a neutral wire. And you stated at around 3:19 that if you use a surge protector in your home that it won't work. What won't work? What's the impact of running this generator if there's no neutral. I'll admit that I don't fully understand that statement. Dammit Jim, I'm a Software Architect, not an electrician! :) Could you expand on this for me please?

    • @GeneratorReviews
      @GeneratorReviews  Рік тому

      The surge protector needs to see a bonded neutral to ground in order to work properly

    • @egravelfl
      @egravelfl Рік тому

      @@GeneratorReviews So this generator, or at least when used with the parallel kit, is not meant to be used in back feeding a whole house. Is there a way to make it compatible? If not, what inverter generator can be use for such application that provides at least 9000 Watts? Thanks.

  • @alanmarbaker7478
    @alanmarbaker7478 2 роки тому +1

    Is the genmax 50 amp plug on a 50 amp breaker so you can take advantage of all the amps available when connected in parallel? Or is it a 35 amp breaker so it only gets the max of 1 generator?

    • @GeneratorReviews
      @GeneratorReviews  2 роки тому +1

      It’s a 50 amp breaker.

    • @GeneratorReviews
      @GeneratorReviews  2 роки тому +1

      That’s why when I use it solo by itself I usually use a 30 amp four pin
      30a x 240v= 7200

  • @campbellsoup4910
    @campbellsoup4910 2 роки тому

    Hey G'
    Very informative vid👍🏾

  • @defjamsgreen
    @defjamsgreen 2 роки тому

    Great generator split phase connecting video .Keep us preppers informed of how they are wired in parallel to get the most power out of them . 😉🤙

  • @melvinhanson3659
    @melvinhanson3659 2 роки тому

    When you use these generators on your home is there a transfer switch that negates the bonded neutral or will I need to umbind it at the generator? If that’s the case then you want to use it for your rv do you have to rebond it?

    • @GeneratorReviews
      @GeneratorReviews  2 роки тому

      The transfer switch and the Rv both require a bonded generator but the inlet box is the only one that has to be a floating neutral generator.
      I hope this helps
      Thanks for watching and subscribing 👊🏾💯

  • @shanwar9844
    @shanwar9844 2 роки тому

    The second genmax sounds like the starter solenoid doesn't release the starter properly. It's hung up on the flywheel for a bit. What's your take on that?

    • @GeneratorReviews
      @GeneratorReviews  2 роки тому

      After watching it again sounds like I should’ve turned the choke a little sooner but since I had the camera in one hand

  • @davidsimon6011
    @davidsimon6011 2 роки тому

    Hi Gavin....:) Questions....? I have a Westinghouse 4500 dual fuel inverter generator for running my 30amp Rv, I also have a 50amp surge protector with a pigtail because I'm running power from a 50amp pedestal circuit. I have a soft start for my A/C as well. Does this generator have a neutral so I can use my 50 amp surge protector inline with my generator? I haven't tried running it yet with my RV. Hope this makes sense I'm a little nieve to some of this....;) Thanks

    • @GeneratorReviews
      @GeneratorReviews  2 роки тому

      You just need a bonding plug for your generator and you can and should always use a surge protector
      amzn.to/3xtXjwv

  • @banhvo4958
    @banhvo4958 8 місяців тому

    Hi Galvin, i had predator 9500 and genmax 9000iedc,both set on floating neutral for home backup through 50amp inlet, do i need to use bonding plug to make it bond neutral before parallel these 2 generator generators ? Or just leave it floating neutral?

    • @GeneratorReviews
      @GeneratorReviews  8 місяців тому

      The only time we have to worry about bonded is when you’re trying to use a surge protector or charge an EV car

    • @banhvo4958
      @banhvo4958 8 місяців тому

      Thank you, i have to connect neutral on both generator although it's floating ?

  • @vipseat
    @vipseat 2 роки тому

    Between the Genmax 9000 and Duromax XP12000EH, which would you recommend for a 2000 square foot home?

    • @GeneratorReviews
      @GeneratorReviews  2 роки тому +1

      The Genmax 9000 is an inverter generator and would provide pure sine wave power to your home and would be quieter.

  • @RShivesy
    @RShivesy 2 роки тому

    You gotta charge money for watching these videos as we all are learning so much.😁
    Where is the link to that Progressive Industries 50amp lighted plug? Nice asset to have.Thanks Gavin

    • @GeneratorReviews
      @GeneratorReviews  2 роки тому

      Thanks 😊
      Find that thanks button and sponsor a video 👍🏾

  • @MrCam3565
    @MrCam3565 2 роки тому +1

    is it possible to make your own parallel plug for the predator or duromax like meeting the two 240v plugs together and still get the 50 amps? and if its possible would you make one and show how you did it and do a second part to this video?

    • @GeneratorReviews
      @GeneratorReviews  2 роки тому +6

      Yes that is a possibility and yes I can show how to make it great idea by the way💡👍🏾

    • @mikek8229
      @mikek8229 2 роки тому +1

      I'd really like to see a video in on that too

    • @tomroth2634
      @tomroth2634 2 роки тому

      I would love to see that!

    • @Rk-mt4ll
      @Rk-mt4ll 2 роки тому

      Yes, Mine is working great. Check out the diagram on post 123
      www.powerequipmentforum.com/threads/duromax-xp9000ih-pk-parallel-box-question.25478/page-7#post-96403

  • @code3k5
    @code3k5 2 роки тому

    now i want 2 genmax ;)

  • @wow1022
    @wow1022 2 роки тому +2

    this is dangerous AND BE CAREFUL ABOUT ANY MODIFICATIONS, current is NOT supposed to flow through the ground during normal operation... DO NOT plug the parallel kit into your home without paralleling the neutral from each generator into the neutral of the 50A socket on the parallel kit.... use #8 stranded wire MINIMUM for your neutral as each generator puts out 30A and #8 is good for 40A continuous, you can get a neutral off the 30A twist socket by wiring a custom plug

  • @redfule
    @redfule 2 роки тому

    Very good 👍 what are the prices of the Duramax and the Genmax

    • @GeneratorReviews
      @GeneratorReviews  2 роки тому +1

      Check out the links in the description I have all the prices and the links to them

  • @aronlichtman
    @aronlichtman Рік тому

    If i connect 2 genmax 9000 can i get 62amps?

    • @GeneratorReviews
      @GeneratorReviews  Рік тому

      You will get 12500 watts at 52 amps 240v

    • @aronlichtman
      @aronlichtman Рік тому

      @@GeneratorReviews but the 50amp breaker will trip by 50amp how can I get the full power?

  • @MikeMike-is2hl
    @MikeMike-is2hl 2 роки тому

    Is there a parallel kit with 120/240 ? I would like to pair 2 inverters to power my house... looking for a pair that will give me at least 12K watts. Is there any combo that will give me that ?

    • @GeneratorReviews
      @GeneratorReviews  2 роки тому

      They do have a few but brand specific the Honda and Duromax both has a 120/240 kit I haven’t found a universal One yet

  • @ryanyoshimura
    @ryanyoshimura 2 роки тому

    So if I use this parallel kit that has no neutral and plug to my house inlet, do I still need remove the bonded neutral in the generator?

    • @GeneratorReviews
      @GeneratorReviews  2 роки тому

      Great question
      You shouldn’t have to since the neutral is not bonded but you still running all that power on one ground

    • @barryhagan9742
      @barryhagan9742 3 місяці тому

      Do not remove the bonded neutral when using Duromax kit. That is the only way the unbalanced current from your 120V home circuits is returning to the source. If you float the neutrals, there is no path for that unbalanced current, so it will flow on the hot 120V legs and cause over/under voltage on your home circuits. The severity of that over/under voltage depends on how unbalanced the loads are. Every time you turn something on or off in the 120V home circuits you will be changing that imbalance.
      These kits should not be sold without neutral wiring. It is irresponsible how they were allowed to sell them.

  • @BradiKal61
    @BradiKal61 2 роки тому +1

    If your home needs two 9,000 watt generators in parallel to keep you going during a power outage then why don't you just get a dedicated home backup generator that runs off of natural gas? Am I crazy?

    • @GeneratorReviews
      @GeneratorReviews  2 роки тому

      99% of people who need this owns trailer business like food trucks and this Barry gets them by

    • @cleverman86
      @cleverman86 2 роки тому +5

      I went with the two 9kw portable generator due to the high cost of dedicated home backup plus install and permits. I also get the flexibility of taking it with me when traveling.

    • @GeneratorReviews
      @GeneratorReviews  2 роки тому

      @@cleverman86 👌🏾💯yep best route

    • @motoboss5250069qew
      @motoboss5250069qew 2 роки тому

      @@GeneratorReviews so if I'm running 2 Duromax 9000 generators on parallel for home backup I can't use surge protection? Is it safe?

    • @GeneratorReviews
      @GeneratorReviews  2 роки тому +1

      @@motoboss5250069qew perfectly fine

  • @electriccuts
    @electriccuts 2 роки тому +1

    How do you get all your generators? Do they send them to you?

    • @GeneratorReviews
      @GeneratorReviews  2 роки тому +1

      I get sponsored by Genmax and the predator and Duramax already sold.

    • @electriccuts
      @electriccuts 2 роки тому

      @@GeneratorReviews you sell the generators??

    • @electriccuts
      @electriccuts 2 роки тому

      @@GeneratorReviews what website?

    • @GeneratorReviews
      @GeneratorReviews  2 роки тому +2

      @@electriccuts i’m still working on my website the ones I sold are the ones I buy and then I sell them.
      If you see one I review and you wanna buy it just email me

    • @electriccuts
      @electriccuts 2 роки тому

      @@GeneratorReviews what is your email address?

  • @davestaco
    @davestaco 2 роки тому

    Can you parallel the genmax and the predator?

  • @satgod
    @satgod 7 місяців тому

    over a year and still no predator 240v parallel kit

    • @michaelslack6891
      @michaelslack6891 3 місяці тому

      Get the Duromax parallel kit and add 2 neutral wires easily.

    • @colencasey7761
      @colencasey7761 3 місяці тому

      @@michaelslack6891 made my own, was just saying they need to make one
      also the ground and neutral are tied together on the predators so one or the other gets you the same unless you unbond the neutral from the ground on them

  • @BradiKal61
    @BradiKal61 2 роки тому

    Bye bye Duromax!

  • @FatMat916
    @FatMat916 3 місяці тому

    How long to charge an ev???

    • @GeneratorReviews
      @GeneratorReviews  3 місяці тому

      It really depends on the amperage you’re using and the EV itself