Generator and Technical Contents
Generator options and configuration 400kva
In this video give u more details about the options and function of this generator where we are the one make the configuration and functional test
Переглядів: 186
Відео
#SCHNIEDER MICRO LOGIC LSI HOW SET AND CALCULATE
Переглядів 339День тому
In this video I explain how to set and calculate this micro logic from schnieder breaker which is L-is for your overload and S-is for you short circuit and I-is for your instantaneous protection.
#2806engine Leroy somer alt 380 vac 60 hz synchronizing
Переглядів 8514 днів тому
In this video give you an example on how we did the synchronizing we encountered some trouble using the right tools to fix easier is must so watch till end to know more how we succeeded to this project.
#LSIG ABB BREAKER PROTECTION #HOW TO SET AND #CALCULATE
Переглядів 14014 днів тому
In this video explain how to do the settings and calculation LSIG breaker trip.
#2506PERKINSENGINE OPTION TEST AND TROUBLE SHOOTING
Переглядів 19528 днів тому
IN this video showing wiring troubleshooting,configuration,
#2806engine synchro options troubleshooting
Переглядів 261Місяць тому
In this video we are given some ideas on how to fix this type of problem and we show you how we succeed in synchronising.
#2206seriesengine #talalternator #synchronizing
Переглядів 368Місяць тому
In this video i show you the troubleshooting of what this generator is and how to use a multimeter to check pls watch the video till end thank you
MECCALTE ALTERNATOR DIFFERENT STANDARD CONNECTION? 400VAC 50HZ
Переглядів 141Місяць тому
In this video i explain what happened to the connection why it is reverse polarity and it looks like wiring is not the usual wiring we see in other alternator which is 400vac 50hz output pls watch till end.
Deepsea 8610mk2 Basic configuration explain
Переглядів 246Місяць тому
Deepsea 8610mk2 Basic configuration explain
DEEPSEA 8610 MK2 wiring diagram and functionality simplify
Переглядів 3872 місяці тому
DEEPSEA 8610 MK2 wiring diagram and functionality simplify
SOLAR INVERTER AND GENERATOR SYNCHRONIZING EXPLAIN
Переглядів 1782 місяці тому
SOLAR INVERTER AND GENERATOR SYNCHRONIZING EXPLAIN
HOW TO TROUBLESHOOT AND REMOVE 1206 PRIME PUMP
Переглядів 3473 місяці тому
HOW TO TROUBLESHOOT AND REMOVE 1206 PRIME PUMP
#FACTORYLOADTESTING #770kva and inductive load bank
Переглядів 843 місяці тому
#FACTORYLOADTESTING #770kva and inductive load bank
GOODWE Green operating indicators explain
Переглядів 523 місяці тому
GOODWE Green operating indicators explain
HOW TO PREPARE AND DO MAINS GRID SYNCHRONIZING
Переглядів 8623 місяці тому
HOW TO PREPARE AND DO MAINS GRID SYNCHRONIZING
#HOW TO IDENTIFY PERKINS SERIAL NUMBER
Переглядів 933 місяці тому
#HOW TO IDENTIFY PERKINS SERIAL NUMBER
HOW TO FIX FAIL TO OPEN BREAKER AND PREPARE SYNCHRO 500KVA
Переглядів 3524 місяці тому
HOW TO FIX FAIL TO OPEN BREAKER AND PREPARE SYNCHRO 500KVA
PERKINS 4012 SERIES ECM CONFIGURATION AVR CONFIGURATION LOAD TESTING PART-2
Переглядів 1814 місяці тому
PERKINS 4012 SERIES ECM CONFIGURATION AVR CONFIGURATION LOAD TESTING PART-2
PERKINS 4012 SERIES ENGINE LOOM INSTALLATION AVR CONFIGURATION DSE CONGRATULATIONS LOAD TESTING
Переглядів 1434 місяці тому
PERKINS 4012 SERIES ENGINE LOOM INSTALLATION AVR CONFIGURATION DSE CONGRATULATIONS LOAD TESTING
INSTALLATION OF L-SERIES IN 1104C PERKINS ENGINE
Переглядів 4514 місяці тому
INSTALLATION OF L-SERIES IN 1104C PERKINS ENGINE
HOW TO ADJUST SPEED TO 1800 RPM AND 240VAC USING R120 AVR
Переглядів 5065 місяців тому
HOW TO ADJUST SPEED TO 1800 RPM AND 240VAC USING R120 AVR
CONFIGURATION 7SETS OF DSE890 WITH 6120 DSE MODULE
Переглядів 2065 місяців тому
CONFIGURATION 7SETS OF DSE890 WITH 6120 DSE MODULE
45KVA WITH AUTOMATIC TRANSFER SWITCH LETS SIMPLIFY
Переглядів 2995 місяців тому
45KVA WITH AUTOMATIC TRANSFER SWITCH LETS SIMPLIFY
110% LOAD TEST USING CONTAINERIZED INDUCTION LOAD BANK
Переглядів 3505 місяців тому
110% LOAD TEST USING CONTAINERIZED INDUCTION LOAD BANK
Why did you loadbank this with induction? The one you use to do with is resistive right?
Open type lods
Container load ni loadtest na namin para ready na pag salpak sa container
Sir ,a technician from Peru says in UA-cam for D alarm to set 317 Digital Input Polarity D to 1 from zero Do you think this is okay way to clear the alarm? similarly for F alarm set 327 Digital Input Polarity F to 1 from zero thanks
Hi sir thank you for asking digital input is a negative supply coming from your sw or any function that you program but only thing is negative in yes it posible u ask about it but make aure it is negative 👍
@@benzblogsVlogs thank you very much !! have a good day sir
sir , what fault symbol comes on your DSE panel? our Ferbo(Italy) 42KVA generator showing auxiliary input F fault on DSE 6020 screen and generator does not start how to find auxiliary input and clear the fault?
Yes check if its working or the contacts is good this is inside the breaker
@@benzblogsVlogs thank you very much !!
Hello good morning,Hi sir benz,,anyone know about parts no.of oil and fuel filters of TAFE Power Generator 621 ES engine Model..thank you
My dear im not incounter TAFE GENERATOR so i font have idea about it
Is it possible to communicate with an IC-NT controller with a DSE8660 MKII to do Island mode synchronization? If so how to do the wiring. THANKS
Im not try but im sure it will communicate same wiring dse msc and can for comap
Gracias por compartir este video...quisiera preguntar porque el cotrolador me parpadea 21 veces... como dandome un codigo... el motor no arranca desde el ECU... Saludos
Welcome
@@benzblogsVlogs Gracias... el codigo 21 es el MAP sensor fuera de rango.. la recomendacion es revizar el fusible de 60ma en la entrada del sensor..
Lawak Ng stock yard nyo Jan lods
Oo lods marami din
Alm ko jan sa inyo tatlo na yata
(Neutral in Load side of alternator) T-4 T-5 T-6 (Neutral in Line Side of output Breaker) T-10 T-11 T-12 (Install plates in this connection) T-7 to L-1 T-8 to L-2 T-9 to L-3 Tama ba to Sir? 400v to 220v L-L connection
Correct but the two side neutral are joint should be
How to configure 400v to 220v
If u need to comfig 440 -220 you have to change also the wiring ang the wiring to module and alternator connection
@benzblogsVlogs the generator is 100kva/80kw 3phase, how to convert the 400v output in L-L to 220v output L-L
@benzblogsVlogs how can I convert the 400v L-L output to 220v L-L output the controller is DSE6120 MK3
@@benzblogsVlogs pwede maka hingi ng diagram pano ma convert yung 400v to 220v L-L connection
@@wintertrucheon6418 no problem
Is it 6 lead out from stator?
What is your question again pls?
@benzblogsVlogs how many lead out from stator?
Ayos lods merry Christmas
Merry christmas
Nice view lods Ganda
Wow
Nice lods
Thank you bro. for the info you have shared. More power
Welcome sir 🙏
Sir send me your what’s number and I have one issue depsea 6110 display coming start and again stop
Hi recently i am facing issue that dse 8810 not indicating any LEDs on controller and not starting like hanged condition so tried firmware updation , after updation problem solved but again it comes after power off What may be the reason
The reason is your clock battery is dead
Hello. My MPU is giving a signal of 2.1 VAC but there is no output Voltage on A and B to the actuator
Meaning there is already problem it self your speed controller try to adjuat the idle to zero
How to do it link,
No need link now only update firmware
Good explanation idol iba talaga Ang master
Bless you lods
Sir good morning. Can you teach me how to synchronize generator sets using deepsea 8610 mk2 ?
Litle bit complicated but if u have knowldge about it its easy for you
Nice one lods morning...
Bless morning 🌄 lods
Do you need to adjust AVR on DSE config suite 8610 mk2, I always adjust centre and range? Can you do a video showing that? Please
Yes if nessisary you need to catch 70-75 percent of a calibration
@ I've tried but can't always get to 70-75, if I change one, it takes the other one off track, any way you could please make a video like that?
@ I use AVR ss341, 440s, and 408
@@elporky6420 sw1-2 in 75% thin andjust the avr according to you needs
Yon o ayos idol.iba talaga..❤❤❤
Salamt lods
Watching lods
Very bad Vdo
Thank you no problem
@ Actually Language issue
Is God worker I'm apirshet u
Bless you
What is the link on how to fix the problem on DSE when it say Memory Corruption refer to Manual
Simply update firmware version after that you need to config again in order to work the module
Sir dse 8610 mk2 gov output A and B wire is connected to L series Aux1 (8) and another wire is , where to connect?
Chck the diagram and it depend on the configuration from laeries but mostly that is 3-8 but need to comfig
Helo sir, pls how can i get the password setting for iNTL amf 25
0000
Thanks for sharing sir...pls how can I change interlite amf 25 to single face mannually, it shurting down. Thank you sir
I think not posible u need laptop to config
Sir ano root cause ng ramping o hunting ?
Ramping nasa speed controller Yan pweding lagyan or Hindi Ang hunting naman is pweding dahil sa dumi Ng fuel barado or colang sa calibration sa speed controller or mismong may problima Ang enjection pump
Emcp 1.1 phase sequence incorrect alram coming in. Faults how to turn off this in settings please tell thanks
Use multi meter to check check the comnection RYB if in correct posation and equal voltage
Sir i am your big fan #Powerlearningchannel
Same with you sir i am watching your videos have bless day
Watching from Botswana Africa Master, I have a Generator set with Volvo engine with Deepsea Controller 5320 running in good condition, after a while its just switch off, no display in deepsea controller even the indicating lights is off also. We check the wirings its ok, we change the battery still no display. Is the Deepsea controller is the problem or the ECU? Please enlighten me Thanks.
First check the voltage dc if there is from the module supply after that if there is thin check the led display from the module where it has red color if there is meaning only the display is the problems
@@benzblogsVlogs Thanks master appreciate...
buenas tardes tengo un caso de falla de comunicacion pero no tengo el enlace
El configuration or wiring problimo
Is configuración me dice la pantalla memoria corrupta consulte el manual@@benzblogsVlogs
how you sense the output voltage on AVR if you remove U & W cable
In order to undertand what are the posible causes of low voltage shutdown
Also, bka pwede makabili sa company nyo ng woodward proact digital speed control model II. May minomodify akong perkins engine 4008. Ang existing speed governor ay model I. Nagkakaroon ng delay ng impulse between dse and speed governor dahil sa interposing relay. Kaya balak ko palitam ng model II para direct sa dse teminal.
Sir dipo kc ng bibinta ng parts yung company check mo nalamg sir wala akong idea but im sure di sila ngbibinta
Idol, anong pin number sa ecm ang speed governor ng 2806 engine
20-24-19 lods
Great job
Idol❤❤❤❤
Hello bro,please show laptop closeup
It can auto start but can't stop running in auto mode
Till me what the module and if there is an ats or amf function
Thanks bro, very educational. I have a question. Why can't a generator fail to stop in auto mode.
Check the the module what model check if your using remote start or amf till me thin i reply to you what is the posiblity
Hi ,how are you brother ,I am facing problem with perkins 1300 series to replace 7320 AMF controller with new 7320 MKII controller.Generator is not getting started with new controller and working good with old controller.The old controller is screen is faulty that's why need to change the controller.can you guide Thanks
Yes bro what your problem
If u replace with new controller make aure you need to config again read the old module save the file and during the configuration compare the old config and follw it so you have the guide line what are the old configuration so it will work propperly
Ikaw lang ang nag gawgawa ng trouble mo 😅😅
Oh thank you so much may Godbless you
Love you from India sir you have explained more easy thank you so much sir 🎉
Thank you bless you
When I connect my pc with device using usb cable, It is not showing anything. It says Com4 inaccessible. I tried manytimes but cant connect to device with usb cable.Any solution?
Check the settings of your module and if not working with usb thin use the rs232 to config
Or update your sofetware
Watching friend, good evening, nice sharing