OPEN TANK LEVEL MEASUREMENT

Поділитися
Вставка
  • Опубліковано 15 сер 2024
  • This video is to assist NAIT students in doing the level measurement lab using the Rosemount 1151 DP transmitter.

КОМЕНТАРІ • 38

  • @noelfaithfulkari2857
    @noelfaithfulkari2857 9 років тому +8

    please do more videos regards transmitters, valves, RTD's,.... thanks a lot; best I've seen yet. thanks

  • @malikgarrett2036
    @malikgarrett2036 5 років тому

    This video is the best in explaining all steps. I just start taking instrumentation class

  • @qzorn4440
    @qzorn4440 5 місяців тому

    An Amazon $80 Riiai 4-20mA 0-24V precision 0.01mA calibrator will work just fine. Hundredth's of a milliamp is adequate. This will save $13,000 of buying a Fluke 754 😎 Nice video

  • @randiahmed860
    @randiahmed860 5 років тому

    Thank you , it's very interesting information please don't stop up load like these videos .

  • @1quickchevy2
    @1quickchevy2 7 років тому

    Nait was a great place to learn. Great labs, and great instructors.

  • @derina.maleek9408
    @derina.maleek9408 5 років тому

    Please make more videos it is best video I ever seen don't waste that lab you have keep going and we are supporting you

  • @shaiksaleem06
    @shaiksaleem06 8 років тому

    thanks for the video its very helpful for people who didn't have practical knowledge

  • @geethsri4914
    @geethsri4914 9 років тому

    thank u sir . this most use full
    and he explain very good and basic knowledge Pearson all so understand

  • @karimtalebi7111
    @karimtalebi7111 8 років тому

    Great. Please put more videos. I waiting for anothet excellent training like this. Thank You!

  • @JZ-Sensor
    @JZ-Sensor 6 місяців тому

    I love it

  • @TheCommonSenseProfessor
    @TheCommonSenseProfessor 8 років тому +2

    I am totally jealous of your lab!

  • @athilaldurry5880
    @athilaldurry5880 3 роки тому

    many thanks

  • @estradacantu
    @estradacantu 8 років тому

    Great explanation

  • @kaunghtethein3322
    @kaunghtethein3322 4 роки тому

    Very useful, thank you. One question, can i not use pressure regulator in the first place and use the actual water level to calibrate? If yes, what difference would that make? Anyone please ...

  • @abdulbilakhiya6026
    @abdulbilakhiya6026 3 роки тому

    Appreciate

  • @andrewtaylor5972
    @andrewtaylor5972 3 роки тому

    What’s the calculation to derive 0.49kPa? Thanks

  • @rodelpabito7292
    @rodelpabito7292 6 років тому

    procedure for boiler level dp tansmitter....here the lrv-= -6.683kpa
    urv= -1.343kpa
    wet leg type
    span = 5.34

  • @megamanwins
    @megamanwins 2 роки тому

    Why you do not upload anymore? its been like 7 years! :(

  • @bac4998
    @bac4998 5 років тому

    Thanks.

  • @CavadCavidHuseynov
    @CavadCavidHuseynov 8 років тому

    Superb

  • @totoilongo6132
    @totoilongo6132 6 років тому

    Thanks

  • @shamshadall-rounder7619
    @shamshadall-rounder7619 Рік тому

    Why you not mention 250 omh In series conection ?
    Branch type calibration need also 250 omh

    • @unupeter7657
      @unupeter7657 Рік тому

      U don't need a 250 ohms resistance if u are not hooking communicating device...... The 1151 series transmitter are purely analog and are not hart enabled, the there will be no beed to reduce the loop impedance. Thanks 🙏

  • @amirimaf4203
    @amirimaf4203 5 років тому

    tanks

  • @attacknblack1984
    @attacknblack1984 9 років тому +1

    Can you post some vids about square root extraction

  • @prgomad5392
    @prgomad5392 3 роки тому

    What is the name of this facility lab

  • @Q1W2E3QW
    @Q1W2E3QW 8 років тому

    at minutes 3 you start sir to connect high side to regulator and Instrument Air Supply !!! this made me confused ... what I know , its connect to process - bottom of a tank

    • @gr8bastard
      @gr8bastard 7 років тому

      Q1W2E3QW the instrument air connection is used for bench calibration purpose.

    • @Q1W2E3QW
      @Q1W2E3QW 7 років тому

      ok .... why you not use pressure transmitter for open tank instead of using DP Transmitter.
      as you know, its more expensive ... plus a manifold related to differnial transmitter is more expense than manifold of pressure transmitter...in addition, you dont have to wary about low side to elemenate dust and wind impact.

  • @rahulmavath4291
    @rahulmavath4291 4 роки тому

    Why you calibrate with Lrv of 0.49 kpa. why you choose that value

    • @KevinRocket01
      @KevinRocket01 3 роки тому

      cause its the equivalent pressure of the reference or datum line of the tank. it is the measured pressure where tank is considered zero level. it is common in level measurement to compensate the sludge or sediments settling down at the bottom of the tank.

  • @abulkhayer6989
    @abulkhayer6989 6 років тому

    nice