LOGO! 4 - 20 mA on the 0 - 10 V input? | Siemens PLC programming

Поділитися
Вставка
  • Опубліковано 27 лис 2024

КОМЕНТАРІ • 28

  • @Dzhookac
    @Dzhookac Місяць тому

    I had a lot of trouble making analog inputs to work properly. This video really clarifies many questions I had before..
    Thank You very much! :D

    • @QuickPLC-kh5of
      @QuickPLC-kh5of  Місяць тому +1

      Great. If you haven't already, have a look at Analog amplifier gain & offset: ua-cam.com/video/VwrP_mM-KTg/v-deo.htmlsi=9lG3zvsgCJJcVvVq.

    • @Dzhookac
      @Dzhookac 29 днів тому

      @@QuickPLC-kh5of thank you! Great video!

  • @СергейДигтенко
    @СергейДигтенко 4 місяці тому +2

    The video is very informative, hardware and programing are very clear. Thank you Sir! Regards from Ukraine.

    • @QuickPLC-kh5of
      @QuickPLC-kh5of  4 місяці тому

      Thank you for the feedback. We hope that your lives can get back to normal as soon as possible. There are many refugees from your country in my town in Ireland.

    • @СергейДигтенко
      @СергейДигтенко 4 місяці тому

      @@QuickPLC-kh5of Thank you for the support!

    • @QuickPLC-kh5of
      @QuickPLC-kh5of  3 місяці тому

      I did some more analog work. See quickplc.com/?Home___LOGO%21_index___Analog_amp_config and the video.

  • @mellorenato92
    @mellorenato92 29 днів тому

    Excelente Mister! Um abraço.

  • @chandradasaarachchilage8306
    @chandradasaarachchilage8306 16 днів тому

    Very clearly instruction thankuou❤

  • @dalematthews8748
    @dalematthews8748 4 місяці тому

    Very clearly explained 👌🏽

  • @Samath180
    @Samath180 6 місяців тому +1

    ❤ I love ..from Sri Lanka

  • @farazdeqnajim4205
    @farazdeqnajim4205 7 місяців тому +1

    Thank you 🎉

  • @slimenkabil
    @slimenkabil 2 місяці тому

    Thank you

  • @zegarmistrz00
    @zegarmistrz00 6 місяців тому +2

    Please do more videos about logo :)

    • @QuickPLC-kh5of
      @QuickPLC-kh5of  6 місяців тому +1

      I am, thank you. What did you like? What could I do better?

    • @Samath180
      @Samath180 6 місяців тому

      I wish continued..PLC logo programming..

  • @thien731987
    @thien731987 2 місяці тому +1

    Fan you

  • @raedalabsi
    @raedalabsi 6 місяців тому

    I really benefited a lot from your wonderful channel
    I have a solar energy system to charge 54 VDC batteries, and I want to control the turning on and off of the electric generator at values for example: 44 - 60 VDC volts using the Siemens logo!8.
    Is there a voltage sensor for this? or any anther ideas

    Thank you for your help🌹

    • @QuickPLC-kh5of
      @QuickPLC-kh5of  6 місяців тому +1

      If the LOGO! M (negative) is connected to the solar system negative then you can just use a pair of resistors to make a potential divider. A 9k - 1k divider would give you 4.4 to 6.0 V input to the LOGO! and that would give you 440 to 600 counts inside the LOGO! Make sure to calculate the power dissipated in the resistors using V^2/R for each resistor.

    • @raedalabsi
      @raedalabsi 5 місяців тому +1

      @@QuickPLC-kh5of Thanks Sir

  • @mobisat95
    @mobisat95 6 місяців тому +1

    Can you do one with pressure sensor (or temperature) to include threshold triggers and mathematic instructions?
    Let me expand. You have a 0-10V, 0 to 16 bar pressure sensor and you set up the gain, install it and instead of showing the working pressure of 3.8 bar, it reads 3.2 bar. Can you show using mathematic instruction or similar how to trim the resulting pressure to read correctly. Also add threshold triggers for alarms on same.

    • @QuickPLC-kh5of
      @QuickPLC-kh5of  6 місяців тому

      What is the configuration of your analog amplifier?
      The analog videos seem to be of higher interest than others. I'll see if I can do some more.
      Thanks!

    • @QuickPLC-kh5of
      @QuickPLC-kh5of  6 місяців тому

      First check the signal arriving at the LOGO! 3.8 bar / 16 bar * 10 V = 2.37 V. If you don't measure that with a meter then the problem is outside the LOGO! If you can't fix it then you need to rescale your reading by 3.8 / 3.2 = 1.1875. So instead of Measurement Range maximum = 160 or 1600 make it 160 * 1.1875 = 190 or 1900. Set the decimal places in message text to 1 or 2 depending on your 160 or 1600 for 0.1 bar or 0.01 bar steps.

  • @adssaeed
    @adssaeed 7 місяців тому

    thanks could you please explain for me the gain and offset

    • @QuickPLC-kh5of
      @QuickPLC-kh5of  7 місяців тому

      What do you not understand. Give enough details that someone could provide an answer.

    • @QuickPLC-kh5of
      @QuickPLC-kh5of  3 місяці тому

      I made another video and a calculator for gain and offset. See quickplc.com/?Home___LOGO%21_index___Analog_amp_config.

  • @bahiense62
    @bahiense62 4 місяці тому +1

    The problem, you lost 200 counts in the AI or the same, resoluton.

    • @QuickPLC-kh5of
      @QuickPLC-kh5of  4 місяці тому

      Correct. This is explained clearly at around 3:27. While you lose some resolution, you gain a ""live zero" and save the cost and space of an analog module. You said, "... or the same resolution." I don't understand that part of your comment. Thank you for the feedback.