How to reduce the grounding resistance value according to PUIL standards

Поділитися
Вставка
  • Опубліковано 5 гру 2022
  • The grounding system or better known as grounding is a very important component in electrical installations, because grounding functions as protection when leakage current occurs in equipment, so that humans who touch the equipment will be safe from electric shock.
    In accordance with the requirements of PUIL (General Electrical Installation Regulations), the grounding resistance value must be less than or equal to 5 Ohms and anything above this value cannot be tolerated.
    In reality, the installed grounding resistance value does not match what is required by PUIL (above 5 Ohms), therefore efforts need to be made to reduce the grounding resistance value.
    In this video, we will learn how to reduce the grounding resistance value and continue with the measurement process using an Earth Tester measuring instrument.
    Hopefully this video is useful for creative friends who are learning about electrical systems. If you have questions or input, please write them in the comments column. Thank you for your support and support for the Siroedhie Kreasi channel...
    @siroedhiekreasi
    #GroundingResistance #PUIL #EarthTester #GroundingResistance #siroedhiekreasi​

КОМЕНТАРІ • 60

  • @suwitokiman201
    @suwitokiman201 Місяць тому +1

    Jelas dan simpel sehingga mudah dipahami. Thx atas sharingnya.

  • @radityarohmat6797
    @radityarohmat6797 4 місяці тому

    Maksih bos ilumnya.smoga bermanfaat

  • @TukangListrikAmatiran
    @TukangListrikAmatiran Рік тому +1

    Thanks ilmu nya

  • @siapaagung4979
    @siapaagung4979 4 місяці тому

    Keren pak Rudi ilmu nya bisa di cerna semua..... sangat bermanfaat pak

  • @user-uy1uc2ix8w
    @user-uy1uc2ix8w 8 місяців тому

    Terimakasih ilmunya bapak , semoga jadi amal jariah 👍

  • @rafifahaura4547
    @rafifahaura4547 9 місяців тому

    Mantap master, terima kasih ilmunya, semoga menjadi amal

    • @siroedhiekreasi
      @siroedhiekreasi  9 місяців тому

      Amin...semoga bermanfaat

    • @wawansetiono6529
      @wawansetiono6529 7 місяців тому

      ​@@siroedhiekreasiBang saya ngak punya alat earth tester. Apakah bahaya kalau tegangan tidak sesuai

    • @wikanatmojo8447
      @wikanatmojo8447 5 місяців тому

      ​@@siroedhiekreasikalo earth voltage nya tidak aman faktor- faktor penyebabnya apa pak, dan penanganannya gimana

    • @siroedhiekreasi
      @siroedhiekreasi  5 місяців тому

      @wikanatmojo8447 tidak aman bila nilai resitansi pentanahan lebih besar dari 5 ohm. arus gangguan akan sulit disalurkan ke tanah

  • @bagongcupang
    @bagongcupang Рік тому +1

    panel listrik sound sistem 1 phase omm

  • @manoeng
    @manoeng Рік тому +1

    Pengalaman Saya Elektroda Bantu Tergantung Dari Situasi Tanah Dilokasi, Mungkin Untuk Lokasi Tanah Yang Baik Panjang 20-30 Cm Cukup Membantu, Tetapi Jika Di Tanah Pasir Berbatu Halus Sangat Sulit Alat Ukur Pasti Akan Membaca Nilai Resistansi Yang Sangat Besar Sementara Kedalaman Rood 18 Meter, Akhirnya Saya Menggunakan Elektroda Bantu Dari Material Besi Galvanize Sepanjang 2 Meter.....

    • @siroedhiekreasi
      @siroedhiekreasi  Рік тому +2

      terima kasih sharing pengalamannya Pak 🙏. Saya juga masih belajar dan pengen berbagi sedikit yg saya tahu

    • @elrumy5176
      @elrumy5176 Рік тому +2

      Jarak antar elektroda brp mas....

    • @manoeng
      @manoeng Рік тому +2

      @@siroedhiekreasi Sama Sama Pak......

    • @yudirudiat6499
      @yudirudiat6499 Рік тому +1

      Grounding kok pakai galvanis om

  • @totetamtoti2443
    @totetamtoti2443 Рік тому +1

    di tempat saya pegunungan tanah lembab dalamnya 1,5 meter, nilainya gede 300 ohm,

  • @aghnatkurniadharmawan3102
    @aghnatkurniadharmawan3102 Місяць тому

    di Point mana ya yang menyebutkan nilai 5 ohm pada PUIL?
    Terimakasih

  • @ahmadsulkifli5840
    @ahmadsulkifli5840 Рік тому +1

    Itu besi yg ditanam, klo cuman 1 az gimana, klo ditanam di dlm rumah sebelum di bangun ap efek nya, (buat instalasi grounding rumah 1300 wat), ...🙏

    • @siroedhiekreasi
      @siroedhiekreasi  Рік тому +1

      materi ini adalah cara menurunkan nilai resistansi pentanahan, kita buat 3 buah elektroda yg dihubung paralel agar terlihat bahwa huhungan paralel akan menurunkan nilai resistansi. dimana sesuai PUIL harus bernilai lebih kecil atau sama dgn 5 ohm.

    • @siroedhiekreasi
      @siroedhiekreasi  Рік тому +1

      di video saya yg lain ada saya buatkan cara memasang grounding memggunakan satu buah elektroda. ua-cam.com/video/xK96_XmyMH0/v-deo.html

  • @AhmadFauzi-my5uh
    @AhmadFauzi-my5uh Рік тому

    Kalau mau ukur sambungan ke panel nya dilepas dulu?

  • @Ariaditama
    @Ariaditama 6 місяців тому

    Panjang elektroda utama yg di pararel di tanam berpa panjanynya pak?

  • @rafifahaura4547
    @rafifahaura4547 9 місяців тому

    Untuk daya 13200 pakai batangan groudroof brapa mili besaranya dan panjang untuk kedalamanya brapa meter grounding utama, berikut tambahan groudroof

    • @siroedhiekreasi
      @siroedhiekreasi  9 місяців тому

      minimal menggunakan ukiran 25 mm pak, lebih besar akan semakin baik. kedalaman ewlektroda sangat relatif. Tambahan grounrod bila nilai resistansi di atas 5 Ohm

    • @rafifahaura4547
      @rafifahaura4547 9 місяців тому

      Terima kasih master, atas ilmunya semoga semangkin sukses

  • @aingsukarto3378
    @aingsukarto3378 9 місяців тому

    bang mau tanya kalau tidak punya alat ukur khusus bagaimana solusinya apakah bisa pakai multitester atau ada metode lain .terima kasih

  • @nurmuhammadhidayatullah4780
    @nurmuhammadhidayatullah4780 Рік тому +1

    Mau tanya mas.kalau nilai resistansi y di atas 5 bahanya apa mas?

    • @siroedhiekreasi
      @siroedhiekreasi  Рік тому +1

      nilai resistansi yg besar ( di atas 5 ohm) akan menyebabkan arus gangguan sulit dialirkan ke tanah dan akan membahayakan manusia yg menyentuh objek yg mengalami gangguan

  • @Its-Khy_JustNada
    @Its-Khy_JustNada Рік тому +1

    Kalu di tanah berbatu kapur apa bisa

    • @siroedhiekreasi
      @siroedhiekreasi  Рік тому +1

      bisa pak, bisa menggunakan bor. tapi memang agak sulit pengerjaannya

  • @ilhamjanuar5510
    @ilhamjanuar5510 9 місяців тому

    7:59 Maaf mas bukannya kalo rangkaian paralel seharusnya ambil penyambungannya dari elektroda utama ya seperti system T dan system F? Kalo dari elektroda kedua bukannya disebut rangkaian seri? Mohon pencerahannya, terima kasih🙏

    • @siroedhiekreasi
      @siroedhiekreasi  9 місяців тому

      bukan mas, karakter rangkaian seri ketika dijumlahkan resistansi akan bertambah besar. Sementara karakter rangkaian paralel ketika dijumlahkan nilai resitansi akan semakin kecil seperti terlihat pada video ini 🙏

  • @aktsarabdikar636
    @aktsarabdikar636 Рік тому +1

    diparalelkan minimal dengan kabel bc berapa ya?

  • @rasaudio5453
    @rasaudio5453 2 місяці тому

    minimal brpa meter batang besi yg di tanam pak🙏

    • @siroedhiekreasi
      @siroedhiekreasi  2 місяці тому

      Relatif Pak, tergantung struktur tanah. Elektroda panjang total 4 meter

  • @memed2075
    @memed2075 Рік тому

    estimasi biaya bikin grounding pln brp mas?

  • @taftazani4521
    @taftazani4521 Рік тому +1

    Berapa kedalaman elektroda utamanya mas? Dan berapa juga kedalaman elektroda bantu yg terpasang itu mas?

    • @siroedhiekreasi
      @siroedhiekreasi  Рік тому +1

      @@yohanesputra7913 luar biasa nih Pak, saya harus banyak belajar sama Pak Yohanes 🙏

    • @siroedhiekreasi
      @siroedhiekreasi  Рік тому +1

      di video ini kita belajar cara memperkecil nilai resistansi pentanahan bila tidak diperoleh nilai sesuai standar PUIL, adapun kedalaman elektroda utama seperti yg disampaikan Pak Yohanes. untuk elektroda bantu 20 cm seperti yg terlihat dalam video ini

    • @siroedhiekreasi
      @siroedhiekreasi  Рік тому +1

      @@yohanesputra7913 Terima kasih Pak Yohanes, sudah berbagi ilmu dan pengalaman. Semoga Pak Yohanes dan keluarga sehat² selalu ya Pak 🙏

  • @hansisyd9943
    @hansisyd9943 Рік тому +1

    Berapa jarak min antar batang groundnya ?

    • @siroedhiekreasi
      @siroedhiekreasi  Рік тому +1

      minimal bisa kita kasih jarak 1 meter pak, maksimal 5 meter

    • @hansisyd9943
      @hansisyd9943 Рік тому

      ​@@siroedhiekreasi Batang ground jika timbul seperti itu aman? Atau perlu di timbun sampai tidak terlihat?

    • @siroedhiekreasi
      @siroedhiekreasi  Рік тому

      @@hansisyd9943semestinya ditimbun, karena ini untuk contoh jadi gak kita timbun. untuk proses pemasangan yg sebenarnya ada di video saya yg lain. ini linknya ua-cam.com/video/xK96_XmyMH0/v-deo.html

  • @imam9585
    @imam9585 Рік тому

    Elektora batu itu bahannya apa kak

  • @adekgarbi6211
    @adekgarbi6211 Рік тому +1

    Kalau kita butuh, berapa biaya pengukuran pak?

    • @siroedhiekreasi
      @siroedhiekreasi  Рік тому +2

      biaya tergantung dari nilai resistansi yg diinginkan Pak, semakin kecil mendekati nol Ohm maka semakin mahal

    • @siroedhiekreasi
      @siroedhiekreasi  Рік тому +1

      @@yohanesputra7913 terima kasih Pak Yohanes atas dukungan dan supportnya untuk channel yg masih seumur jagung ini 🙏🙏🙏

    • @siroedhiekreasi
      @siroedhiekreasi  Рік тому

      @@yohanesputra7913 Amin 🙏

    • @adekgarbi6211
      @adekgarbi6211 Рік тому +1

      @@yohanesputra7913 terimakasih pak