How to install grounding according to standards. Carelessness can have fatal consequences

Поділитися
Вставка
  • Опубліковано 3 бер 2021
  • The grounding system or better known as grounding is a very important component in electrical installations, because grounding functions as protection when leakage current occurs in equipment, so that humans who touch the equipment will be safe from electric shock.
    In accordance with the requirements of PUIL (General Electrical Installation Regulations), the grounding resistance value must be less than or equal to 5 Ohms and anything above this value cannot be tolerated.
    In this video, we will learn how to install grounding and continue with the measurement process using an Earth Tester measuring tool.
    Hopefully this video is useful for creative friends who are learning about electrical systems. If you have questions or input, please write them in the comments column. Thank you for your support and support for the Siroedhie Kreasi channel...
    Come on, let's watch this video...let's go kemon
    #Grounding #PUIL #EarthTester #GroundingResistance #siroedhiekreasi

КОМЕНТАРІ • 852

  • @onedeeProject
    @onedeeProject 2 роки тому

    Ikut nyimak boss selamat sukses

  • @bejegriezman7326
    @bejegriezman7326 2 роки тому

    Semangat om meski telat nonton vedeo ny tapi sangat bermanfaat ilmu ny buat saya

  • @dedigaly3352
    @dedigaly3352 Рік тому

    Ok maseh saya like mantap

  • @majestyteknik7723
    @majestyteknik7723 6 місяців тому

    Pekerjaan yg perlu perhitungan matang.... 👍👍👍

  • @iwayanpujawan7267
    @iwayanpujawan7267 Рік тому

    Terus berbagi bang🙏 saya tertarik belajar tapi masih awam🙏

  • @noerhadi8797
    @noerhadi8797 2 роки тому +5

    Sukses dan berkah selalu untuk bapak dan keluarga
    Karna sudah baik hati berbagi wawasannya

  • @user-fm2zf4nl9r
    @user-fm2zf4nl9r 3 місяці тому

    Trmksh pak utk ilmunya.

  • @aangjunaidi5914
    @aangjunaidi5914 2 роки тому

    ManTap ,jd pengen belajr kelistrikan dr nol...sukses bang

  • @abimunandar5583
    @abimunandar5583 2 роки тому +1

    Alhamdulillah.. Trimakasih pak info nya 🙏

  • @fajartambunan3221
    @fajartambunan3221 2 роки тому +4

    Ma Sha Allah Tabarakallah...
    Semoga Ilmu Yang Disebarkan Menjadi Sedekah Jariyah 😇😇

  • @shundhem_electrick
    @shundhem_electrick 2 роки тому +1

    Luar biasa, terimakasih ilmunya.

  • @WillemLuntungan
    @WillemLuntungan 2 роки тому

    Mantap ground 👍👍

  • @abdussalamabdussalam1638
    @abdussalamabdussalam1638 3 роки тому

    banyak sekali ilmu di channel ini, terima kasih sudah berbagi. semoga abang sehat selalu

  • @rafifahaura4547
    @rafifahaura4547 8 місяців тому

    Alhamdulillah, semoga sukses dan dimudahkan urusannya

  • @vitaldearaujo5171
    @vitaldearaujo5171 5 місяців тому

    mkasih banyak bang atas berbaginya ilmu

  • @rizalmaulana8632
    @rizalmaulana8632 2 роки тому

    Mantap pak

  • @rudisamijo
    @rudisamijo 2 роки тому +1

    Terimakasih Ilmu nya bos, semoga menjadi amal jariah👍👍

  • @wantograb8108
    @wantograb8108 2 роки тому +1

    cukup jelas

  • @rulgempargemilangsago963
    @rulgempargemilangsago963 2 роки тому

    Mantap ..ilmunya ..boss

    • @siroedhiekreasi
      @siroedhiekreasi  2 роки тому +1

      terima kasih boss...🙏 saya juga sedang belajar. mohon saran dan masukannya

  • @lingkuppetarung6415
    @lingkuppetarung6415 2 роки тому

    terimakasi tas ilmu yg di bagikan

  • @anakpetani_7791
    @anakpetani_7791 2 роки тому

    Terimakasih ilmunya sukses selalu

  • @agushapiludin6415
    @agushapiludin6415 10 місяців тому

    Terus berkarya bang,semangat.... 💪

  • @prismatech_ind
    @prismatech_ind 9 місяців тому

    Terimakasih mantap ilmunya pak

  • @didimaulanamahulauw3613
    @didimaulanamahulauw3613 Рік тому

    Mantapp sukses n sehat² trus tim nya 🙏🏻

  • @listrikoke2885
    @listrikoke2885 2 роки тому

    Terimakasih bg ilmu nya🙏🙏

  • @f.oetomo4573
    @f.oetomo4573 2 роки тому

    Terima kasih infonya.

  • @kembangtelonproduction9583
    @kembangtelonproduction9583 2 роки тому +1

    Setelah lihat video ini saya berhasil buat sendiri dibwh 5 ohm. Sudah saya videokan juga, ternyata mudah. Terima kasih...

  • @depanbelakang5550
    @depanbelakang5550 3 роки тому

    Mantap master

  • @gilanggm8413
    @gilanggm8413 2 роки тому

    sangat bermanfaat ilmunya

  • @aryanuramdiansyah8247
    @aryanuramdiansyah8247 2 роки тому

    Baru tau,terimakasih atas ilmunya pak.

  • @TUTORIALLISTRIK303
    @TUTORIALLISTRIK303 2 роки тому

    Keren Bossku salam kenal🙏

  • @ereniyegah4766
    @ereniyegah4766 Рік тому

    terima kasih pak videonya

  • @AdeAprilockers
    @AdeAprilockers 2 роки тому

    Terima kasih pak.... Semoga jadi amal jariyah pak..🙏

  • @adityabaladewa3966
    @adityabaladewa3966 3 роки тому

    Nongol diberanda terlihat menarik. Auto subret pak.

  • @sukasuka728
    @sukasuka728 2 роки тому

    Mantap ilmunya pak, saya subscribe 👍

  • @Achenx-bo7rs
    @Achenx-bo7rs 9 місяців тому

    👍💪Terima kasih

  • @elektricalchannel9784
    @elektricalchannel9784 2 роки тому

    Mantap

  • @omahngareptebu
    @omahngareptebu 2 роки тому

    di bantu sama air uenak bosss. g perlu di pantek2 gitu😅

  • @ngatnomas8749
    @ngatnomas8749 Рік тому +1

    Ikut nyimak.. semoga ilmu yang bapak berikan bisa menjadi amal jariyah ya Pak..

    • @siroedhiekreasi
      @siroedhiekreasi  Рік тому

      Amin ...

    • @robotpenghancurjohe3325
      @robotpenghancurjohe3325 Рік тому

      @@siroedhiekreasi mas info rod yg ditanam kalo gak ada yang murni tembaga gimana sama kabelnya itu hitam tipe apa ya ?

    • @siroedhiekreasi
      @siroedhiekreasi  Рік тому

      @@robotpenghancurjohe3325 kabel yg hitam bisa pakai jenis kabel bc mas

    • @robotpenghancurjohe3325
      @robotpenghancurjohe3325 Рік тому

      @@siroedhiekreasi mas kalo road gak murni tembaga gimana ya, saya si yakin bisa, mohon kalo ada waktu di jelaskan mas, saya suka belajar

    • @siroedhiekreasi
      @siroedhiekreasi  Рік тому +1

      @@robotpenghancurjohe3325 bisa sih mas, tapi nilai resistansinya lumayan besar dan membutuhkan elektroda yg lumayan bnayak untuk mendapatkan nilai resistansi seperti yg dipersyaratkan oleh PUIL. disamping itu, kalau tidk menggunakan tembaga murni akan rawat berkarat

  • @dirojo
    @dirojo 3 роки тому +1

    berkelas tutorial singkatnya om. thnks.

  • @D_K
    @D_K 3 роки тому

    Selamat siang kak

  • @manoeng
    @manoeng Рік тому

    Sangat Bermanfaat....Subscribe Dulu😁

  • @jameskaligis6976
    @jameskaligis6976 2 роки тому

    Thanks

  • @syamsultvchannel8421
    @syamsultvchannel8421 Рік тому +1

    😁😁😁😁😁pakailah mesin hammerjack untuk masukkan earth chamber.nya agar tak payah pukul guna hammer. .cable harus min.8mm.jangan kecil.dan earth yg masuk dalam sekurang2nya 4x joint

  • @herywaluyo1074
    @herywaluyo1074 Рік тому

    Mungkin yg dimaksut om dibawah itu ..untuk groung panel besar
    Memang lebih kecil nilai omh nya lebih bagus

  • @Bang_Din
    @Bang_Din 2 роки тому +1

    Saya pernah dapat grounding murni,dibawah 1ohm,pemiliknya sangat puas,saya yg kerja jg sangat senang melihatnya😁

    • @siroedhiekreasi
      @siroedhiekreasi  2 роки тому +1

      wah...mantap nih. saya sendiri belum pernah dapat di bawah 1 ohm Pak

    • @siroedhiekreasi
      @siroedhiekreasi  2 роки тому

      kalau boleh tau, berapa batang grounding rod yg digunakan Pak ? terima kasih

    • @adiadisupriyadi5045
      @adiadisupriyadi5045 Рік тому

      Chanek abang ngebahas soal praktek teknik grounding juga bang? Mau lihat dong saya!

  • @fajarfajar4188
    @fajarfajar4188 3 роки тому

    Sangat membantu..
    Sy ingin pasang tp blm tau dgn siapa yg ahli

    • @siroedhiekreasi
      @siroedhiekreasi  3 роки тому +1

      bisa pasang sendiri aja Pak, gak susah kok 🙏

  • @abdurrachmanabdurrachman2244

    Assallamu'alaikum..Saya sangat suka dengan deretan videonya, sangat tertata dan penuh pemahaman, teori dan praktenya sama. 🙏🙏🙏Maaf sebelumnya saya masih belajar dan mau menanyakan ke bapak, kapan bisa berbagi tentang video baru mengenai rangkain panel khusus HVAC beserta diagramnya terima kasih .Wassalamu'alaikum Wr. Wb.

    • @siroedhiekreasi
      @siroedhiekreasi  Рік тому

      Waalaikumussalam. terima kasih Pak, saya juga masih belajar. untuk rangakaian panel listrik 3 phase saya sudah buatkan tutorialnya. saya buat dalam 4 episode. bila berkenan bisa Bapak cek di playlist kelistrikan 🙏. ini salah satu contohnya ua-cam.com/video/XzMbywffLzM/v-deo.html

    • @wawansetiono6529
      @wawansetiono6529 6 місяців тому

      ​@@siroedhiekreasiBang saya ngak punya alat earth tester. Apakah bahaya kalau tegangan tidak sesuai

    • @siroedhiekreasi
      @siroedhiekreasi  6 місяців тому

      @wawansetiono6529 bila nilai resistansi grounding ridak sesuai, akan sangat berbahaya saat terjadi gangguan arus bocor Pak. manusia yg menyentuh leralatan bisa kesetrum

    • @wawansetiono6529
      @wawansetiono6529 6 місяців тому +1

      @@siroedhiekreasi ok bang makasih🙏

    • @siroedhiekreasi
      @siroedhiekreasi  6 місяців тому

      @wawansetiono6529 sama sama bang

  • @iblesbosuok
    @iblesbosuok 2 роки тому

    Saya dulu pasang panel distribusi 11kVA fasa tunggal, ardenya bela-belain membor tanah sedalam 12 meter agar mencapai air tanah. Penghantar pakai BC-35 dimasukkan ke pipa kasing bor tanah mentok ke dasar.
    Itupun cuma dapat resistansi 1,6Ω.
    Salam genimili

    • @siroedhiekreasi
      @siroedhiekreasi  2 роки тому

      sangat mantap tuh Pak, dapat 1,6 ohm. terima kasih sharingnya 🙏

  • @hartonolubis1559
    @hartonolubis1559 3 роки тому

    Mak.. Ngeri kali pak.. kebayang kalo tu palu lepas di tangan.. wkwkwkwkwkw...

  • @farchanzulianto92
    @farchanzulianto92 10 місяців тому

    Waktu tanam groundingnya sambil dialiri air biar tanah lebih empuk kayaknya jadi mudah mukulnya

  • @gummi4977
    @gummi4977 2 роки тому +5

    Terima kasih info nya, pak. Sangat menarik.
    Sekalian mau bertanya:
    1. Untuk di daerah perumahan yg lagi dibangun, dimana baiknya ground root tembaga nya dipasang? Karena rumah berdempetan, apa bisa ditaruh di bawah lantai rumah sebelum benar" di pasang keramik?
    2. Berapa biaya pemasangan atau jasa pemasangan grounding ini?
    3. kalau tidak punya alat ukur yg bapak pakai, baiknya dipasang berapa buah lagi tambahan batang tembaga nya pak buat antisipasi mencapai < 5 ohm ?

    • @siroedhiekreasi
      @siroedhiekreasi  2 роки тому +3

      1. bisa Pak, atau kalau mau hemat dibuat satu ground root untuk dua rumah juga bisa.
      2. biaya pemasangan bervariasi Pak, mulai 2 s.d 3 jt. semakin kecil nilai resistansi, semakin mahal biayanya
      3. sebaiknya menggunakan alat ukur Pak, karena tanpa alat ukur kita tidak bisa mengetahui resistansi yg sebenarnya 🙏

    • @gummi4977
      @gummi4977 2 роки тому

      @@siroedhiekreasi wah begitu ya, kira" yg ahli buat urusan grounding itu tukang apa ya pak namanya?

    • @siroedhiekreasi
      @siroedhiekreasi  2 роки тому +1

      @@gummi4977 sebenarnya gak perlu yg benar² ahli Pak 🙏😀. pasang sendiri juga bisa, gampang banget caranya. lebih kurang caranya seperti yg ada dalam video ini. tapi sebaiknya diukur Pak 🙏

    • @gummi4977
      @gummi4977 2 роки тому

      @@siroedhiekreasi Ndak punya mesin tes nya pak hehe
      Terima kasih banyak pak atas insight nya, semoga barokah 🙏

    • @siroedhiekreasi
      @siroedhiekreasi  2 роки тому

      @@gummi4977 amin... 🙏

  • @sahrawioc629
    @sahrawioc629 2 роки тому +2

    Kenapa harus pakai yang panjang arde nya, apakah gak sebaiknya di paralel arde nya biar semakin kecil tahanan grounding nya

  • @budiawan1784
    @budiawan1784 Рік тому +2

    Terimakasih, sdh menyimak dan menyisakan beberapa pertanyaan:
    1. Rod memakai solid brass?
    2. Untuk daya 900-1.200, pakai Rod diameter berapa dan panjang minimal berapa?
    3. Setelah rod terkubur.... Apa yang harus dilakukan jika HASIL PENGUKURAN lebih besar dari 5 ohm?

    • @siroedhiekreasi
      @siroedhiekreasi  Рік тому +1

      jika lebih besar dari 5 ohm, bisa kita pasang elektroda berikutnya dihubung paralel, agar tahanannya menjadi lebih kecil. mengenai panjangnya relatif, tergantung dari karakter tanah, bisa menngunakan diameter 16 mm²

    • @budiawan1784
      @budiawan1784 Рік тому +1

      @@siroedhiekreasi terimakasih.
      Saya "pemakai" PLN pakai meteran lama (pakai dulu...bayar blakangan) daya 900, belum ada grounding dan mmg mau grounding; mumpung ada sdkt rejeki.

    • @siroedhiekreasi
      @siroedhiekreasi  Рік тому +1

      @@budiawan1784 baik Pak, grounding terkadang sering diabaikan. tapi masalah keselamatan adalah hal yg sangat perlu kita perhatikan. 🙏

  • @user-wb5zp3xr2y
    @user-wb5zp3xr2y Рік тому

    😊

  • @jhoniirawan2172
    @jhoniirawan2172 2 роки тому +5

    Oya pak satu lagi,,kebanyakan yg saya lihat dr instalasi listrik rumahan khususnya di pedesaan. Kebanyakan grounding gk terpakai,, jd groundingnya cuma sebatas dr tanah ke box sekring(artinya sia-sia) . Keluar dr box cuma kabel fasa dan netral,, karena kalau instalasi rumah setiap stop kontak harus pake ground membutuhkan dana lebih ketimbang cuma 2 kabel.Padahal grounding itu penting dan sesuai standar.

    • @daengbacho829
      @daengbacho829 2 роки тому

      itu semua tergantung sipemilik rumah gan.. mau ngeluarin biaya tambahan untuk kabel grounding apa ngga?. kebanyakan ya mintanya mau yg murah..

    • @jhoniirawan2172
      @jhoniirawan2172 2 роки тому +1

      @@daengbacho829 iya mas,, yg saya maksud di atas itu termasuk instalasi dirumah saya sendiri.Masalahnya ya mengirit biaya. Hehehe
      Tp kalau mengingat fungsi dr kabel grounding, sebenarnya penting sekali karena kita terhindar dr sengatan listrik jika ada arus bocor.

    • @jayaabadi9027
      @jayaabadi9027 5 місяців тому

      Itu pakek Kuningan asli ya ,biasanya besi dicat warna kuning emas kalau di tempatku di desa

  • @MadiMubarokah
    @MadiMubarokah 3 роки тому +2

    Masyaallah, sangat bermanfaat buat sy yang belum paham masalah Grounding. Sy mau bertanya pak, solusi untuk kami yg terkadang punya alat2 komputer yg rentan terhadap gangguan listrik karena tidak adanya grounding bagaimana ya? Seperti grounding sederhana begitu. Karena sy sering instalasi live streaming pakai laptop kemudian kami dapati seluruh perangkat kami teraliri listrik yang bagian besinya, pernah sy coba buat grounding sederhana dgn cara tanem paku 1 inci ke tanah dan di sambung ke ground stop kontak hasilnya tetap teraliri listrik tapi tidak separah tanpa grounding sederhana tersebut

    • @siroedhiekreasi
      @siroedhiekreasi  3 роки тому +1

      kalau seperti itu kondisinya, kemungkinan nilai resistansi pentanahan nya masih tinggi Pak. Belum seperti yg dipersyaratkan oleh PUIL, yaitu lebih kecil atau sama dengan 5 Ohm. Solusi yg bisa saya tawarkan adalah elektroda pentanahannya harus ditambah, dan ditanam agak dalam, seperti yg terlihat dalam video, elektroda saya tanam dengan kedalaman lebih kurang 3 meter. Elektroda pentanhan biasa di sebut juga dwngan ground root bisa Bapak beli di toko perlengkapan listrik. Selamat mencoba, semoga berhasil ya Pak 🙏

    • @siroedhiekreasi
      @siroedhiekreasi  3 роки тому

      paku 1 inchi belum memadai Pak, masih terlalu dangkal dan bahannya tidak terbuat dari tembaga. 🙏

    • @MadiMubarokah
      @MadiMubarokah 3 роки тому

      Begitu ya pak, terima kasih atas jawabannya pak. Untuk harganya berapa ya pak? Tembaga gorunding nya? Kemudian cara buat mengukur tingkat ohm selain pakai alat bapak yg ada di video itu apa ya kira2?

    • @siroedhiekreasi
      @siroedhiekreasi  3 роки тому

      @@MadiMubarokah terima kasih kembali Pak, untuk harga memang lumayan mahal Pak, di daerah saya (aceh) harga per batang di kisaran 800 k. Untuk mengukur tahanan pentanahannya menggunakan earth tester, kalau gak punya alat ukur memang agak susah sedikit Pak. Tapi bisa kita gunakan cara manual seperti yg sudah Bapak lakukan, setelah elektroda terpasang dan dihubungkan ke sistem, bisa kita lakukan uji sentuh. Kalau tegangan sentuh masih terasa besar, berarti nilai resistansi pentanahannya masih belum memadai 🙏

    • @siroedhiekreasi
      @siroedhiekreasi  3 роки тому +1

      kalau nilai resistansi pentanahannya masih besar (belum memenuhi persyaratan) bisa kita buat dengan metode paralel Pak. Dua buah elektroda atau lebih, kita tanam dalam hubungan paralel

  • @denz9282
    @denz9282 2 роки тому +1

    ijin bang bertanya mana lbh baik penggunaan stick rod (dalam cuma 3meter sprti abang diatas ) atau tombak splitzen dg kabel BC 50mm2 dg kedalmaan 6meter?

    • @siroedhiekreasi
      @siroedhiekreasi  2 роки тому +2

      ada banyak model pentanahan Pak, intinya adalah nilai resistansi pentanahan harus memenuhi standar PUIL yaitu lebih kecil atau sama dengan 5 Ohm. Grounding yg paling baik adalah yang nilainya mendekati 0 ohm karena lebih cepat menyalurkan arus gangguan ke bumi. 🙏

  • @dkredy
    @dkredy 5 місяців тому

    Terimakasih sharingnya, ingin bertanya:
    Apakah grounding tidak diperlukan bak control?
    Untuk kabel dr Rod ke MDP sebaiknya menggunakan kabel BC atau NYA?

    • @siroedhiekreasi
      @siroedhiekreasi  5 місяців тому

      bok control idealnya diperlukan pak, tapi tergantung sikon juga. biasanya menggunakan kabel bc pak tapi yg menjadi pedoman adalah diameter penghantarnya, semakin besar akan semakin baik

  • @IsaruddinIsar
    @IsaruddinIsar Рік тому

    Pak, bila berkenan tolong buatkan tutorial cara menurunkan nilai resistansi pentanahan bila nilainya lebih besar dari 5 ohm. terima kasih atas responnya

    • @siroedhiekreasi
      @siroedhiekreasi  Рік тому

      baik, terima kasih. insya Allah kita buatkan di lain waktu dan kesempatan 🙏

  • @capt.hasmangbinbatjo6825
    @capt.hasmangbinbatjo6825 Рік тому +1

    Pak mau tanya klau pasang grounding dari kwh pln ke tanah dan yang ke instalasi hanya 2 kabel saja netral dan phase.apakah itu aman.terima kasih by Hasmang

  • @fandiartitani9860
    @fandiartitani9860 2 роки тому

    Bang saran biar lebih cepat pake humerr drill yang besar bang...

  • @AxyStudio
    @AxyStudio 2 роки тому

    Mantap ilmu nya Pak, mohon bantuannya menjawab, kalau uda tanam batang elektroda di pekarangan rumah, terus pekarangan tersebut kebanjiran, setinggi mata kaki, dimana batang elektroda terendam air, apakah aman? karena kadang anak2 suka main air, apakah bisa nyeterum? Posisi listrik kwh meter semua nyala.

    • @siroedhiekreasi
      @siroedhiekreasi  2 роки тому

      aman pak

    • @AxyStudio
      @AxyStudio 2 роки тому

      @@siroedhiekreasi jadi gpp ya terendam Pak. Gk bakal nyetrum?

    • @siroedhiekreasi
      @siroedhiekreasi  2 роки тому

      @@AxyStudio ya pak gpp

    • @AxyStudio
      @AxyStudio 2 роки тому

      @@siroedhiekreasi siap, terima kasih banyak 👍🏻

  • @anhito
    @anhito 2 роки тому +4

    1. Sebaiknya Pakai kabel ground nya atau nyaf?
    2. Untuk pemasangan ground listrik 1 phase dan penangkal petir sebaiknya dipisah jarak nya berapa jauh

    • @keretanafaz1135
      @keretanafaz1135 Рік тому

      brapa min ukuran kabel NYAF ke grounding, pipa tembaga berapa ukuran ? dan kedalaman minimal brapa ?

  • @aribudiman3228
    @aribudiman3228 2 роки тому

    ijin share ya min...

  • @arielenofficial4684
    @arielenofficial4684 27 днів тому

    Kak mohon bantuan anti petir saya kabel groding anti pertinya digabung kabel grading di di goding ncb box listrik.saya egk kal.mohon bantunya saya binggung

  • @edo_daniartha
    @edo_daniartha 4 місяці тому

    Assalamualaikum Pak. Izin bertanya Sebulan lalu saya sudah ganti kabel instalasi rumah. pakai supreme 3 ×2.5 jalur utama dan 2x1.5 untuk Lampu. saya baru ingat kalau kabel grounding ke Tanah itu sdh lama bgd di putus. lalu sy coba cek lagi dibawah tembok rumah saya dan ada bekas tembaga dan sisa kabel sambungan groundingnya. pertanyaannya, apakah bisa sy sambungkan lagi ?, atau harus beli dan buat baru di tempat yg berbeda. saya lihat warna tembaganya sudah hitam sekali. 1 lagi jika sdh pasang grounding perlukah buat pasang ELCB /RCBO di box mcb. rumah sy masih 900 watt. Terima kasih sdh mau dijawab Pak. 🙏 Waalaikumsalam wr.wb

    • @siroedhiekreasi
      @siroedhiekreasi  4 місяці тому

      bisa pakai grounding yg lama saja pak, warna hitam wajar karna proses korosi. bisa diamplas dulu sebelum disambung kembali. ELCB/RCBO diperlukan sebagai proteksi pak

  • @dedekkurniadi672
    @dedekkurniadi672 2 роки тому +1

    kalau untuk rumah minimalis (6 rumah) dengan tipe 5x8
    apakah bisa dan fungsi ny sama, kalau hanya 1 ground saja di tancapkan tembaga dan di pararel ke setiap rumah?

    • @siroedhiekreasi
      @siroedhiekreasi  2 роки тому

      bisa Pak, pastikan nilai resistansinya di bawah 5 Ohm. Semakin mendekati 0 Ohm akan lebih baik lagi

  • @diywoodworkingjourney5010
    @diywoodworkingjourney5010 11 місяців тому

    Terima kasih atas videonya. . .
    Btw, boleh ngga sambungan tiang tembaganya di solder dengan timah solder?

    • @siroedhiekreasi
      @siroedhiekreasi  11 місяців тому +1

      kalau disolder dikhawatirkan lepas pak, sebaiknya dibaut atau bisa juga sistem las menggunakan serbuk misiu (konsepnya hampir sama seperti disolder)

    • @diywoodworkingjourney5010
      @diywoodworkingjourney5010 11 місяців тому

      @@siroedhiekreasi betul juga yah. . .kalau pake sistem las bubuk mesiu pasti materialnya menyatu dengan sempurna, saya pernah liat di video saat teknisi rel kereta api menggunakan sistem ini untuk menyambung rel kereta 🙏
      Makasih atas ilmunya, sangat berguna untuk saya. . .terima kasih edukasinya, sukses selalu 🙏

  • @darsilmane6934
    @darsilmane6934 Рік тому

    biasanya saya pasang coper roadnya. tanah di bor. gak di pukul make hammer.

  • @omahngareptebu
    @omahngareptebu 2 роки тому

    konek nya di bilitkan kawat nya bos, lalu di klem😂

  • @user-hk3mp8fr3c
    @user-hk3mp8fr3c 3 місяці тому

    untuk rumah yg besaran listriknya hanya 4 ampere..sebaiknya ukuran panjang stick grounding brp meter ? dan besar batang stick grounding brp milimeter ?... mhn jawabanya bg...
    trus untuk jarak tanam stick grounding yg dibolehkan sesuai aturan, bberap meter jauhnya dari KWH meteran (atau kotak yg divideo abg td)? ....hal ini sy tanyakan krn ingin mendapatkan tanah untuk tanam grounding yg lembab (misalnya pinggir parit)...mhn jawabanya bg....
    trus besar kabel yg BC/atau kabel yg abg pakek tsb brp milimeter minimalnya bg? (untuk besaran listrik rumahan 4 ampere)..mhn pencerahannya bg..

    • @siroedhiekreasi
      @siroedhiekreasi  3 місяці тому

      mengenai panjang stick relatif pak tergantung struktur tanahnya, mengenai diameter stick semakin besar semakin baik (yg saya gunakan dlm video ini 25 mm), dgn jarak stick ke box panel +- 4 meter. yg menjadi patokan adalah nilai resistansinya pak tidak boleh lebih dari 5 ohm

  • @surinnida2183
    @surinnida2183 2 роки тому +1

    kami buat menara dari siku besi utk penempatan spiker dan Di pasang penangkal petir sedang Kabel BC kan tanpa isolasi dan pemasangnya pakai clem yg nempel body kalo ada petir apa gak kena bodi siku .trm ksh. Sebelumya

    • @siroedhiekreasi
      @siroedhiekreasi  2 роки тому

      untuk pemasangan grounding pada bagian konduktor terbuka seperti besi siku sebaiknya menggunakan penghantar berisolasi. Agar aman ketika terjadi sambaran petir

  • @AlgojoBuzzer
    @AlgojoBuzzer 2 роки тому +2

    Kenapa rata² Meter an listrik PLN tidak menerapkan fungsi ground???
    Apakah mereka tidak mengikuti SOP

  • @matyie609
    @matyie609 7 місяців тому

    Kalau kt malaysia pakai drill hammer saja.. xperlu letih pakai tukul😂

    • @siroedhiekreasi
      @siroedhiekreasi  7 місяців тому

      siap pak, kebetulan saya belum punya alatnya 😂

  • @asepdadangsepriawansepriaw1789
    @asepdadangsepriawansepriaw1789 2 роки тому

    Trimakasih atas Tutorialnya Mas. Saya mau tanya : yang dipake untk ground itu apakah bisa besi ukuran 8 mm atau 12 mm ?. Dan kalo diberi lilitan kabel tembaga itu gimana ?. Ukuran resitensi Ground stadar itu brapa OM ?.

    • @siroedhiekreasi
      @siroedhiekreasi  2 роки тому +1

      Terima kasih kembali. untuk ground rod tidak bisa menggunakan besi Pak 🙏. karena antara besi dan tembaga memiliki hambatan jeenis yg berbeda dan material besi kurang baik menghantarkan arus. Seperti yg saya sampaikan dalam video, nilai resistansi sesuai standar PUIL adalah lebih kecil atau sama dengan 5 Ohm. Semakin mendekati 0 ohm akan semakin baik

    • @regystacy4887
      @regystacy4887 2 роки тому +1

      Bantu jawab pak, saya pernah tanam ground pake besi, waktu itu pake potongan besi D16, ujung nya dililit kabel. Jika tanahnya adalah bekas rawa yang ditimbun, maka untuk penanaman titik grounding yang baik, tanah timbunan harus dikupas dulu. kebetulan waktu itu di proyek, jadi timbunan tanah sekitar 3m dikupas, lalu besi tersebut ditanam dan diurug kembali. kabel pakai 16 mm2, dapat resistansi sekitar 0.5 Ohm - 1.5 Ohm. namun utk hal yang pasti, sebaiknya pakai copper rod.

    • @badartsani8841
      @badartsani8841 2 роки тому

      Besi boleh juga dipakai sebagai grounding rod, asalkan disesuaikan ukurannya dan dilapis galvanis/sepuh tembaga. Sudah ada standar yg mengatur berbagai ukuran grounding rod menurut bahan materialnya. Klo besi lapis tembaga klo tidak salah minimal 15mm diameter.

  • @ethonnuga2405
    @ethonnuga2405 3 роки тому

    Maaf mas mau tanya untuk mengukur grounding apa harus sejajar dengan tembok atau boleh arah depan dari tembok rumah,,,

    • @siroedhiekreasi
      @siroedhiekreasi  3 роки тому

      tidak mesti kawan, bebas aja. yang penting nilai resistansi pentanahannya sesuai dengan yg dipersyaratkan PUIL 🙏

  • @budiwiro8487
    @budiwiro8487 2 роки тому

    Maaf ,,,klo pembuatan grounding banyak caranya,,yg sy sarankan cari lokasi disekitar gedung yg tanahnya lembab lebih bagus yg ber air.Klo di area yg tandus /kering tanahnya keras ada bahan campuran yg digunakan spy tanahnya lembab dan lembek, maaf gak sy sebut bahannya.Utk mencapai nilai 0, sebetulnya mudah tp banyak yg gak ngerti caranya,,grounding petirpun sama,,nilai yg bagus dibawah 0, klo hanya sekedar syarat ada grounding gampang aja ,,,pake kabel BC 25,/16, jg bisa

    • @siroedhiekreasi
      @siroedhiekreasi  2 роки тому

      Alhamdulillah...terima kasih sharing ilmu dan pengalamannya Pak. Sangat mencerahkan 🙏

    • @rahmatpkytimur4880
      @rahmatpkytimur4880 2 роки тому

      Jadi gmna caranya mas utk dpt tahanan di bawah 5 ohm..bisa minta masukan nya
      Rencana nya saya mau pasang root 2 titik Kedalaman 8 meter pake bc 10 mm ..apakah ada cara yg lebih efektif 🙏

    • @manoeng
      @manoeng Рік тому

      @@rahmatpkytimur4880 Gunakan Bahan Semen Grounding...Bisa Bentonite atau Bahan Lainnya.

  • @deninav156
    @deninav156 3 роки тому

    Ilmunya sangat membantu, InsyaAllah berkah Pak.
    Kalau tester pakai multimeter tekiro MS-DM1908, apakah bisa?

    • @siroedhiekreasi
      @siroedhiekreasi  3 роки тому +1

      Amin... kalau untuk mengukur tahanan pentanahan tidak bisa menggunakan multimeter Pak 🙏. Alat ukurnya earth tester seperti yg saya gunakan dalam video ini 🙏

    • @deninav156
      @deninav156 3 роки тому

      @@siroedhiekreasi berapa nilai tahanan grounding yang tepat khusus untuk mesin Cnc Pak?

    • @siroedhiekreasi
      @siroedhiekreasi  3 роки тому +1

      @@deninav156 seperti yg saya sampaikan dalam video ini, nilai tahanan pentanahan sesuai standar PUIL adalah lebih kecil atau sama dengan 5 Ohm. Tapi kalau bicara ideal, nilai tahanan pentanahan yg paling kecil mendekati Nol Ohm yang lebih baik Pak 🙏

    • @siroedhiekreasi
      @siroedhiekreasi  3 роки тому +1

      @@deninav156 di beberapa perusahaan, mensyaratkan nilai pentanahan harus 0,2 Ohm, tapi nilai tersebut perlu biaya yg lumayan mahal Pak 🙏

    • @wachanel1721
      @wachanel1721 2 роки тому

      @@siroedhiekreasi biaya yg mahal maksudnya gimana pak. Apakah ada komponen tambahan?

  • @Nezukokmd
    @Nezukokmd Рік тому +2

    Pak apakah ada sumber referensi , apabila grounding petir tidak boleh menyatu dengan grounding instalasi ?

    • @ucupbintangtoedjoe4489
      @ucupbintangtoedjoe4489 Рік тому

      Mudahnya pahami apa itu gronding dulu insyaallah nanti pinter dengsn sendirinya

  • @amirudincrane
    @amirudincrane 2 роки тому

    Mau Nanya Pak l,Pemasangan Ground Anti Petir di tanam dalam rumah Atau Diluar rumah grounding nya,Trus cara pemasangan nya apa sama Rumah 3 tingkat , Mohon Penjelasan nya ,🙏🙏🙏

    • @siroedhiekreasi
      @siroedhiekreasi  2 роки тому

      dipasang di luar rumah Pak, carampemasangannya sama persis seperti yg ada dalam video. Dan nilai resistansi pentanahan semakin mendekati 0 ohm akan semakin baik

  • @zulkarnaintan8794
    @zulkarnaintan8794 2 роки тому +1

    Jangan pakai Tang buat kencangin bautnya. Pakai kinci Ring

    • @muhammadsukma9199
      @muhammadsukma9199 Рік тому

      Kumci ring ga bisa masuk itu kalo lewat bawah enak nya pake kunci pas

  • @budionobudi8647
    @budionobudi8647 2 роки тому +1

    Pak mau Tanya apakah boleh kabel grounding Di tanam satu persatu dibawah stop kontak satu persatu, Dan apa resikonya terimakasih..

    • @siroedhiekreasi
      @siroedhiekreasi  2 роки тому +1

      boleh Pak, karena ada banyak model/ tipe pentanahan. Tapi yang perlu diperhatikan adalh nilai resistansi pentanahannya, apakah sesuai standar atau tidak. Karena kalau hanya sekedar kita pasang grounding dan tidak diukur, tidak ada jaminan apakah sistem groundingnya efektif atau tidak. 🙏

  • @wachanel1721
    @wachanel1721 2 роки тому

    Pak klw kabel yg dri grounroot nya itu apakah bsa langsung di sambungkan ke unit (alat medis) bukan ke panel listrik sprti di video. Dan satu lagi apa jenis kabel yg di gunakan? Dan berapa ukuran kabel yg disarakan? Terima kasih 🙏

  • @Taukahkamu92
    @Taukahkamu92 2 роки тому +1

    Maaf bang mau tanya,,. Atap rumah sya baja ringan, untuk menghindari bahaya, apakah bisa saya psang kabel grounding dari atap baja ringan ke tongkat grounding..?
    Terima kasih

    • @siroedhiekreasi
      @siroedhiekreasi  2 роки тому +1

      bisa Pak, dan pastikan resistansi pentanahan sesuai yg dipersyaratkan PUIL. Agar berfungsi ketika ada gangguan 🙏

  • @netasari5470
    @netasari5470 11 місяців тому +1

    Coba diukur pak, tegangan Phase to grounding brapa Volt?

  • @lologuegue2067
    @lologuegue2067 2 роки тому

    Maff bang numpang tanya klo pngukuran ga sesui gimana ??? Apa kita cabut lgi besi grondingya n kita pndah tmpat dn tancapkan lgi ???
    Efek apa klo grondingnya melebihi ukuran ohm apa vol td hehe??(mf lupa)
    Trimaksih.....

    • @siroedhiekreasi
      @siroedhiekreasi  2 роки тому

      kalau nilainya belum sesuai, kita tambah elektroda lagi bang, disambung secara paralel. Efeknya kalau resistansi pentanahan bernilai di atas 5 ohm ( besar), saat terjadi gangguan arus bocor maka manusia yg menyentuh peralatan akan kesetrum karena arus bocor tsb tidak bisa dialirkan secara maksimal ke bumi. Penjelasan secara teoritis ada di video saya yg lain dengan judul "Bahaya Instalasi Listrik Tanpa Grounding"

  • @abumuhammad966
    @abumuhammad966 2 роки тому

    Bang root elektrodaYG ditanam bahan tembaga asli BKN y? Atau sepuhan tembaga?
    Kl misalkan kita tes dgn avo meter PHASA dengan GROUND dgn hasil tegangannya sama dengan PHASA dgn NETRAL, apakah ini sdh menandakan ground SDH bgs?

    • @siroedhiekreasi
      @siroedhiekreasi  2 роки тому

      Yang saya gunakan dalam video ini bahan tembaga asli bang. untuk mengetahui nilai resistansi pentanahan kita gunakan alat ukur earth tester, tidak bisa menggunakan avometer

  • @hartonolubis1559
    @hartonolubis1559 3 роки тому

    Ajarin saya dong pak

  • @madegusti2402
    @madegusti2402 2 роки тому

    Bekerja tanpa prosedur keselamatan kerja. Csra kerja yg sangat High risk

  • @freddypurnomo8722
    @freddypurnomo8722 Рік тому

    bang jika buat generator 1000w apakah perlu gensetnya di lengkapi rod grounding ?
    apa ada saran di beri rod ground berapa meter minimal terpendek ?

    • @siroedhiekreasi
      @siroedhiekreasi  Рік тому

      perlu bang, mengenai kedalaman rodnya relatif bang. yg paling penting resistansinya harus sesuai. maks 5 ohm, semakin mendekati 0 ohm semakin baik

  • @aditya-5893
    @aditya-5893 2 роки тому +1

    Untuk kabel grounding / penangkal petir....apakah bisa dimasukkan ke lubang pipa sumur air? Daripada pakai electroda..

    • @siroedhiekreasi
      @siroedhiekreasi  2 роки тому

      tetap pakai elektroda Pak, karena material yg digunakan (tembaga) dengan diameter tertentu dan nilai resistani lebih kecil atau sama dengan 5 ohm akan sangat berperan menyalurkan arus gangguan.

  • @muhwildan9418
    @muhwildan9418 2 роки тому

    mas mau nanya. utk grounding jalur listrik. kan jadinya L-N-G.(tiga kabel).
    trus apakah Grounding tersebut boleh disatukan ke body alat elektronika sebagai earthing.
    tapi satu titik grounding rod.

    • @siroedhiekreasi
      @siroedhiekreasi  2 роки тому

      bisa Mas, ada banyak model grounding. Kalau yang Mas tanyakan adalah grounding langsung ke peralatan. Adapun grounding dalam video ini adalah grounding sistem secara keseluruhan.

  • @mochamadridwan5998
    @mochamadridwan5998 2 роки тому +1

    untuk mencapai nilai 0 ohm apakah bisa? apakah batang rod dari bahan tembaga murni gak karatan ditanam dibawah tanah? usia batang rodnya berapa tahun ? berapa banyak biaya yg dikeluarkan untuk dapat menghasilkan resistansi 0 ohm?

    • @siroedhiekreasi
      @siroedhiekreasi  2 роки тому

      idealnya tahanan 0 ohm bisa dicapai, tapi pada kenyataannya memang sulit Pak. PUIL juga mensyaratkan dikisaran 0 sampai 5 Ohm. Rod yg ditanam tidak berkarat ( beda dengan besi) dan bisa digunakan selamanya, tapi tentunya harus ada pemeliharaan. Kalau resistansi berubah di atas toleransi, maka harus dilakukan penyesuiaan kembali.

  • @ahmadriyadi86
    @ahmadriyadi86 2 роки тому

    Hadir menyapa lur... mudah2an bisa bermanfaat & bisa saling bantu lur..🙏🙏🙏💯👍🙏🙏🙏👍👍👍👍

  • @indrakusuma2682
    @indrakusuma2682 2 роки тому +1

    pak mohon arahannya soal SOP pengukuran..
    pengukuran dengan earth tester bisa dilakukan setelah ground terkoneksi ke instalasi listrik atau bagaimana ya ?
    apa ketika arde di tancapkan sudah bisa langsung dilakukan pengukuran ?

    • @siroedhiekreasi
      @siroedhiekreasi  2 роки тому +1

      pengukurannya setelah elektroda kita tancapkan mas. sebelum terkoneksi ke instalasi listrik

    • @indrakusuma2682
      @indrakusuma2682 2 роки тому

      @@siroedhiekreasi baik, terima kasih ya pak...

    • @siroedhiekreasi
      @siroedhiekreasi  2 роки тому

      @@indrakusuma2682 sama sama

  • @naradzarwahyu2002
    @naradzarwahyu2002 2 роки тому

    Permisi pak mau tanya, sebelum dilakukan penanaman elektroda. Cara memilih jenis tanahnya bagaimana ya? Apa cukup kira2 saja yang dekat dengan sumur atau daerah resapan air atau ada cara2 standart nya?

    • @naradzarwahyu2002
      @naradzarwahyu2002 2 роки тому

      Pada saat saya baca kolom komentar. Untuk menurunkan nilai resistansi dilakukan penanaman elektroda tembaga lagi dengan jarak 1m, nah untuk panjang elektroda yang ke 2 ini berapa meter pak? Sama dengan elektroda pertama atau bisa lebih pendek?

    • @siroedhiekreasi
      @siroedhiekreasi  2 роки тому +1

      kita kira² saja Pak, tapi sebaiknya kalau memungkinkan kita pilih lokasi yg lembab/basah, agar mudah saat kita memasukkan elktroda.

    • @siroedhiekreasi
      @siroedhiekreasi  2 роки тому +1

      @@naradzarwahyu2002 panjangnya relatif, yang penting nilai resistansi terpenuhi sesuai standar PUIL (≤ 5 Ohm)

  • @riyan3yanto70
    @riyan3yanto70 2 роки тому

    Mau nanya gan, klo pasang gron di salurn air/got gimana y gan & itu yg di tanm namny ap y/ boleh pake besi ya gan,terimaksih..

    • @siroedhiekreasi
      @siroedhiekreasi  2 роки тому

      namanya elektroda pentanahan atau ground rod, tidak bisa pakai besi gan. ground rod itu terbuat dari material tembaga. boleh² aja pasang di saluran air, dannpastikan nilai resistansinya sesuai yg dipersyaratkan oleh PUIL 🙏

  • @yogial-fa4289
    @yogial-fa4289 Рік тому

    Ada baiknya pakai helm bang , yg nonton agak khawatir 😅 palu takut lepas..waktu pukul ground Rod nya