Check the loft tanks EVERY year. You will be AMAZED
Вставка
- Опубліковано 8 вер 2024
- Often we find the system is “pumping over” this video will show how to solve this and other faults.
More info:
Order both books + CO2 chart, order value £45.00 no vat
UK Post Code only.
Order the books & CO2 chart from
www.mrcombi.co...
Our APPs are all one price £4.99 no vat
www.mrcombi.co...
Apple iOS download: apps.apple.com....
Google Play download: play.google.co....
BOOKS: www.mrcombi.co...
Hi mr combi, thanks for the upload +the logic of the pumping over question for you if i may could there be other underlining issues i.e blocked cold feed split coil etc or by extending the vent pipe would resolve the issue any help is most grateful take care thankyou
Hi Harry, thanks for asking, no it would not solve that problem and changing the cold feed makes the system fill much faster with less air in the water.🤩👍
@@mrcombiBedford thanks for the reply so basically because the f+e tank is within the 5 metre head of the pump the vent pipe requires to be extended in order to prevent pump overrun
Thanks
Pumping over i meant to say
My first message was miss interpreted what I meant was could the pumping over be due to blocked cold feed or pump setting too high or split coil, faulty cylinder thermostat etc etc could any of these faults cause it to pump over
Thanks